B
C
Abb. 21.1.3. EX1 controller zones
B
Connector
Contactor No.
Contactor name
Functional block name
miniEX1
X19
1
AI1 (0-10V)
A1-Supply air CO
2
or RH (input 0-10VDC)
2
GND
3
24VDC
X20
1
GND
Electric/Water heater control (output 0-10VDC)
2
AO1 (0-10V)
3
GND
Hydraulic heater water temperature sensor
4
AI2 (NTC)
X21
1
DO1
Working indication output (START). 24VDC; 1,2W max.
2
24VDC
3
DO2
Alarm indication output (STOP). 24VDC; 1,2W max.
4
24VDC
C
Connector
Contactor No.
Contactor name
Functional block name
miniEX1
X23
1
DI1
Electric heater manual protection (NC)
2
12VDC
3
DI2
Electric heater automatic protection (NC)
4
12VDC
5
DI3
Filter relay/Fire place I, DI (NC)
6
12VDC
7
DI4
Filter relay/Fire place II, DI (NC)
8
12VDC
21.2. FIRE PROTECTION SIGNAL INPUT (FIRE PROTECTION INPUT (NC))
Fire protection signal input must be normally closed, until the fire protection system is not connected a jumper is installed in the factory.
Automation controller A zone X4.