23

Smarty 4X V

www.salda.lt

This function is designed to maintain a proper quality of room air. To activate it the exhaust air CO

2

 sensor must be connected and properly configured 

in the service environment window SERVICE › SENSORS. When completed, the exhaust air CO

2

 value is displayed in the section MONITORING.

In the service environment window SERVICE › MAIN › CO

2

 REDUCTION FUNCTION you can switch on/off the function, indicate preferred CO

2

 level 

and allowable limit; when it is exceeded (CO

2

 set + allowable excess) CO

2

 is reduced, information is displayed and air-flow is increased. When CO

reaches the set point, reduction is switched off.

CO

2

 protection is inactive in the stand-by and building protection modes.

In the service environment section SERVICE › MAIN › PASSWORD › PASSWORD CHANGING MODE › ON you can change login passwords. For 

this it is necessary to activate the change and after entering a preferred password (4 digits), click a button SET. To review and change the parameters 

without a password, just set 0.

If set parameters result in incorrect operation of the system, you can always restore the factory defaults in the service environment window SERVICE 

› MAIN › FACTORY SETTINGS.

› Shut down the system;

› Run the supplied air fan at full speed and shut down the exhausted air fan;

› Run the exhausted air fan at full speed and shut down the supplied air fan;

› Run the supplied and exhausted air fan at full speed.

The preferred air-flow can be indicated in percentage or in 4 fixed speeds where each of them is dedicated to a relevant system mode:

› Building protection;

› Economy;

› Comfort;

› Maximum power.

Fan speed can be controlled by:

› Percentage - speed in percentage is indicated in the adjuster environment window ADJUSTER › AIR FLOWS ADJUSTING: 0 % corresponds to 

0, and 100 % – 10 V control signal voltage;

› Pressure - the maximum system pressure is indicated, which based on speed settings in the adjuster environment ADJUSTER › AIR FLOWS 

ADJUSTING means 100 % air-flow;

› Air-flow (m

3

/h) - K factors of supply and exhaust air and the maximum system air-flow (m

3

/h) are displayed, which based on speed settings in the 

adjuster environment ADJUSTER › AIR FLOWS ADJUSTING means 100 %.

Fans based on air-flow and pressure are controlled by PID controller and its coefficients are indicated in the adjuster environment section ADJUSTER 

› PID CONTROLLERS ADJUSTING › FANS SPEED CONTROL BY AIR FLOW OR PRESSURE. Every fan is controlled individually.

In the service environment window SERVICE › FANS › FANS SPEED CONTROL you can limit the minimum and maximum fan control signal voltage. 

Based on manufacturer set parameters, the minimum 2V voltage is indicated, which means that 0V voltage signal is sent when fans are off, and 2V 

voltage signal is immediately switched on when rotation is required.

It is possible to specify the nominal flows of supply and exhaust air. Then, the maximal air flow is calculated automatically.

The following can be connected to the system:

› Supply/exhaust air dampers (On/Off, 3P or Open/Close type). They are opened prior to starting the fans and closed after their shutdown;

› Recirculation dampers that are used for heat exchanger frost protection, maintaining of temperature and full recirculation function;

› Fire dampers with one or two limit switches. They are controlled in the same way as supply/exhaust dampers, except for cases when testing 

function is active or fire protection is activated.

If On/Off, 3P or Open/Close type damper is indicated, proper opening time must be indicated. On/Off type damper control:

› When it is necessary to open, OPEN signal is activated;

› It is necessary to wait until it opens and fans are started;

› OPEN signal is activated during the entire operation time;

› When shutting down the system, it is necessary to wait for 10 s, until the fans stop rotating and switch off the OPEN signal.

3P type damper control:

› When it is necessary to open, OPEN signal is activated;

› Waiting until it opens, OPEN signal is switched off and fans are started;

› OPEN and CLOSE signals are switched off during the entire operation time;

› When shutting down the system, it is necessary to wait for 10 s, until the fans stop rotating and activate the CLOSE signal for an indicated time 

period.

Open/Close type damper control:

› When it is necessary to open, OPEN and CLOSE signals are activated;

› It is necessary to wait until it opens and fans are started;

› OPEN and CLOSE signals are activated during the entire operation time;

› When shutting down the system, it is necessary to wait for 10 s, until the fans stop rotating and switch off the OPEN signal (CLOSE remains 

active) for an indicated time period.

Содержание Smarty 4X V

Страница 1: ...Subject to technical modification Smarty 4X V_P0115_AZ_0002 AHU WITH HEAT RECOVERY Smarty 4X V User s and service technical manual...

Страница 2: ...tac tor 22 1 27 CO2 Reduction Function only using additional extract air CO2 sensors 23 1 28 Changing Passwords 23 1 29 Restoring Factory Defaults 23 1 30 Fan Control 23 1 31 Damper Control 23 1 32 He...

Страница 3: ...cal data 5 Units number 6 Web address All units are packed in the factory to withstand regular conditions of transportation Upon unpacking check the unit for any damages caused during transportation I...

Страница 4: ...unit s and its components edges may be sharp and cutting Do not wear loose clothing that could be entangled in to operating unit Do not place fingers or other foreign objects through inlet or exhaust...

Страница 5: ...arty 4X V 1 1 Mini MCB Premium Smarty 4X V 1 2 Mini MCB Basic Advanced Smarty 4X V are available in three versions Unit is designed to operate only indoors It is forbidden to use the unit in potential...

Страница 6: ...solvents that may scratch or damage housing and impeller Do not plunge the motor into any fluid while cleaning impeller Make sure that impeller s balance weights are not moved Make sure the impeller...

Страница 7: ...re connected When there is a folt in fans motor any separate notice is shown on the control panel Unplug fan control connector from the control board Connectors are the same for the both fans X2 X4 Di...

Страница 8: ...bmerge it into a bath and wash with warm soapy water do not use soda Then rinse it with weak hot water stream too strong stream can fold the plates Place back the heat exchanger only when it is comple...

Страница 9: ...tic control system of the air handling unit Power plug socket shall be installed at a distance to ensure unstrained power cable of the unit Standard length of the unit power cable shall be 2 5 m long...

Страница 10: ...E the remote control panel shall be connected and or disconnected only after disconnecting power supply to HVAC unit Electrical equipment connection to the control board terminals Control board connec...

Страница 11: ...0 10 protection class IP54 Supply air fan phase voltage 50 Hz VAC 1 230 power current kW A 0 21 0 92 speed min 1 4400 control input VDC 0 10 protection class IP54 Total power consumption power curren...

Страница 12: ...Pa V l s V m h 3 Pstat Pa V l s V m h 3 Specific fan power SFP 700 600 500 400 300 200 100 0 80 85 90 95 194 167 139 111 83 55 28 0 0 100 200 300 400 500 600 700 0 0 200 400 600 800 1000 1200 1400 25...

Страница 13: ...salda lt Possibility to insert coupling of corresponding diameter 150 mm 160 mm 252 mm 224 mm 386 mm 110 mm 265 mm 110 mm 113 mm 116 mm 170 mm 80 mm 810 mm 900 5 mm 599 mm 406 mm G3 8 538 mm 284 mm 1...

Страница 14: ...ntenance door and filter covers If the installed ventilation unit is adherent to the wall it may transmit noise vibrations to the premises Though the level of noise caused by the fans is admissible it...

Страница 15: ...nd power network plug socket distribution devices Prior to carrying out any ventilation unit installation and connection activities until its hand over to the customer the unit must be disconnected fr...

Страница 16: ...not exceed 2 Nm Pipe 3 metal pipe should be connected with G3 8 elbow plastic pipe with G3 8 elbow or rubber hose with strap if the unit is placed on the legs in other cases condensate hose can be con...

Страница 17: ...DJUSTER USER SETTINGS ECONOMY MODE TEMPERATURE or USER MENU SETTINGS ECONOMY MODE Comfort mode is running when people are present in the premises The system operates at speed 3 In this mode the temper...

Страница 18: ...time mode and week day is indicated The system changes modes according to the Weekly Schedule only when the indicated time comes therefore a user can always change the existing mode manually This sche...

Страница 19: ...her than the set outdoor temperature Exhaust air temperature is higher than the set temperature Exhaust air temperature is higher than the outdoor temperature by at least 2 C Summer If all conditions...

Страница 20: ...tem stopped A 28 Alarm Hydronic heater water temperature sensor failure System stopped A 29 Alarm Hydronic pre heater water temperature sensor failure System stopped A 30 Alarm Hydronic cooler water t...

Страница 21: ...time speed of fans temperatures pressure etc The amount of information de pends on the system configuration This tool is designed for preventive maintenance of the system This function is designed to...

Страница 22: ...is on PIR sensor When the sensor is activated the selected system mode is activated If the signal is not received for 30 minutes the mode is acti vated Function is set in the service environment sect...

Страница 23: ...are controlled by PID controller and its coefficients are indicated in the adjuster environment section ADJUSTER PID CONTROLLERS ADJUSTING FANS SPEED CONTROL BY AIR FLOW OR PRESSURE Every fan is contr...

Страница 24: ...the rotor Heating of outdoor air using a preheater Suspension of the supply air flow Shutting down of the unit according to the low supply air temperature by default the limit is 5 C Shutting down of...

Страница 25: ...m the fan speed is reduced When the manual protection is activated the heater and its power circuit are disconnected a warning is shown and the indicated action is performed According to the factory s...

Страница 26: ...be connected to the third 0 10 VDC input For each input the sensor voltage interval 0 10 V 1 10 V 0 5 V 0 6 2 7 V 0 3 3 V and the minimum and maximum values are indicated for each input Types of temp...

Страница 27: ...air fan M3 Exhaust air damper actuator FLEX MCB Control panel TE Exhaust air temperature sensor shall be ordered separately M1 ByPass motor TL Outdoor air temperature sensor Stouch Control panel PF F...

Страница 28: ...PE EKA NIS or EKA Electric preheater TL Outdoor air temperature sensor Stouch Control panel PF Filter for supply air G4 F7 optional PC Personal computer M1 ByPass motor MBGateway Net module CEE7 7 Po...

Страница 29: ...linija pa ym tus komponentus ir kabelius pajungia SALDA arba vartotojas Components and cables marked with the dash line connected by SALDA or customer Bypass actuator for versions 1 1 and 1 2 Bypass p...

Страница 30: ...EX1 module power control X22 1 I2C_SCL X22 2 I2C_SDA X22 3 GND X22 4 2 5VDC X22 5 3 3VDC X22 6 12VDC X22 7 24VDC X22 8 GND miniEX1 V0 2 Electrical preheater DI5 automatic protection DI6 manual protect...

Страница 31: ...L1 M3 Vin GND AO1 Transmitter 1 System mode switch Fan speed switch 32 30 31 J3 J4 33 Extract air CO2 or RH input 0 10VDC TE Optional Extract air temperature sensor X7 5 AI4 0 10V X7 6 GND X7 7 24VDC...

Страница 32: ...D Aleksandravi ius EI A klenikas Pyn l SMARTY ZP3XV 0k 221 1007 0 1 1 PS 0k Principal connection scheme 6 01 2015 11 19 2015 11 19 2015 11 19 1 2 3 4 5 6 X25 7 8 794941 1 Bypass actuator motor 24 B B...

Страница 33: ...0k Principle connection scheme 8 01 2015 11 24 2015 11 24 2015 11 24 1 2 3 4 5 6 X25 7 8 794821 1 1 2 3 4 5 6 X3 KF2EDGKD 2 5 6P 1 2 3 4 5 6 X5 7 8 KF2EDGKD 2 5 8P 1 2 3 4 5 6 X29 7 8 794821 1 X12 KF2...

Страница 34: ...9 2017 05 09 2017 05 09 BK Black Juodas BN Brown Rudas GY Grey Pilkas WH White Baltas BU Blue M lynas RD Red Raudonas GN YE Green Yellow alias Geltonas 48VDC 0 10V Tacho GND 48VDC 0 10V Tacho GND PV I...

Страница 35: ...230V Max 2kW 230V X12 1 PE X12 2 N L1 X12 3 DO2 L L2 N2 miniMCB V0 3 01 6 3 X2 5 GND X2 6 AO3 0 10V N2 miniMCB V0 3 01 5 3 External preheater Control 0 10V Power over 2kW 2f 400V K1 A1 A2 230VAC 11 14...

Страница 36: ...erating No supply voltages Check whether the device is connected to the plug socket Two pole protection device is off or a current leakage relay is active if installed by the in staller Switch on only...

Страница 37: ...0 10V 24VDC_P STEP_B STEP_B STEP_A STEP_A 24VDC_P 3 3V_1W DI4 TACHO2_K DI3 TACHO2_A TACHO1_K DI2 TACHO1_A DI5 12VDC DI6 12VDC DI7 12VDC 12VDC DI8 AI4 NTC GND GND AI3 NTC GND AI2 NTC GND AI1 NTC DI9 3...

Страница 38: ...ntrol 2 STEP_B 3 STEP_B 4 STEP_A 5 STEP_A 6 24VDC_P X4 1 DI2 TACHO1_A Supply fan speed RPM 2 TACHO1_K 3 DI3 TACHO2_A Extract fan speed RPM 4 TACHO2_K 5 DI4 Fire protection input NC 6 3 3V_1W X5 1 DI5...

Страница 39: ...D 3 PE X10 1 PE Electric Water Heater power line circulation pump max 0 6kW 2 DO1 L L2 _2 3 N L1 _2 X11 1 N L1 _2 230VAC Power supply for X10 and X12 2 L L2 _2 3 PE X12 1 PE Preheater power line max 2...

Страница 40: ...ector Contactor No Contactor name Functional block name miniEX1 X19 1 AI1 0 10V A1 Supply air CO2 or RH input 0 10VDC 2 GND 3 24VDC X20 1 GND Electric Water heater control output 0 10VDC 2 AO1 0 10V 3...

Страница 41: ...in the factory Automation controller A zone X4 In product versions 1 1 pre heater is integrated inside the product In product versions 1 2 and 1 3 pre heater is integrated on the outdoor air channel P...

Страница 42: ...alled inside supply air duct Wiring diagram Automation controller B zone X19 Supply air CO2 or RH input 0 10VDC 24VDC GND 1 2 3 AI1 0 10V Vin GND AO1 Transmitter 2 Extract air CO2 or RH input 0 10VDC...

Страница 43: ...duct Tool for drilling holes are required for its installation CO 2 concentration ppm 3000 Effect on an individual 2500 2000 Reduced concentration drowsi ness headache etc 1500 1000 Pettenkofer limit...

Страница 44: ...r duct Arrangement based on air direction Electric Heater Supply Air Sensor TJ KE Mini MCB TJ Wiring diagram On Off heater connection Automation controller D zone X10 and C zone X23 This control metho...

Страница 45: ...inside air duct Arrangement based on air direction Electric Heater Supply Air Sensor TJ Wiring diagram 0 10V heater connection Automation controller B zone X20 connector 12VDC DI2 DI1 12VDC DI4 DI3 1...

Страница 46: ...02 2016 06 16 2016 06 16 2016 06 16 PE L N KE1 X10 1 PE X10 2 DO1 L L2 X10 3 N L1 miniMCB V0 2 X10 1 PE X10 2 DO1 L L2 X10 3 N L1 miniMCB V0 2 K1 1 2 3 4 5 6 K1 A1 A2 X5 1 DI5 X5 2 12VDC X5 3 DI6 X5...

Страница 47: ...sportation system Settings with the FLEX MCB control panel 1 Go to Menu Service Heaters Enter the password the initial password 4444 2 Select Control Position in the settings Heater on basic or Pre he...

Страница 48: ...ller F zone X18 connector Switch positions for X18 connector configuration Switch Position Purpose S2 1 A Y RS422 RS485 2 B Z RS422 RS485 3 120R line termination resistor 4 1kR line pull up resistor 5...

Страница 49: ...MCB power indication LED3 3 3V miniMCB power indication ON mode LED4 MiniMCB status LED LED5 Communication line Transmit indication LED6 Communication line Receive indication LED7 24V peripheral POWER...

Страница 50: ...T0049 Channel humidity transmit ter S KFF U ZAKKT0051 Humidity transmitter S RFF U D F2 ZAKKT0050 Remote control panel with rj45 cable Stouch PRGPU051_rj45 Net module MB Gateway GAUMBGATEWAY001 Switch...

Страница 51: ...5x180x25 G4 with band MPL Z ZFEPF121 Filer 475x134x25 F7 with band MPL ZFEPF119 optional Condensate pump MAXI BLUE SET PRGSIK002 Siphon Siphon D20 GKIS001 Legs Smarty legs GAGKSMARTY168_1004 Supply an...

Страница 52: ...or Door GPUD232_1028_0 Heat exchanger Heat exchanger ZSLPLGS0023 Supply extract air fan Fan GPUVM224_1068_1068 Supply extract air fan Fan GPUVM224_1030_1030 Supply extract air fan Fan GPUVM224_1031_10...

Страница 53: ...ge and permission has been upgraded or unskilled repairs were made 3 4 when the unit was used not for its original purpose 4 This warranty does not apply at these malfunction cases 4 1 mechanical dama...

Страница 54: ...tion Fan cleaning Once a year Heat exchanger cleaning Once a year Filter replacement Every 3 4 months NOTE The purchaser is required to fill in the Product maintenance table 2 At least 2 Look at the p...

Отзывы: