11
Smarty 4X V
www.salda.lt
NOTE. Subject to technical modification
Technical data
W
According to EN 13141-7 standard.
Smarty 4X V
Exhaust air filter
class
G4
width
L [mm]
475
height
H [mm]
180
depth
W [mm]
25
model
MPL
Supply air filter
class
G4/(F7 - optional)
width
L [mm]
475
height
H [mm]
134
depth
W [mm]
25
model
MPL
Smarty
4X V 1.1
4X V 1.2
Exhaust air fan
phase/voltage
[50 Hz/VAC]
~1/230
power/current
[kW/A]
0,21/0,92
speed
[min
-1
]
4400
control input
[VDC]
0-10
protection class
IP54
Supply air fan
phase/voltage
[50 Hz/VAC]
~1/230
power/current
[kW/A]
0,21/0,92
speed
[min
-1
]
4400
control input
[VDC]
0-10
protection class
IP54
Total power consumption
power/current
[kW/A]
1,2/5,2
-
Automatic control integrated
1,62/7,09
0,42/1,89
Thermal efficiency
90 %*
Insulation of walls
[mm]
30
Netto weight
[kg]
39
Pre-heater
power/current
[kW/A]
+
Smarty 4X V
LWA visas, dB(A)
LWA, dB(A)
63 Hz
125 Hz
250 Hz
500 Hz
1 kHz
2 kHz
4 kHz
5 kHz
Supply
62
47
53
58
56
54
51
46
41
Exhaust
54
44
45
50
47
45
43
38
35
Surrounding
51
30
35
48
46
40
35
27
24
Measured at
flow/pressure
[m
3
/h / Pa]
406/50
Right side connection
Left side connection