![Salda SAV Скачать руководство пользователя страница 6](http://html.mh-extra.com/html/salda/sav/sav_mounting-and-installation-instruction_801987006.webp)
SAV v2019.06
6
| EN
A
[mm]
B
[mm]
C
[mm]
a
[mm]
b
[mm]
b1
[mm]
c
[mm]
c1
[mm]
c2
[mm]
g
[mm]
e
[mm]
ød
[mm]
m
[kg]
SAV 2000
533
502
565
44
440
31
265
53
38
170
401
26,5
21,0
SAV 4000
588
627
565
44
561
33
265
53
38
220
455
26,5
34,0
SAV 6000
738
777
783
44
711
33
283
53
38
280
596
26,5
45,0
SAV 9000
818
852
818
44
786
33
318
57
45
280
676
26,5
57,0
TECHNICAL DATA
SAV 2000
SAV 4000
SAV 6000
SAV 9000
Phase / Voltage
[50 Hz / V]
~1 / 230
~1 / 230
~3 / 400
~3 / 400
Power
[kW]
0,173
0,484
0,54
0,992
Current
[A]
0,8
2,32
1,1
1,9
Speed
[min
-1
]
1392
1410
1405
1415
Max. air temperature
[°C]
+60
+70
+70
+70
Capacitor
[µF]
8,0
8,0
-
-
Protection class
IP-44
IP-54
IP-54
IP-54
Wiring diagram
#1
#1
#2
#2
Speed controller
MTY1,5 / TGRV1,5
MTY2,5 / TGRV4
TGRT2
TGRT2
IMPROPER OPERATION AND REPAIR
Fault removal works shall be performed only by trained and qualified personnel.
Before start of repair works, ENSURE THAT the unit is connected from the supply voltage and wait until the fan motor stops and the heater cools
down.
Follow the above safety requirements.
When the unit switches-off:
Check if voltage and current of the mains correspond to the requirements indicated in the product label.
Check for power availability to the unit.
Upon elimination of power supply faults, switch-on the unit again.
When the fan does not rotate:
When the fan motor has stopped because of overheating and the external protection is activated:
Allow the motor to cool down for 15–20 minutes.
Eliminate the cause for motor overheating.
Switch the fan again.
When the fan does not switch again:
Disconnect the supply voltage.
Wait unit any mechanical movement stops, the motor cools down and the connected capacitors discharge.
Ensure that the impeller is not blocked.
Inspect the capacitor (for single-phase fans – according the connection diagram). If faults repeat, change the capacitor.
Decreased air flow:
Check if the water heater is not dirty. Clean the heater as described in sections “Maintenance” and “Water heater”.
Cold supply air:
Check the air temperature which is set by the thermostat.
Check the tightness of the water heater.
Check if the supply water and control assemblies are in order and operational.
Increased noise and vibration:
Clean the fan as described in section “Fan maintenance”.
If the fault can not be removed, please contact the supplier.
ACCESSORIES
SAV
Fan Heater
T
Room thermostat
GR
Fan speed controller MTY
Room digital thermostat
Fan transformer speed controller TGRV
AM
Mixing point
Fan transformer speed controller TGRT
VV
3-way water valve
VP
Thermic water valve actuator
2-way water valve