EN
8
www.salda.lt
F
L
EX
1.
“
Exit
” – return to the user menu window
2.
“
System PI
” – PI coeffi cients of the entire system which defi nes the response to the heating or cooling
2.1.
“
Kp
” – {1–1000}, factory setting 1
2.2.
“
Ki
” – {1–10000}, factory setting 8
3.
“Room PI” – coeffi cients for work based on the extracted air
3.1.
“
Kp
” – {1–1000}, factory setting 100
3.2.
“
Ki
” – {1–10000}, factory setting 10
4.
“
Heater PI
” – electric heating coeffi cients
4.1.
“
Kp
” – {1–1000}, factory setting 30
4.2.
“
Ki
” – {1–10000}, factory setting 10
5.
“
Bypass/Rotor PI
” – coeffi cients of the bypass valves or rotor
5.1.
“
Kp
” – {1–1000}, factory setting 10
5.2.
“
Ki
” – {1–10000}, factory setting 10
6.
“Chiller PI”
– coeffi cients of the cooler
6.1.
“
Kp
” – {1–1000}, factory setting 10
6.2.
“
Ki
” – {1–10000}, factory setting 10
7.
“
PreHeat PI
” – coeffi cients of the preheater
7.1.
“
Kp
” – {1–1000}, factory setting 30
7.2.
“
Ki
” – {1–10000}, factory setting 10
8.
“
Night Control
” – night cooling settings. Feature will be activated when the “
day T>
” limit is exceeded for
the working unit, and when temperature drops below “
NightT
>” and the room temperature stays above
“
Room T>
” after switching off the unit.
8.1.
“
day T>
” – {15–40}°C maximum ambient air temperature, factory setting 26°C
8.2.
“
Night T>
” – {0–15}°C minimum ambient air temperature, factory setting 16 °C
8.3.
“
Room T>
” – {10–30}°C room air temperature, factory setting 17°C
8.4.
“
Exercise
” – {0–5 } h. Period for blowing, measuring. If the setting is “
0
”, ambient air sensor should
exit outdoors, factory setting 3h
9.
“
Watt. heater
” – temperature settings of the water heater
9.1.
“
Watter crit
” – {“
Watter stop
” + 5, 20}°C The limit from which the temperature of the return water is
forced to be increased, factory setting 10°C
9.2.
“
Watter stop
” – {-10 “
Watter crit
” -5}°C The limit at which fans are stopped, factory setting 5°C
9.3.
“
Pump stop
” – {10–30}min. Time after which the water pump is switched off if there is no need for
heating, factory setting 10min
9.4.
“
Pump exerc.
” – {0–5}h. The period for preventive start of the water pump for “
Pump stop
” time,
factory setting 10h
10.
“
Actuator settings
” – select the basic settings of the unit
10.1.
“
Heater
” – {E_On/Off, E_0_10, E_ESKM, W_VAL+-, W_0_10}, factory setting depends on the type
of the unit
E_On/Off – the electric heater is On/Off controlled using the relay
E_0_10 – the electric heater is controlled using 0–10 V output
E_ESKM – TRIAC control of the electric heater
W_VAL+ - Control of the three-position actuator of the water heater
W_0_10 – Control of the 0–10 V actuator of the water heater
“
Menu
” → “
Advanced
” → “
Service
” additional settings from the controlled recuperator, enter the password
4444
.