1. Connect 0-10V control signal wire of the CO2 converter to the analog input T.SET of the control board (X16 

„transmitter2“). Converter power supply (24VDC) wire is connected to the board 24 and neutral (0V) 
wire to the COM contact (X16 „transmitter2“).

2. Confi gure the control board using the FLEX panel:

2.1. On the panel, select Menu → Additional → Service (enter password 4444) → Vent. Control. Change the 

value of the parameter „CO2“ to „On“.

2.2. On the panel, select Menu → Additional → Service → CO2. In accordance with parameters of the CO2 

converter, select the CO2 level (using ppm units), which will be indicated at 0V threshold (parameter min_0V), 
and the level, which will be indicated at 10V (parameter max_10V).

2.3. On the panel, select Menu → Additional → Service → CO2. Select the level above which, when allowable 

level of CO2 is exceeded, the fans will operate at maximum speed (parameter PPM_100%).

2.4. On the panel, select Menu → Additional → Add.Func. Set the maximum allowable level of CO2 above 

which the supply air fl ow is increased (parameter CO2).

3. On the panel, in the menu Sensor overview you can see instantaneous exhaust CO2 value.
4. When allowable set CO2 level is exceeded, the information message High CO2 level is displayed at the initial 

screen and the speed of fans is increased based on the amount at which allowable level is exceeded.

5. In case of any fault of the CO2 converter, menu Emergency overview shows message CO2 sensor. Check if 

CO2 converter is properly connected (only current input).

EN Air quality parameters control based on the CO2 converter.

1. Connect 0-10V control signal wire of the supply air pressure converter to the analog input FAN of the control 

board, connect 0-10V control signal wire of the exhaust air pressure converter to the analogous input T.SET of 
the control board (X16 „Transmitter1“, „Transmitter2“). Converter power supply (24VDC) wire is connected to 
the board 24 and neutral (0V) wire to the COM contact (X16 „Transmitter1“, „Transmitter2“).

2. Confi gure the control board using the FLEX panel:
2.1. On the panel, select Menu → Additional → Service (enter password 4444) → Vent. Control. Change the 

value of the parameter SAF to Pressure. Change the value of the parameter EAF to Pressure.

2.2. On the panel, select Menu → Additional → Service → PSI. In accordance with the parameters of the 

pressure converter, select the minimum threshold 0V (parameter min_0V) and the maximum threshold 10V 
(parameter max_10V).

2.3. On the panel, select Menu → Additional → SAF Ctrl. Set the supply air fan speeds in accordance with the 

pressure.

2.4. On the panel, select Menu → Additional → EAF Ctrl. Set the exhaust air fan speed in accordance with the 

pressure.

3. On the panel, in the menu Sensor overview, you can see instantaneous supply and exhaust air pressure 

values.

4. In case of any fault of the pressure converter, menu Emergency overview shows message GP sensor. Check 

if pressure converters are properly connected (only current input).

System control based on the supply and exhaust air pressure converters

Содержание FLEX

Страница 1: ...anuel de service fr P 10 Manuale di servizio it Pag 12 VALDYMO PULTAS SU SKYST J KRISTAL EKRANU CONTROL PANEL WITH THE LIQUID CRYSTAL DISPLAY STEUERUNGSPULT MIT LCD BILDSCHIRM FLEX BO TIER DE COMMANDE...

Страница 2: ...ght T 0 15 C emiausia lauko oro temperat ra gamyklinis nustatymas 16 C 8 3 Room T 10 30 C patalpos oro temperat ra gamyklinis nustatymas 17 C 8 4 Exercise 0 5 h Kas kiek laiko vyksta prap timas matavi...

Страница 3: ...0V 0ppm 2000 Pa gamyklinis nustatymas 300 12 CO2 pasirinkus CO2 valdym nustatomos CO2 keitiklio jimo min max ribos 12 1 min_0V 0ppm 2000 ppm gamyklinis nustatymas 0 12 2 max_10V 0ppm 2000 ppm gamyklin...

Страница 4: ...Sistemos valdymas pagal tiekiamo bei i traukiamo oro sl gio keitiklius 1 Prijunkite CO2 keitiklio 0 10V valdymo signalo laid valdymo plok t s analogin jim T SET X16 transmit ter2 Keitiklio maitinimo 2...

Страница 5: ...Chiller PI 6 1 Kp 1 1000 10 6 2 Ki 1 10000 10 7 PreHeat PI 7 1 Kp 1 1000 30 7 2 Ki 1 10000 10 8 Night Control day T NightT Room T 8 1 day T 15 40 C 26 C 8 2 Night T 0 15 C 16 C 8 3 Room T 10 30 C 17...

Страница 6: ...C R C TK 10 2 R EC R C 10 4 Fans Tipe EC AC EC 0 10 AC AC 11 PSI 11 1 min_0V 0ppm 2000 0 11 2 max_10V 0ppm 2000 300 12 CO2 CO2 CO2 12 1 min_0V 0ppm 2000 ppm 0 12 2 max_10V 0ppm 2000 ppm 1000 13 Vent C...

Страница 7: ...parametras bei koks lygis prie 10V ribos max_10V parametras 2 3 Pultelyje pasirinkite Meniu Papildomas Service CO2 Nustatykite kiek vir ijus leid iam CO2 lyg ventiliatoriai sukasi maksimaliu grei iu P...

Страница 8: ...0 15 C minimum ambient air temperature factory setting 16 C 8 3 Room T 10 30 C room air temperature factory setting 17 C 8 4 Exercise 0 5 h Period for blowing measuring If the setting is 0 ambient ai...

Страница 9: ...000 Pa factory setting 0 11 2 max_10V 0ppm 2000 Pa factory setting 300 12 CO2 when CO2 control is selected min and max limits are set for the CO2 converter 12 1 min_0V 0ppm 2000 ppm factory setting 0...

Страница 10: ...ncy overview shows message CO2 sensor Check if CO2 converter is properly connected only current input EN Air quality parameters control based on the CO2 converter 1 Connect 0 10V control signal wire o...

Страница 11: ...drigste Temperatur der Au enluft Werkseinstellung 16 C 8 3 Room T 10 30 C Temperatur der Raumluft Werkseinstellung 17 C 8 4 Exercise 0 5 h Intervalle der Sp lung bzw Messung Wenn die Einstellung 0 ist...

Страница 12: ...11 2 max_10V 0ppm 2000 Pa Werkseinstellung 300 12 CO2 nach der Auswahl von der CO2 Steuerung werden Min und Max Eingangsgrenzen des CO2 Tauschers eingestellt 12 1 min_0V 0ppm 2000 ppm Werkseinstellung...

Страница 13: ...n Defekts vom CO2 Wandler wird im Men St rfall bersicht die Anzeige CO2 F hler gezeigt berpr fen Sie ob der CO2 Wandler richtig angeschlossen ist nur Stromeingang Steuerung der Luftqualit tsparameter...

Страница 14: ...baisse au dessous de NightT dispositif arr t et la temp rature du local baisse au dessous de RoomT 8 1 DayT 15 40 C temp rature ext rieure maximale r glage d usine 26 C 8 2 NightT 0 15 C temp rature...

Страница 15: ...signal 0 10V AC Commande des moteurs AC par trois tensions xes 11 PSI s lection maintien de pression r glage des valeurs d entr e min et max du convertisseur de pression 11 1 min_0V 0 ppm 2000 Pa r gl...

Страница 16: ...nt raccord uniquement l entr e du courant Les param tres de qualit de l air sur la base des donn es du convertisseur de CO2 1 Raccordez le l du signal de commande du convertisseur de pression de l air...

Страница 17: ...ratura esterna a dispositivo spento inferiore a NightT e la temperatura interna scende sotto Room T 8 1 day T 15 40 C la temperatura esterna massima impostazione di fabbica 26 C 8 2 Night T 0 15 C la...

Страница 18: ...ri AC tramite tre voltaggi ssi 11 PSI con il supporto della pressione selezionato viene impostato il limite min max dell ingresso del convertitore di pressione 11 1 min_0V 0ppm 2000 Pa impostazione di...

Страница 19: ...ione degli allarmi viene visualizzato il messaggio Sensore CO2 Accertarsi che il sensore di CO2 sia collegato correttamente solo l ingresso conduttore Qualit dell aria controllata tramite un sensore d...

Страница 20: ......

Отзывы: