EN |
23
AMBERAIR COMPACT CXP v2024.2
From the top (the ceiling-mounted version):
•
Unscrew the 4 screws of the longitudinal bracket.
• Remove the bracket.
•
Unscrew the holder of the heat exchanger, 3 screws.
• The heat exchanger is held by the second holder at the other end of the heat exchanger.
After the holder is unscrewed, the heat exchanger becomes loose. If it is hanged, it will drop.
• Remove the spacers of the heat exchangers.
From the bottom (the floor-mounted version):
•
Unscrew the 4 screws and remove the longitudinal bracket.
•
Unscrew the 2 holders of the heat exchanger.
• Remove the spacers and the heat exchanger.
Figure 6.6.1. AmberAir Compact ceiling-mounted version
Figure 6.6.2.
AmberAir Compact 1-2 CX P, 4 CX P floor-mounted version
Figure 6.6.3.
AmberAir Compact 3 CX P floor-mounted version
6.7. ELECTRIC, WATER HEATER MAINTENANCE
•
In case manual protection is activated, check for a fault before pressing the RESET button. If the fault is identified after it has been rectified, press
the RESET button using a screwdriver or a similar object.
•
Heaters are equipped with 2 thermal protection devices: an automatic self-resetting protection device that is activated at +50 °C, and a manually
restored protection device that is activated at +100 °C.