2.SPECIFICATION
2.1 The dimensions for Swimming Pool Heat Pump Unit
108
1046
286
450
810
810
841
860
Water outlet
(
50)
Water intlet
(
50)
3.INSTALLATION AND CONNECTION
3.5 Swimming Pool Heat Pumps Electrical Wiring
NOTE: although the unit heat exchanger is electrically isolated from the rest of the unit,
it simply prevents the flow of electricity to or from the pool water. Grounding the unit is
still required to protect you against short circuits inside the unit. Bonding is also required.
3.6 Initial startup of the Unit
Note: in order for the unit to heat the pool or spa, the filter pump must be running to
circulate water through the heat exchanger.
Start up procedure
- after installation is completed, you should follow these steps:
1. Turn on your filter pump. Check for water leaks and verify flow to and from the pool.
2. Turn on the electrical power supply to the unit, then press the key ON/OFF of wire controller,
it should start in several seconds.
3. After running a few minutes make sure the air leaving the top(side) of the unit is cooler
(between 5-10
).
4. With the unit operation turn the filter pump off. The unit should also turn off automatically.
5. Allow the unit and pool pump to run 24 hours per day until desired pool water temperature is
reached. When the water-in temperature reach setting, the unit just shuts off. The unit will now
automatically restart (as long as your pool pumps is running) when the pool temperature drops
more than 2
below set temperature.
The unit has a separate molded-in junction box with a standard electrical conduit nipple already
in place. Just remove the screws and the front panel, feed your supply lines in through the conduit
nipple and wire-nut the electric supply wires to the three connections already in the junction box
(four connections if three phase). To complete electrical hookup, connect heat pump by electrical
conduit, UF cable or other suitable means as specified (as permitted by local electrical authorities)
to a dedicated AC power supply branch circuit equipped with the proper circuit breaker, disconnect
or time delay fuse protection.
Disconnect
- A disconnect means (circuit breaker, fused or un-fused switch) should be located
within sight of and readily accessible from the uni, this is common practice on commercial and
residential air conditioners and heat pumps. It prevents remotely-energizing unattended equipment
and permits turning off power at the unit while the unit is being serviced.
Water Flow Switch
- the unit is equipped with a flow switch that turns it on when the pool pump is
running and shuts it off when the pump shuts off. This switch is the same type used in all gas pool
heaters and is factory adjusted for normal pool installations. If the pool water level is more than a
few feet above or below the thermostat knob of the unit, your dealer may need to adjust it at initial
startup.
Time Delay
- the unit is equipped with a 3 minute built-in solid state restart delay included
to protect control circuit components and to eliminate restart cycling and contactor chatter.
This time delay will automatically restart the unit approximately 3 minutes after each control
circuit interruption. Even a brief power interruption will activate the solid state 3 minute restart
delay and prevent the unit from starting until the 5 minute countdown is completed. Power
interruptions during the delay period will have no effect on the 3 minute countdown.
SAKURA - Total Air Conditioning Solution
SAKURA - Total Air Conditioning Solution