![Sakata SOB-50VA Скачать руководство пользователя страница 108](http://html1.mh-extra.com/html/sakata/sob-50va/sob-50va_service-manual_3546775108.webp)
Light Commercial R410A on-off
S13-01.01.13en
1.
Precaution on Installation
1). Measure the necessary length of the connecting pipe, and make it by the following way.
a. Connect the indoor unit at first, then the outdoor unit.
Bend the tubing in proper way. Do not harm them.
Specially Notice the pipe length/height/dimension of each capacity.
Maximum pipe length
Piping sizes
CAUTIONS
Daub the surfaces of the flare pipe and the joint nuts with frozen oil, and wrench it for 3~4 rounds
Be sure to use two wrenches simultaneously when you connect or disconnect the pipes.
With hands before fasten the flare nuts.
b. The stop value of the outdoor unit should be closed absolutely (as original state). Every time you
connect it, first loosen the nuts at the part of stop value, then connect the flare pipe immediately (in 5
minutes). If the nuts have been loosened for a long time, dusts and other impurities may enter the pipe
system and may cause malfunction later. So please expel the air out of the pipe with refrigerant before
connection.
Expel the air after connecting the refrigerant pipe with the indoor unit and the outdoor unit. Then fasten
the nuts at the repair-points.
Locate The Pipe
Drill a hole in the wall (suitable just for the size of the wall conduit), then set on the fittings such as the
wall conduit and its cover.
Bind the connecting pipe and the cables together tightly with binding tapes. Do not let air in, which will
cause water leakage by condensation.
Pass the bound connecting pipe through the wall conduit from outside. Be careful of the pipe allocation
to do no damage to the tubing.
Connect the pipes.
Then, open the stem of stop values of the outdoor unit to make the refrigerant pipe connecting the
indoor unit with the outdoor unit in fluent flow.
Be sure of no leakage by checking it with leak detector or soap water.
Cover the joint of the connecting pipe to the indoor unit with the soundproof / insulating sheath (fittings),
and bind it well with the tapes to prevent leakage.
c.
2)
a.
b.
c.
3)
4)
5)
6)
Installation
107
Pipe gauge
Tightening torque
Flare dimension A
Min (mm) Max
Flare shape
Φ6.4
15
~
16N.m
(153
~
163 kgf.cm)
8.3
8.7
Φ9.5
25
~
26N.m
(255
~
265kgf.cm)
12.0
12.4
Φ12.7
35
~
36N.m
(357
~
367kgf.cm)
15.4
15.8
Φ15.9
45
~
47N.m
(459
~
480 kgf.cm)
18.6
19.1
Φ19.1
65
~
67N.m
(663
~
684kgf.cm)
22.9
23.3
Model
Liquid(mm)
Gas(mm)
18,000Btu/h
6.4
12.7
24,000Btu/h
9.5
15.9
36,000Btu/h~60,000Btu/h
12.7
19
Model
Max. Length
Max. Elevation
18,000Btu/h~24,000Btu/h
25m
15m
36,000Btu/h
30m
20m
48,000Btu/h~60,000Btu/h
50m
25m
Содержание SOB-50VA
Страница 1: ...S13 01 01 13en Light Commercial Air Conditioner R410A ON OFF Service Manual 2013...
Страница 6: ...Light Commercial R410A on off S13 01 01 13en 2 2 Outdoor Units General Information 5...
Страница 14: ...Light Commercial R410A on off S13 01 01 13en 4 Service Space Indoor Units Four way Cassette Type Compact 13...
Страница 48: ...Light Commercial R410A on off S13 01 01 13en 4 Service Space Indoor Units Ceiling Floor 47...
Страница 55: ...Light Commercial R410A on off S13 01 01 13en SIB 100TAY SIB 140TAY SIB 200TAY Indoor Units Ceiling Floor 54...
Страница 62: ...Light Commercial R410A on off S13 01 01 13en SIB 50TAV SIB 60TAV Indoor Units Ceiling Floor 61...
Страница 63: ...Light Commercial R410A on off S13 01 01 13en SIB 100TAY SIB 140TAY SIB 200TAY Indoor Units Ceiling Floor 62...
Страница 68: ...Light Commercial R410A on off S13 01 01 13en 3 Dimensions Indoor Units HSP Duct Type 67...
Страница 69: ...Light Commercial R410A on off S13 01 01 13en Indoor Units HSP Duct Type 68...
Страница 72: ...Light Commercial R410A on off S13 01 01 13en 5 3 SIB 140DAY SIB 200DAY Indoor Units HSP Duct Type 71...
Страница 81: ...Light Commercial R410A on off S13 01 01 13en 11 Field Wiring SIB 60DAV Indoor Units HSP Duct Type 80...
Страница 82: ...Light Commercial R410A on off S13 01 01 13en SIB 100DAY SIB 140DAY SIB 200DAY Indoor Units HSP Duct Type 81...
Страница 91: ...Light Commercial R410A on off S13 01 01 13en 5 Wiring Diagrams SOB 50VA Outdoor Units 90...
Страница 92: ...Light Commercial R410A on off S13 01 01 13en SOB 60VA SOB 100YA Outdoor Units 91...
Страница 93: ...Light Commercial R410A on off S13 01 01 13en SOB 140YA SOB 200YA Outdoor Units 92...
Страница 117: ...Light Commercial R410A on off S13 01 01 13en 6 Wiring Please refer to the Wiring Diagram Installation 117...