PCD7.D250
User program examples
26/770 E1
(D25-08-E.DOC)
SAIA-Burgess Electronics Ltd.
Page 8-33
8.6 Function block :
INPUT
Data entry using the PCD7.D250 industrial terminal:
┌─────────────┬──────────────┐
│
│
INPUT
│
│
└──────────────┤
INP_TXT
──┤
=1
│
PARAM
──┤
=2
│
DIGIT
──┤
=3
│
DECIMAL
──┤
=4
│
X_POS
──┤
=5
│
Y_POS
──┤
=6
│
SIGN
──┤
=7
│
K_SIGN
──┤
│
CHAN_N
──┤
│
RBSY_F
──┤
2=
├──
PARAM
XBSY_F
──┤
├──
IN_BUSY
IN_BUSY
──┤
│
│
│
├────────────────────────────┤
│
Index modified : no
│
├────────────────────────────┤
│
Execution time : 0.2/1.4ms
│
1
)
├────────────────────────────┤
│
Used Fb levels : 1
│
├────────────────────────────┤
│
Program lines
: 372
│
└────────────────────────────┘
1)
0.2 ms:
RBSY_F = "0"
(no character in receive buffer)
1.4 ms:
RBSY_F = "1"
(number 0...9 is read from the
receive buffer and processed)
Function description
This function block allows the editing of the contents of a register or
counter via the PCD7.D250 industrial terminal. A minus sign and
decimal point are supported.