Saia-Burgess Controls AG
Manual PCD2.F2xxx serial interface
modules │ Document 27-649 ENG02 │ 2018-08-15
Module variants
PCD2.F2xxx serial interface modules
1-16
When using this module, the permitted ambient temperature for the control unit is
reduced by 5°C.
More details are available in the manual 26-740 “Installation components
for RS-485 networks”.
1.5.5
Belimo MP-Bus PCD7.F180S - serial interface module
Up to a maximum of 8 actuating drives and sensors can be connected.
PCD7.F180S
Belimo connection
Port x.1
Belimo MP-Bus
10 pin spring-loaded terminal block
0 PGND
MP
1
2 ‘MFT’
‘IN’
3
4
PGND 5
6
7
8 (SGD)
9
MP-Bus cabling
0 PGND Earth connection, MP line
1 MP
Multi-point
The MP-Bus is the Belimo master slave
bus. Up to 8 slaves can be connected to
a master device.
These are:
-
MFT(2) flap drives
- MFT(2) valve drives
-
MFT fire damper drives
- VAV NMV-D2M compact controller
2 ‘MFT’ MFT programming unit (internal MP-Bus)
3 ‘IN’
detection of MFT programming unit
(input 10 kΩ, Z5V1)
5 PGND Earth connection, MFT programming unit