Saia-Burgess Controls AG
Manual PCD2.F2xxx serial interface
modules │ Document 27-649 ENG02 │ 2018-08-15
Module variants
PCD2.F2xxx serial interface modules
1-11
1.4.3
Belimo MP-Bus on module - PCD2.F2810 port x.0
The PCD2.F2810 module has a full Belimo MP-Bus interface on port x.0 an. An
MP-Bus with up to 8 drives and sensors can therefore be connected to port x.0.
Belimo connection
Port x.0
Belimo MP-Bus
10 pin
spring-loaded terminal block
0 PGND Acom 1
2
MST
IN
3
4
PGND 5
6
7
8
9
MP-Bus cabling
0 PGND Earth connection, MP line
1 MP
Multi-point
The MP-Bus is the Belimo master slave bus. Up to 8
slaves can be connected to a master device.
These are:
-
MFT(2) flap drives
- MFT(2) valve drives
-
MFT fire damper drives
- VAV NMV-D2M compact controller
2 ‘MFT’ MFT programming unit (internal MP-Bus)
3 ‘IN’
detection of MFT programming unit
(input 10 kΩ, Z5V1)
5 PGND Earth connection, MFT programming unit
1