Chapter 12: Constant List
Firmware – S2011 and S3012
Revision: 1 (9/98)
85
© Saftronics, Inc.
Table 27
Constant List (Continued)
Constant
Function Name
Description
Factory
Setting
n022
Deceleration time 2
Unit
:
0.1 seconds (1 seconds for 1000 seconds and
above)
Setting range :
0.0 to 3600 seconds
10.0 seconds
n023
S
−
curve selection
(Setting)
(S
−
curve time)
0
:
S
−
curve not provided
1
:
0.2 seconds
2
:
0.5 seconds
3
:
1.0 seconds
1
n024
Display mode
(Setting)
(Unit)
0
: 0.1 Hz
2 to 39
: RPM (input # of motor poles)
40 to 3999 : custom
0
n025
Frequency reference 1
(same as Fref LED)
Setting depends on n024 setting
Range
:
0 to 9999
0.0Hz
n026
Frequency reference 2
Setting depends on n024 setting
Range
:
0 to 9999
0.0Hz
n027
Frequency reference 3
Setting depends on n024 setting
Range
:
0 to 9999
0.0Hz
n028
Frequency reference 4
Setting depends on n024 setting
Range
:
0 to 9999
0.0Hz
n029
Jog frequency
Setting depends on n024 setting
Range
:
0 to 9999
6.0Hz
n030
Frequency reference upper limit
Unit
: 1%
Setting range : 0 to 100%
100%
n031
Frequency reference lower limit
Unit
: 1%
Setting range : 0 to 100%
0%
n032
Motor rated current
(same as FLA LED)
Unit: 0.1A
Range: 10 to 200% INV rated
Unit is 1A, when setting is more than 1000A
kVA
dependent
n033
Motor overload protection selection
(OL1)
(Setting)
(Characteristics)
0
:
No protection
1
:
Standard motor (time constant 8 minutes)
2
:
Standard motor (time constant 5 minutes)
3
:
Inverter motor (time constant 8 minutes)
4
:
Inverter motor (time constant 5 minutes)
1
n034
Stopping method selection (OH1)
(Setting)
(Stop Method)
0
:
Ramp to stop
−
Decel 1 (fault)
1
:
Coast to stop (fault)
2
:
Ramp to stop
−
Decel 2 (fault)
3
:
Inverter motor (time constant 8 minutes)
3
n035
Multi-function contact input selection
(Terminal S2)
0
: REV RUN command (2-wire sequence)
1
: FWD/REV RUN command (3-wire sequence)
2
: External fault (NO contact input)
3
: External fault (NC contact input)
4
: Fault reset
5
: LOCAL/REMOTE selection
6
: Serial communication/control circuit terminal selection
7
: Fast stop
8
: Master frequency reference input level selection
9
: Multi-step speed reference
10 : Multi-step speed reference
11 : Jog frequency selection
12 : Accel/decel time selection
13 : External baseblock (NO contact input)
14 : External baseblock (NC contact input)
15 : Search command from maximum frequency
16 : Search command from set frequency
17 : Constant setting enable/disable
18 : PID integral value reset
19 : PID Control disable
20 : Timer function
21 : OH3 (Inverter overheat alarm)
22 : Analog reference sample/hold
0
n036
Multi-function contact input selection
(Terminal S3)
Set items are same as n035
2
n037
Multi-function contact input selection
(Terminal S4)
Set items are same as n035
4
efesotomasyon.com - Control Techniques,emerson,saftronics -ac drive-servo motor
Содержание FP5/GP5 Series
Страница 1: ...FP5 GP5 TECHNICAL MANUAL efesotomasyon com Control Techniques emerson saftronics ac drive servo motor...
Страница 2: ...efesotomasyon com Control Techniques emerson saftronics ac drive servo motor...
Страница 107: ...efesotomasyon com Control Techniques emerson saftronics ac drive servo motor...