3.0 RECEIVING & INSTALLATION
3.1 Installation
The cabinet containing the DF8 Plus must be installed in an area where
the following conditions exist:
Ambient temperature does not exceed 40ºC (104ºF).
Ambient temperature is not less than 10ºC (50ºF).
Altitude above sea level is 2000 feet (600m) or less.
Ambient air is reasonably clean, dry and free of flammable or
combustible vapors, steam, or corrosive gases, etc.
The cabinet must be installed away from any heat source, and a
minimum of 1 foot (30.48 cm) is required around the air inlet and
outlet, on ventilated units.
The DF8 Plus has been designed for 50ºC maximum inside the
enclosure.
When the unit is installed in poor environmental conditions, it must be
derated as follows:
1.5% per Cº above 40ºC, or 0.75% per Fº above 104ºF.
15% per 1000 feet (300m) above 2000 feet (600m).
The DF8 Plus is to be connected according to the NEC and any other
applicable Electrical Codes in the customer's area. The chassis must
be bonded to earth ground.
Section 6 pages 8, 9, and 10 show typical connections for speed
controlled wound field motors. For permanent magnet motors, there
will be no connections to F+ and F-.
See page 11 for typical torque control connections.
Note: For motor field connections of 100/50 or 200/100, refer to page
12.
3.2 Derating Data
3.3 Wiring
StockCheck.com
Содержание DF8 PLUS Series
Страница 11: ...SAFTRONICS 9 6 0 WIRING DIAGRAMS 6 1 DF8P 10 DF8P 15 S t o c k C h e c k c o m...
Страница 12: ...SAFTRONICS 10 6 0 WIRING DIAGRAMS CONT D 6 2 DF8P 25 S t o c k C h e c k c o m...
Страница 14: ...SAFTRONICS 12 6 0 WIRING DIAGRAMS CONT D 6 4 6 4 6 4 6 4 6 4 MOTOR CONNECTIONS S t o c k C h e c k c o m...
Страница 16: ...SAFTRONICS 14 7 0 DIMENSIONAL OUTLINES CONT D 7 2 DF8P 25 CHASSIS S t o c k C h e c k c o m...
Страница 17: ...SAFTRONICS 15 7 0 DIMENSIONAL OUTLINES CONT D 7 3 NEMA 1 ENCLOSED WITH OPERATORS S t o c k C h e c k c o m...