background image

FIGURE 3.

GROUND 

GROUND 

SCREW

SCREW

W0383-01

MECHANICAL DELAY ADJUSTMENT

The pneumatic delay is preset at approximately 30 seconds at the factory. To adjust the 

delay, turn the adjustment dial on the delay mechanism. Turn clockwise to increase 

the delay, counterclockwise to decrease the delay. Delay can be adjusted over a range 

from 0-90 seconds maximum. See Figure 4. As a point of reference when setting time 

delay in dark environments the notch in the dial indicates an approximate 30 second 

time delay and the larger of the three tabs indicates an approximate 60 second time 

delay.
NOTE: Set the delay to the minimum required to prevent false alarms due to flow 

surges.
After extended service, parts of the detector may become worn reducing the time de-

lay and causing false alarms. If this happens, increase the delay. If the delay is already 

at maximum, replace the mechanical delay assembly. Refer to Maintenance section 

for ordering replacement parts.

OPERATIONAL TESTING

Always notify a central station monitoring waterflow alarms before repairing, main-

taining or testing waterflow alarm devices.
1.   Replace the cover and tighten the security screws with the tamper proof wrench. 

Store the wrench in a secure place.

2.   Open the inspector’s test valve and time how long it takes for the detector to 

indicate a flow condition. The detector should remain activated until the inspec-

tor’s test valve is closed. Air pockets in the sprinkler system may increase the 

apparent time delay.

FIGURE 4. DELAY ADJUSTMENT DIAL

NOTE: RETARD TIME MAY EXCEED 90 SECONDS. ADJUST

AND VERIFY THAT TIME DOES NOT EXCEED 90 SECONDS.

NUMBER ON DIAL IS APPROXIMATE TIME DELAY IN SECONDS

DELAY

ADJUSTMENT

DIAL

W0385-00

MAINTENANCE

To prevent accidental water damage, control valves should be shut tightly and the 

system completely drained before waterflow detectors are removed or replaced.
Inspect detectors in accordance with applicable NFPA codes and standards and/or 

the authority having jurisdiction for leaks and replace if leaks occur. Test detectors 

at least quarterly as described under Operational Testing to insure proper operation. 

Test more often if required by the authority having jurisdiction.
Under normal conditions Safe Signal waterflow detectors should provide years of 

trouble-free service. However, if the delay mechanism becomes faulty, a replacement 

kit is available. To replace the delay mechanisms, request Part No. FS-RT. Complete 

instructions are enclosed with replacement parts. The delay mechanism can be easily 

replaced without removing the detector from the pipe or draining the pipe. If damage 

occurs to paddle, order replacement kit, request Part No. PRK9. Refer to procedure 

below for removal of detector on pipe. Do not repair or replace any other waterflow 

detector components in the field. If any other part of the detector does not perform 

properly, replace the entire detector. Failure to follow this instruction may result in 

failure of the detector to report a waterflow condition.
Proceed as follows to remove a detector.
1.  Drain the pipe.
2.  Turn off electrical power to the detector, and then disconnect wiring.
3.  Unscrew WFDTN from tee fitting.
4.  Lift detector clear of pipe.

If a vane breaks off in a pipe, find and remove it. Failure to do so may restrict the 

proper flow of water to part of the sprinkler system.

FIGURE 5. DIRECTIONAL COVER

NOTCHED COVER INDICATES FLOW DIRECTION AT A

DISTANCE FROM MULTIPLE VIEWING ANGLES

W0382-00

CAUTION

  

I56-4043-D 

 

 4/21

Отзывы: