EPS10EXP Explosion Proof 

Alarm Pressure Switch

INSTALLATION AND MAINTENANCE INSTRUCTIONS

 

Important

Please Read Carefully and Save

This instruction manual contains important information about 

the installation and operation of alarm pressure switches. 

Purchasers who install switches for use by others must leave this 

manual or a copy of it with the user.

Read all instructions carefully before installation, following only 

those instructions that apply to the model you are installing.

Before installing any alarm device, be thoroughly familiar with:

NFPA 72: 

Installation, Maintenance, and Use of  

 

 

 

Protective Signaling Systems

NFPA 13: 

Installation of Sprinkler Systems

Other applicable NFPA standards, local codes, and the require-

ments of the authority having jurisdiction.

Failure to follow these directions may result in failure of the 

device to report an alarm condition. Safe Signal is not respon-

sible for devices that have been improperly installed, tested, or 

maintained.

Operation

As pressure changes, a diaphragm actuates 2 snap action switch-

es. The pressure switch actuation is determined by adjustment 

settings.

Specifications

Contact Ratings: 

10 A, 1/2 HP @ 125/250 VAC

 

2.5 A @ 6/12/24 VDC

Operating Temperature Range: 

–40° F to +160°F

Maximum Service Pressure: 

250 PSI

Maximum Adjustment Range: 

 4 – 20 PSI

Enclosure Rating: 

NEMA Type 4 — Indoor or/Outdoor Use

Hazardous Atmospheres Classification: 

Class I, Groups B, C, D, Div. 1

 

Class II, Groups E, F, G, Div. 1

 

Class III, Div. 1

Approximate Differential: 

3 PSI throughout range

Installation

1.  Back out cover tamper set screw and remove cover (Fig. 1).

2.  Mounting the Switch

  The device is designed to be mounted in the upright or hori-

zontal position; side mounting is also acceptable. 

Figure 1. Pressure switch basic dimensions:

WARNING

To prevent ignition of hazardous atmospheres, disconnect cir-

cuits before removing cover. Keep cover closed while circuits are 

live. Conduit runs must have sealing fittings connected within 

18” of the enclosure.

W0174-00

I56-1427-C

COVER

4.9"

9.5"

LOCKING

SCREW

HEX ADJUST

SCREW

1/4" HEX HEAD

COVER

TAM PER

SET SCREW

(WRENCH

PROVIDED)

ADJUSTMENT

WHEEL

COVER

(WRENCH

PROVIDED)

MAIN ADJUSTMENT

WHEEL (TURN

COUNTERCLOSKWISE

TO INCREASE

PRESSURE)

1/2" NPT

  

I56-1427-C 

 

 4/21