background image

Locate it where vibration, shock, and mechanical loading

are minimal. Refer to piping diagram (Fig. 2 on page 2).

  a.  Mount the device directly to the line via the 1/2

 NPT pres-

sure connection. The use of teflon pipe sealant tape is rec-

ommended. Be sure the fitting is tight enough to prevent 

leaks.

  b.  Apply tightening torque to the brass hex portion of device.

CAUTION

High voltage. Electrocution hazard. Do not handle live AC wir-

ing or work on a device to which AC power is applied. Doing so 

may result in severe injury or death.

3. Wire the device in accordance with the National Electrical 

Code. Two 1/2

 NPT conduit entry holes have been provided 

in the mounting base to accept explosion proof conduit fit-

tings. If necessary, remove conduit entry plug with 3/8

 

square wrench.

4.  Connect wiring to terminals (see Figure 3 and Table 1).

WET

SYSTEM

ALARM

CHECK

VALVE

OS & Y

VALVE

WATER

BY-PASS

VALVE

LOCAL ALARM

SHUT OFF

VALVE

RETARD

WATER

MOTOR

GONG

EPSA10

WET

SYSTEM

ALARM

CHECK

VALVE

OS & Y

VALVE

WATER

BY-PASS

VALVE

LOCAL ALARM

SHUT OFF

VALVE

RETARD

WATER

MOTOR

GONG

EPSA10

DRY

SYSTEM

ALARM

CHECK

VALVE

OS & Y

VALVE

WATER

BY-PASS

VALVE

LOCAL ALARM

SHUT OFF

VALVE

WATER

MOTOR

GONG

CHECK

VALVE

EPSA10

WET SYSTEM

WET SYSTEM

DRY SYSTEM

WIRE TO ALARM

INDICATING CIRCUIT

OF FIRE ALARM

CONTROL PANEL

WIRE TO ALARM

INDICATING CIRCUIT

OF FIRE ALARM

CONTROL PANEL

WIRE TO ALARM

INDICATING CIRCUI

OF FIRE ALARM

CONTROL PANEL

TO

SPRINKLER

SYSTEM

TO

SPRINKLER

SYSTEM

TO

SPRINKLER

SYSTEM

Figure 2. Typical piping diagram for EPS10EXP

W0146-00

Figure 3. Switch terminals:

Table 1. Electrical connections (referenced at factory 
settings):

W0177-00

BREAK WIRE AS SHOWN FOR

SUPERVISION OF CONNECTIO N.

DO NOT ALLOW STRIPPED WIRE

LEADS TO EXTEND BEYOND

SWITCH HOUSING. DO NOT

LOOP WIRES.

SWITCHES AT 4-8 P.S.I. (HIGH TRIP PT.)

SWITCHES AT 0 P.S.I.

SW1

SW2

MODEL EPS10EXP

SW1

SW2

B

COM

A

B

COM

A

A

COM

B

A

COM

B

BOTH SWITCHES ACTIVATE SIMULTANEOUSLY

SWITCH # 1

COMMON 

TERMINALS

TERMINAL

"A"

TERMINAL

"B"

SWITCH #2

GROUND

SCREW

(GREEN)

W0175-00

  

I56-1427-C 

 

 4/21

Отзывы: