Commissioning 

Assure battery operation in the clean environment. 

Before operation, battery charge voltage must be adjusted as constant value as per ambient 

temperature. Such as, at 25

, charge the battery with 2.25V/cell for 16 to 24 hours, or with 

2.35Vpc for 8 to 12 hours; 

If the storage condition is serious, adjust charge voltage is necessary. 

 

Maintenance 

 

1.  Cleaning Notes: 

 

Battery appearance, terminal area and working environment must be kept clean and dry. 

 

In battery cleaning process, avoid use of electrostatic cleaning tools. 

 

Clean the battery with damp cloth. Do not use of gasoline, alcohol or other organic solvents;   

also do not use cloth containing these substances. 

2.  Inspection and Maintenance 

VRLA batteries are not maintenance-free batteries, battery operation process gradually   

changes with time. In order to ensure good battery usage, operational management and   

control are very important. To understand the operation status of batteries and equipment   

and to prevent accidental damage, regular maintenance is required. Periodically check   

and record the measurements using the following method for batteries used in UPS system   

room and base station (including outdoor station) site. 

2.1 Monthly Maintenance Inspection Items 

Item 

Content 

Standard 

Maintenance 

1-Temperatur

e Detection 

1-Measure and record 

battery terminal and 

container temperature by 

using infrared thermometer. 

2-Use infrared thermometer 

to measure ambient 

temperature. 

1-Ambient Temp:       

-20

~+55

 

2-Recommended 

Temperature:   

25±5

 

1-Check that the battery temperature 

compensation functions are turned on and 

that the battery temperature probe is 

properly installed. 

2-Check that the room temperature 

conditioning equipment such as 

air-conditioning is turned on. 

2-

 

Battery 

Float Voltage 

Measurement 

Measure floating voltage on 

positive and negative 

terminal of the battery group 

with multimeter. 

Measurement and 

control module 

display operating 

voltage differences 

within 0.05V 

If the monitoring module shows 

inconsistency even after adjusting, replace 

or repair it. 

Operation and

 maintenance

 

 

19

 

Содержание OPzV Series

Страница 1: ......

Страница 2: ...Characteristics 1 Discharge Characteristic Curve 06 2 Performance Data 07 Chapter III Operation and Maintenance 1 Security Instruction 17 2 Discharge 18 3 Temperature Effect On Battery Capacity 18 4...

Страница 3: ...features Positive plates Negative plates Separators Container and Lid Electrolyte Terminal posts Posts sealing Vents Plates suspension Inter cell connectors Terminal hardware Terminal adaptor Product...

Страница 4: ...rage Systems Emergency power UPS and EPS units Transportation Standards IEC60896 21 22 2004 IEC61427 2014 DIN43539 T5 1984 DIN40742 1999 BSEN 61427 2002 YD T1360 2005 GB T 22473 2008 Eurobat guide Ins...

Страница 5: ...OPzV 800Ah to 1500Ah OPzV 2000Ah OPzV 2500Ah 3000Ah 12V OPzV 50Ah 100Ah 150Ah Product Introduction 03...

Страница 6: ...66 206 471 503 5 37 3 4268 0 50 M10 20 F 7 OPzV 500 2 500 166 206 471 503 5 37 3 4268 0 50 M10 20 F 6 OPzV 600 2 600 145 206 646 678 5 44 5 4606 0 40 M10 20 F 8 OPzV 800 2 800 191 210 646 678 5 60 0 6...

Страница 7: ...to lead dioxide but negative plate has not reached fully charged stage the process of active substance in negative plate transforming to spongy lead is not finished oxygen gas generated in positive p...

Страница 8: ...e 25 Voltage curve of simulation wind energy system cycle application Figure 2 2 Voltage curve of simulation wind energy system cycle application Charge characteristic curve under different depth of d...

Страница 9: ...PzV 300 1 65 453 405 354 308 261 173 113 0 88 3 60 8 51 5 39 8 33 9 17 7 14 96 8 10 4 20 3 56 1 82 1 70 425 380 329 292 254 165 107 0 83 6 57 5 48 6 38 2 32 7 17 3 14 56 7 99 4 16 3 53 1 80 1 75 405 3...

Страница 10: ...2 4 52 1 70 1025 893 831 771 644 440 285 3 222 9 153 3 129 6 101 9 87 2 46 3 39 60 21 31 10 35 8 68 4 51 1 75 947 843 777 717 624 421 269 3 211 2 145 3 124 8 97 9 84 0 44 0 38 40 21 04 10 32 8 64 4 48...

Страница 11: ...0 836 0 575 0 486 0 382 0 327 0 173 0 145 6 79 90 39 66 33 57 17 18 1 75 3443 3086 2729 2376 2040 1580 1010 0 792 0 545 0 468 0 367 0 315 0 168 0 142 3 78 90 39 18 33 27 17 07 1 80 3251 2933 2588 230...

Страница 12: ...315 0 197 3 147 8 120 0 102 5 79 7 69 2 34 9 29 90 16 54 8 65 7 48 3 67 1 70 714 659 590 537 447 300 0 189 8 142 5 114 8 98 0 78 5 67 8 33 5 29 20 16 44 8 52 7 40 3 63 1 75 670 633 570 516 432 291 0...

Страница 13: ...07 1 70 1723 1572 1417 1293 1088 765 6 506 0 380 0 310 5 262 9 211 4 174 5 92 0 79 47 42 67 20 70 17 36 9 02 1 75 1639 1509 1366 1245 1056 752 0 494 0 372 0 302 9 255 2 205 7 168 0 90 7 76 76 42 13 20...

Страница 14: ...4 3 345 0 291 75 160 00 79 28 67 13 34 35 1 75 5742 5319 4816 4420 3840 2840 0 1864 0 1404 0 1135 7 957 1 771 4 630 0 340 0 284 25 158 00 78 26 66 56 34 11 1 80 5138 4863 4592 4240 3720 2780 0 1832 0...

Страница 15: ...ed by skilled personnel only Used batteries must be recycled and disposed properly as improper disposal of batteries is harmful to the environment and health Used batteries shall be properly disposed...

Страница 16: ...erature of 25 discharge over 60 DOD is prohibited except protective measure is adopted such as raising temperature Temperature The operation temperature range is 25 60 All the performance data is meas...

Страница 17: ...vice life curve Floating Charge and Equalizing charge Floating charge Floating operation is the best operation condition for battery In floating operation the battery keep fully charged state under th...

Страница 18: ...tion the battery bank should be supplementary charged The battery is out of work beyond 6 months Running in full floating operation for a long term but not discharge under more than 40 C10 capacity th...

Страница 19: ...can be regarded as the fully charged symbol Refer to the required time as table 3 3 In constant voltage case the charge current keep unchanged for 3 hours in the final stage of charge Charge voltage s...

Страница 20: ...installation instructions Battery which is separately installed on rack and cabinets should be connected by bolts to the foundation Battery racks or cabinets should be properly installed according to...

Страница 21: ...tus of batteries and equipment and to prevent accidental damage regular maintenance is required Periodically check and record the measurements using the following method for batteries used in UPS syst...

Страница 22: ...for cleaning 2 If there is crystalline or liquid clean it with a dry cloth Check and tighten the safety valve 2 2 Quarterly Maintenance Inspection Items In addition to the monthly maintenance items a...

Страница 23: ...capacity to be maintained must be more than 80 and in energy storage use more than 60 of the reference capacity Recovery test measure and record various parameters specified in the monthly quarterly...

Страница 24: ...No 1 Shengyang Road Qufu City Shandong Province 273100 P R China Tel 0086 537 4422313 Fax 0086 537 4411980 E mail sales sacredsun cn...

Отзывы: