Sacred Sun OPzV Series Скачать руководство пользователя страница 14

 

Table 2-2 OPzV Battery Constant Power Discharge Data Sheet (W/cell, 25

 

Constant Power Discharge Data Sheet (25

)-------Watt (W) 

Battery Type 

End Voltage 

(V/cell) 

Discharge Time 

5min 

10min 

15min 

20min 

30min 

1 h 

2 h 

3 h 

5 h 

6 h 

8 h 

10 h 

20 h 

24 h 

48 h  100 h  120 h  240 h 

16 OPzV 2000 

1.65 

4060   

3700   

3328   

3049   

2620   

1975.3    1315.0    985.0   

804.8 

681.0  547.6  441.4  234.8  199.00   

108.00   53.60   45.20   23.08   

1.70 

3919   

3550   

3180   

2930   

2550   

1914.0    1265.0    950.0   

776.2 

657.1  528.6  436.2  230.0  194.50   

106.67   52.85   44.75   22.90   

1.75 

3700   

3402   

3066   

2830   

2480   

1880.0    1235.0    930.0   

757.1 

638.1  514.3  420.0  226.7  189.50   

105.33   52.17   44.37   22.74   

1.80 

3325   

3220   

2960   

2745   

2426   

1830.0    1206.7    915.0   

704.8 

595.2  495.2  410.0  222.4  185.70   

104.00   51.80   43.90   22.59   

1.85 

3123   

2933   

2812   

2614   

2281   

1763.1    1155.0    875.0   

642.9 

566.7  459.5  387.1  215.2  181.30   

102.50   50.93   43.20   22.45   

20 OPzV 2500 

1.65 

5380   

4810   

4310   

3917   

3350   

2483.3    1633.3    1231.3    1006.0  851.2  684.5  551.8  293.5  248.75   

135.00   67.00   56.50   28.85   

1.70 

5168   

4650   

4162   

3817   

3300   

2433.3    1596.7    1203.3    970.2 

821.4  660.7  545.2  287.5  243.13   

133.33   66.06   55.94   28.63   

1.75 

4902   

4432   

4013   

3683   

3200   

2366.7    1553.3    1170.0    946.4 

797.6  642.9  525.0  283.3  236.88   

131.67   65.21   55.46   28.43   

1.80 

4331   

4119   

3827   

3533   

3100   

2316.7    1526.7    1160.0    881.0 

744.0  619.0  512.5  278.0  232.13   

130.00   64.75   54.88   28.24   

1.85 

3604   

3466   

3317   

3268   

2851   

2183.3    1443.8    1093.8    803.6 

708.3  574.4  483.9  269.0  226.63   

128.13   63.67   54.00   28.06   

24 OPzV 3000 

1.65 

6456   

5772   

5172   

4700   

4020   

2980.0    1960.0    1477.5    1207.1  1021.4  821.4  662.1  352.1  298.50   

162.00   80.40   67.80   34.62   

1.70 

6202   

5580   

4994   

4580   

3960   

2920.0    1916.0    1444.0    1164.3  985.7  792.9  654.3  345.0  291.75   

160.00   79.28   67.13   34.35   

1.75 

5742   

5319   

4816   

4420   

3840   

2840.0    1864.0    1404.0    1135.7  957.1  771.4  630.0  340.0  284.25   

158.00   78.26   66.56   34.11   

1.80 

5138   

4863   

4592   

4240   

3720   

2780.0    1832.0    1392.0    1057.1  892.9  742.9  615.0  333.6  278.55   

156.00   77.70   65.85   33.89   

1.85 

4685   

4399   

4221   

3921   

3421   

2620.0    1732.5    1312.5    964.3 

850.0  689.3  580.7  322.9  271.95   

153.75   76.40   64.80   33.68   

12V 1 OPzV 50 

1.65 

125   

123   

113   

105   

86   

57.5 

37.5 

29.5 

19.2 

16.8 

13.3 

11.7 

6.0 

5.15    2.64    1.29    1.09    0.56   

1.70 

116   

114   

106   

96   

83   

55.5 

35.3 

28.1 

18.6 

16.1 

12.7 

11.0 

5.8 

5.07    2.59    1.27    1.07    0.55   

1.75 

106   

104   

98   

90   

78   

52.5 

33.4 

27.6 

17.8 

15.5 

12.3 

10.5 

5.6 

4.98    2.55    1.24    1.05    0.54   

1.80 

96   

95   

86   

79   

70   

50.0 

31.8 

24.9 

16.9 

14.8 

11.7 

10.0 

5.3 

4.68    2.48    1.22    1.03    0.53   

1.85 

93   

80   

73   

69   

60   

47.5 

30.1 

23.6 

16.3 

14.3 

11.1 

9.3 

5.1 

4.49    2.39    1.18    1.01    0.51   

12V 2 OPzV 100 

1.65 

250   

245   

226   

210   

172   

115.0 

75.0 

59.0 

38.4 

33.6 

26.6 

23.3 

11.9  10.30    5.20    2.57    2.18    1.12   

1.70 

232   

227   

212   

192   

165   

111.0 

70.6 

56.1 

37.2 

32.2 

25.4 

22.0 

11.6  10.14    5.18    2.54    2.14    1.09   

1.75 

212   

208   

195   

180   

155   

105.0 

66.8 

55.2 

35.6 

31.0 

24.6 

21.0 

11.1  10.00    5.15    2.50    2.10    1.07   

1.80 

192   

189   

172   

158   

140   

100.0 

63.5 

49.8 

33.8 

29.6 

23.4 

19.9 

10.5 

9.85    5.03    2.46    2.06    1.05   

1.85 

185   

160   

145   

137   

119   

95.0 

60.2 

47.2 

32.6 

28.6 

22.2 

18.6 

10.2 

9.40    4.89    2.40    2.02    1.03   

12V 3 OPzV 150 

1.65 

375   

368   

339   

315   

258   

172.5 

112.5 

88.5 

57.6 

50.4 

39.9 

35.0 

17.9  15.45    7.80    3.86    3.27    1.68   

1.70 

348   

341   

318   

288   

248   

166.5 

105.9 

84.2 

55.8 

48.3 

38.1 

33.0 

17.4  15.21    7.77    3.81    3.21    1.64   

1.75 

318   

312   

293   

270   

233   

157.5 

100.2 

82.8 

53.4 

46.5 

36.9 

31.5 

16.7  15.00    7.73    3.75    3.13    1.61   

1.80 

288   

284   

258   

237   

210   

150.0 

95.3 

74.7 

50.7 

44.4 

35.1 

29.9 

15.8  14.78    7.58    3.69    3.09    1.59   

1.85 

278   

240   

218   

206   

179   

142.5 

90.3 

70.8 

48.9 

42.9 

33.3 

27.9 

15.3  14.10    7.34    3.65    3.03    1.56   

 
 
 
 
 
 
 
 
 
 

Electrical

 Characteristics

 

 

12

 

Содержание OPzV Series

Страница 1: ......

Страница 2: ...Characteristics 1 Discharge Characteristic Curve 06 2 Performance Data 07 Chapter III Operation and Maintenance 1 Security Instruction 17 2 Discharge 18 3 Temperature Effect On Battery Capacity 18 4...

Страница 3: ...features Positive plates Negative plates Separators Container and Lid Electrolyte Terminal posts Posts sealing Vents Plates suspension Inter cell connectors Terminal hardware Terminal adaptor Product...

Страница 4: ...rage Systems Emergency power UPS and EPS units Transportation Standards IEC60896 21 22 2004 IEC61427 2014 DIN43539 T5 1984 DIN40742 1999 BSEN 61427 2002 YD T1360 2005 GB T 22473 2008 Eurobat guide Ins...

Страница 5: ...OPzV 800Ah to 1500Ah OPzV 2000Ah OPzV 2500Ah 3000Ah 12V OPzV 50Ah 100Ah 150Ah Product Introduction 03...

Страница 6: ...66 206 471 503 5 37 3 4268 0 50 M10 20 F 7 OPzV 500 2 500 166 206 471 503 5 37 3 4268 0 50 M10 20 F 6 OPzV 600 2 600 145 206 646 678 5 44 5 4606 0 40 M10 20 F 8 OPzV 800 2 800 191 210 646 678 5 60 0 6...

Страница 7: ...to lead dioxide but negative plate has not reached fully charged stage the process of active substance in negative plate transforming to spongy lead is not finished oxygen gas generated in positive p...

Страница 8: ...e 25 Voltage curve of simulation wind energy system cycle application Figure 2 2 Voltage curve of simulation wind energy system cycle application Charge characteristic curve under different depth of d...

Страница 9: ...PzV 300 1 65 453 405 354 308 261 173 113 0 88 3 60 8 51 5 39 8 33 9 17 7 14 96 8 10 4 20 3 56 1 82 1 70 425 380 329 292 254 165 107 0 83 6 57 5 48 6 38 2 32 7 17 3 14 56 7 99 4 16 3 53 1 80 1 75 405 3...

Страница 10: ...2 4 52 1 70 1025 893 831 771 644 440 285 3 222 9 153 3 129 6 101 9 87 2 46 3 39 60 21 31 10 35 8 68 4 51 1 75 947 843 777 717 624 421 269 3 211 2 145 3 124 8 97 9 84 0 44 0 38 40 21 04 10 32 8 64 4 48...

Страница 11: ...0 836 0 575 0 486 0 382 0 327 0 173 0 145 6 79 90 39 66 33 57 17 18 1 75 3443 3086 2729 2376 2040 1580 1010 0 792 0 545 0 468 0 367 0 315 0 168 0 142 3 78 90 39 18 33 27 17 07 1 80 3251 2933 2588 230...

Страница 12: ...315 0 197 3 147 8 120 0 102 5 79 7 69 2 34 9 29 90 16 54 8 65 7 48 3 67 1 70 714 659 590 537 447 300 0 189 8 142 5 114 8 98 0 78 5 67 8 33 5 29 20 16 44 8 52 7 40 3 63 1 75 670 633 570 516 432 291 0...

Страница 13: ...07 1 70 1723 1572 1417 1293 1088 765 6 506 0 380 0 310 5 262 9 211 4 174 5 92 0 79 47 42 67 20 70 17 36 9 02 1 75 1639 1509 1366 1245 1056 752 0 494 0 372 0 302 9 255 2 205 7 168 0 90 7 76 76 42 13 20...

Страница 14: ...4 3 345 0 291 75 160 00 79 28 67 13 34 35 1 75 5742 5319 4816 4420 3840 2840 0 1864 0 1404 0 1135 7 957 1 771 4 630 0 340 0 284 25 158 00 78 26 66 56 34 11 1 80 5138 4863 4592 4240 3720 2780 0 1832 0...

Страница 15: ...ed by skilled personnel only Used batteries must be recycled and disposed properly as improper disposal of batteries is harmful to the environment and health Used batteries shall be properly disposed...

Страница 16: ...erature of 25 discharge over 60 DOD is prohibited except protective measure is adopted such as raising temperature Temperature The operation temperature range is 25 60 All the performance data is meas...

Страница 17: ...vice life curve Floating Charge and Equalizing charge Floating charge Floating operation is the best operation condition for battery In floating operation the battery keep fully charged state under th...

Страница 18: ...tion the battery bank should be supplementary charged The battery is out of work beyond 6 months Running in full floating operation for a long term but not discharge under more than 40 C10 capacity th...

Страница 19: ...can be regarded as the fully charged symbol Refer to the required time as table 3 3 In constant voltage case the charge current keep unchanged for 3 hours in the final stage of charge Charge voltage s...

Страница 20: ...installation instructions Battery which is separately installed on rack and cabinets should be connected by bolts to the foundation Battery racks or cabinets should be properly installed according to...

Страница 21: ...tus of batteries and equipment and to prevent accidental damage regular maintenance is required Periodically check and record the measurements using the following method for batteries used in UPS syst...

Страница 22: ...for cleaning 2 If there is crystalline or liquid clean it with a dry cloth Check and tighten the safety valve 2 2 Quarterly Maintenance Inspection Items In addition to the monthly maintenance items a...

Страница 23: ...capacity to be maintained must be more than 80 and in energy storage use more than 60 of the reference capacity Recovery test measure and record various parameters specified in the monthly quarterly...

Страница 24: ...No 1 Shengyang Road Qufu City Shandong Province 273100 P R China Tel 0086 537 4422313 Fax 0086 537 4411980 E mail sales sacredsun cn...

Отзывы: