Charge State
Voltage(V)/cell
100%
≥
2.16
80%
≥
2.14
60%
≥
2.10
40%
≥
2.08
20%
≥
2.04
Operation
Table 4-4 open circuit voltage at different charge state
13
The battery supplemental charge method during the storage is: charge battery with 2.35V/cell for 8
to 12 hours.
It is necessary to limit the current, and the optimum limiting value is within 0.2C10 ( A ) .
Testing of the open circuit with the storage battery can decide whether it shall be supplemental
charged. If the voltage drops to 2.10V/cell, the battery shall be supplemental charged in time.
Improper maintenance will shorten the battery service life or decrease the service performance.