12 

5.2 System setting

 

E.g. To set password to as 112, set cycle display interval as 6s, set backlight duration time as 60s, the operation 

process is as follows 

Enter programming interface,
select system setting menu

Change password to 112

Set cycle display interval as 6s

Set backlight duration time as 60s

Save modified data and
exit programming mode

Menu

>3s

Menu

Menu

 

5.3 Input signal setting 

User can set rated current value according to practical situation at field. 

E.g. To set rated voltage value as 1000V, external Hall sensor input ratio is 100.0A/4V, the operation process is as 

follows, 

Enter programming interface,
select signal input setting menu

Set rated voltage as 1000V

Save modified data and
exit programming mode

Menu

Menu
> 3 s

Menu

Set current range as 4.000V

Set rated current as 100.0A

 

 

Содержание AR4DCT

Страница 1: ...1 AR4DCT DIN rail Multi function DC Power Meter User Manual...

Страница 2: ...N AND WIRING 4 3 1 DIMENSION 4 3 2 INSTALLATION 4 3 3 WIRING 5 TYPICAL WIRING 5 3 3 1 AR4DCT MR4DCT DIO 02 5 4 OPERATION 8 4 1 PANEL DESCRIPTION 8 4 2 INSTRUCTION FOR OPERATION KEYS 8 4 3 INSTRUCTION...

Страница 3: ...ation plugs without powering off Connect the terminal wires against the related instructions Please don t touch the terminals when the meter is in operation 2 Product description 2 1 Overview AR4DCT a...

Страница 4: ...sor input 4 4V Consumption 0 01VA each circuit Impedance 200k Power supply Working range AC DC 80 270 V Frequency 50 60 Hz Consumption 5VA Output Energy pulse Photoelectric isolation output pulse widt...

Страница 5: ...and demand only can be read through communication but not can be shown on the panel of meter 2 6 Digital input This meter supports 4 digital inputs The digital input uses the method of dry contact in...

Страница 6: ...ce of bus can be connected with 32 meters at most The start and end terminals of bus can be connected with terminal resistance 3 Installation and wiring 3 1 Dimension 3 1 1 AR4DCT main module dimensio...

Страница 7: ...5 3 3 Wiring Typical wiring 3 3 1 AR4DCT MR4DCT DIO 02 Other typical wiring...

Страница 8: ...R4DCT Voltage input input voltage should not be higher than 1500V 4 Current input input current should be connected via Hall sensor 5 Please make sure the directions of voltage an current are same 6 W...

Страница 9: ...input Voltage signal 11 14 Voltage input Energy pulse output 47 48 Active energy pulse output RS485 communication 58 59 Corresponding to A and B Relay output 15 17 2 relay outputs 16 is common end Di...

Страница 10: ...bit or select an item Menu Keep pressing it for 3 seconds to enter programming mode Cancel or return to upper level menu Confirm or enter next level menu 4 3 Instruction for measurement interface Mea...

Страница 11: ...rd input interface input the password defaulted password is 0001 through or key and press key to enter the setting interface if the password is correct Exit programming mode When the data or items in...

Страница 12: ...Import energy Export energy Energy pulse constant Unit imp kWh Clear demand Not clear demand Clear demand Clear energy Not clear energy Clear energy Input setting Rated voltage Unit V fixed value Curr...

Страница 13: ...ode Energy pulse width Voltage range Rated current of 1 circuit Alarm mode Alarm delay time Alarm hysteresis value Alarm value Cycle display interval LCD backlight duration Energy pulse constant Progr...

Страница 14: ...60s Save modified data and exit programming mode Menu 3s Menu Menu 5 3 Input signal setting User can set rated current value according to practical situation at field E g To set rated voltage value a...

Страница 15: ...operation process is as follows Enter programming interface select signal input setting menu Menu Menu 3s Menu Set relay working mode as alarm mode Alr Set relay pulse width as 10 0s Set alarm item a...

Страница 16: ...e subordinate machine addresses of normal meter and abnormal meter Besides you may check whether there is a fault in the meter by exchanging the installation positions of normal and abnormal meters Da...

Страница 17: ...er is negative The most common problem on spot is inlet and outlet wire of current transformer are in reverse connection Observe signed active power in split phase and it may be negative because of wr...