5.2 System setting
E.g. To set password to as 112, set cycle display interval as 6s, set backlight duration time as 60s, the operation
process is as follows
Enter programming interface,
select system setting menu
Change password to 112
Set cycle display interval as 6s
Set backlight duration time as 60s
Save modified data and
exit programming mode
Menu
>3s
Menu
Menu
5.3 Input signal setting
User can set rated current value according to practical situation at field.
E.g. To set rated voltage value as 1000V, external Hall sensor input ratio is 100.0A/4V, the operation process is as
follows,
Enter programming interface,
select signal input setting menu
Set rated voltage as 1000V
Save modified data and
exit programming mode
Menu
Menu
> 3 s
Menu
Set current range as 4.000V
Set rated current as 100.0A