Operating manual - ChillPAC and LP ChillPAC Mk 3
42/68
010823 en 2021.06
Fig. 21: UniSAB III front
5.3.2
Normal start-up procedure
1.
Confirm that the system conditions permit the chiller to start.
2.
Press the start button on UniSAB III.
3.
Allow the compressor to start up and stabilise.
4.
Check the following on the chiller unit:
a.
Mechanical tightness of the external piping, bolts and valves.
b.
No oil and refrigerant leaks.
If not satisfactory, shut down the chiller and correct the problem.
Top bar
Content area
Info bar
F-key area