27
EN
7
QCV-MB BOARD
See diagram [Ref] 15.1 on page 40
8
FUNCTION OF AUXILIARY
CONTACTS
MC1
CA
CF
2
M1
IN1
CLOSED
DEFAULT
JUMPER
ON / OFF WINDOW
• When the contact is closed the unit can operate.
• When the contact is open the unit is stopped.
8.1 CA (F1-F1) contact
Remote oN/oFF control or remote Summer/Winter
Change-over (see dIP 6 setting).
With dIP 6 on oFF is set as remote oN/oFF where :
• open contact = oN
• closed contact = oFF
With dIP 6 oN is set as SUMMER/WINTER where :
• IN 1 contact open = WINTER
• IN 1 contact closed = SUMMER
8.2 CF (F2-F2) contact
• open window contact;
• person presence probes;
• a further system.
If used, remove the MC1 Jumper for contact
closure.
9
CONFIGURATION DIP SWITCH
SETTINGS
DIP switch configuration table, KD2 set
Position
DIP
DEFAULT
ON
OFF
1
OFF
4 pipe unit
2 pipe unit
2
OFF
Simultaneous
Thermostatic Control
Valve thermostatic
control and continuous
ventilation
3
OFF
T3 Winter and Summer
T3 only Winter
4
OFF
Electric heaters
management
IAQ filter management
5
OFF
Electric heaters
management with
T2 probe
T2 as Change-Over
CH (electric heater II
° phase)
6
OFF
IN1 = Remote
Summer/Winter
IN1 = Remote ON/OFF
7
OFF
Slave
Master
8
OFF
Management of the
opening times of the
3 point 24 Vac valve
actuator
Management of the
opening times of the
3 point 24 Vac valve
actuator
9
OFF
10
OFF
DIP switch configuration table, KD3 set
DIP
Position = ON
Position = OFF - Default
n° 1
EC motor
Asynchronous motor
n° 2
Not assigned
Not assigned