• “PAR” PARAMETERS MENU
This menu allows you to modify the operating
parameters of the unit.
From the main menu, access the “
TECHNICAL
”
menu and use the
TOUCH PAD
to display the
“
PAR
” menu.
Confirm with the “Enter” key.
Use the
TOUCH PAD
to select
the PARAMETER to
be modified and
confirm with “
Enter
”.
Once the parameter is selected, the value will be
displayed.
The value can be modified using the
TOUCH PAD
Table 1
(*) Parameters available only if the "
dGto
”
menu is set with the "
POSt
” function.
“
PAr
”
DESCRIPTION
RANGE
DEFAULT
QLO
Minimum control flow rate in calibration
-10% - +10%
60 m
3
/h
QHI
Maximum control flow rate in calibration
-10% - 0%
F130 = 130 m
3
/h
F150 = 150 m
3
/h
nLO
Minimum rpm in operation
-10% - +10%
600
nHI
Maximum rpm in operation
-10% - +10%
3000
Pstd
Percentage of standard modulation of nominal speed
100% - 110%
100%
Pbst
Percentage of boost/party modulation
110% - 130%
130%
PnGt
Percentage of night modulation
45% - 100%
70%
Pmed
Percentage of intermediate modulation
35% - 70%
45%
Phol
Percentage of minimum - holiday modulation
0 - 35%
25%
tbSt
BOOSTER duration time
60 - 240 min
180 min
TCOOL (*)
Heating setpoint temperature for freecooling management
10 - 30°C
26
THEAT (*)
Cooling setpoint temperature for freecooling management
10 - 30°C
20
Flife
Filter service life
30 - 400 days
180 days
HrLO
Relative humidity for Minimum Humidity mode activation
Relative humidity lower limit in the comfort range
20 - 30
25
Hrst
Relative humidity upper limit in the comfort range
40 - 50
45
HrHiF
Activates the display of parameter
HrHi
On - Off
Off
HrHi
Relative humidity for Maximum Humidity mode activation
60 - 80
65
ErHS
Speed in emergency mode due to excessively low humidity
1 - 4
2
FLUSH
Activation of forced summer exchange mode
On - Off
Off
Func
FUNCTIONS blocking operation (see dedicated paragraph)
-
-
Test (*)
Summer season transition temperature
10 - 30°C
18
Tinv (*)
Winter season transition temperature
10 - 30°C
24
RHnS
Number of samples to calculate dynamic humidity setpoint
1 - 96
96 (15 min)
Содержание Energy SHP-130
Страница 29: ...29 Italiano Installazione del comando a muro 1 2 3 4 1 2 3 4 60 9 10 8 10 9 57 56 ...
Страница 59: ...59 Italiano ...
Страница 62: ...62 English 191 602 975 952 Ø125 547 6 0 2 952 184 1211 773 226 167 16 17 204 390 762 104 6 94 DIMENSIONS ...
Страница 71: ...71 English A A ATTENTION Before powering the unit make sure that the front cover A is closed see figure ...
Страница 85: ...85 English 1 2 3 4 1 2 3 4 60 9 10 8 10 9 57 56 Installing controller on the wall ...
Страница 115: ...115 English ...
Страница 118: ...118 191 602 975 952 Ø125 547 6 0 2 952 184 1211 773 226 167 16 17 204 390 762 104 6 94 Français DIMENSIONS ...
Страница 127: ...127 A A Français ATTENTION Avant d alimenter l appareil vérifier que la couverture frontale A est fermée voir la figure ...
Страница 141: ...141 1 2 3 4 1 2 3 4 60 9 10 8 10 9 57 56 Français Installation de la commande au mur ...
Страница 171: ...171 Français ...
Страница 174: ...174 191 602 975 952 Ø125 547 6 0 2 952 184 1211 773 226 167 16 17 204 390 762 104 6 94 Español DIMENSIONES ...
Страница 183: ...183 A A Español ATENCIÓN Antes de alimentar el aparato compruebe que la cubierta frontal A esté cerrada véase la figura ...
Страница 197: ...197 1 2 3 4 1 2 3 4 60 9 10 8 10 9 57 56 Español Instalación del mando en la pared ...
Страница 227: ...227 Español ...