Saab TankRadar
®
Pro
Pro Display Panel
5-21
Edition 2.
Ref. No: 306010E
DONE
DA Trim
-
AOut 1
Enter meter
value
4000
µ
A
3
Enter the measured value that corresponds to the 4 mA setting.
4
Click the DONE button.
Response
: the analog output is set to 20 mA.
5
Enter the measured value that corresponds to the 20 mA setting.
6
Click the DONE button.
Now the D/A calibration is finished, and the analog output is no
longer in fixed current mode.
7
. Select the Analog output2 option from the Advanced Setup menu (optional).
If the gauge is equipped with an extra analog output, follow the same configuration
procedure as for Analog Output1.
Configuration of the extra analog output is identical to configuration of analog
output 1. See step 6 above.