6
INGRESS PROTECTION IP66
(or as marked on the product - see chart below)
Suitable for use outdoors in all normal weather conditions as the electrical enclosures have at least
this level of ingress protection.
OPERATING TEMPERATURE
Ta -**°C to +**°C
The chart below shows the minimum and maximum ambient temperatures that the SA POWERNET
EX Splitter Unit are certified for use in. This varies according to the plug and sockets as follows:
ATX all voltages
Ta -40°C to +55°C
IP66
CEAG 110V/230V
Ta -55°C to +55°C
IP65
CEAG 24/42V
Ta -25°C to +55°C
IP54
Stahl 110V/230V
Ta -50°C to +45°C
IP66
Stahl 24V/42V
Ta -50°C to +40°C
IP66
Special versions with increased ambient temperature range are available in some variations