PREMASGARD
®
722x
Rev. 2021 - V11
Measuring channel 1
Pressure range
Type 7227
Pressure range
Type 7229
DIP
1
DIP
2
DIP
3
0...+1000 Pa
0...+100 Pa
OFF
OFF
OFF
0...+3000 Pa
0...+200 Pa
O N
OFF
OFF
0...+5000 Pa
0...+300 Pa
OFF
O N
OFF
0
...
+7000 Pa
0
...
+500 Pa
O N
O N
OFF
–1000...+1000 Pa
–100...+100 Pa
OFF
OFF
O N
–3000...+3000 Pa
–200...+200 Pa
O N
OFF
O N
–5000...+5000 Pa
–300...+300 Pa
OFF
O N
O N
–7000
...
+7000 Pa
–500
...
+500 Pa
O N
O N
O N
Measuring channel 2
Pressure range
Type 722x
DIP
4
DIP
5
DIP
6
0...+1000 Pa
OFF
OFF
OFF
0...+3000 Pa
O N
OFF
OFF
0...+5000 Pa
OFF
O N
OFF
0
...
+7000 Pa
O N
O N
OFF
–1000...+1000 Pa
OFF
OFF
O N
–3000...+3000 Pa
O N
OFF
O N
–5000...+5000 Pa
OFF
O N
O N
–7000
...
+7000 Pa
O N
O N
O N
Mode
Measurement signal filtering
Selectable time interval
DIP
7
10 s (default)
OFF
1 s
O N
Note: DIP 8 and 9 are not defined!
TYPES OF MONITORING:
(A) Below-atmospheric pressure:
P1 (+) is not connected
but open against atmosphere
P2 (–) connected to inside of duct
(B) Filter:
P1 (+) connected upstream of filter
P2 (–) connected downstream of filter
(C) Ventilator:
P1 (
+
) connected downstream of ventilator
P2 (
–
) connected upstream of ventilator
Pressure connections at the pressure
switch are marked with
P1 (+) for higher pressure and P2 (–) for
lower pressure.
Mounting diagram
(A)
(B)
(C)
AUTO
ZERO
OFFSET
MODE
1 2 3
ON DIP
4 5 6
ON DIP
7 8 9
ON DIP
1
2
3
1
2
GND
OUT 2
OUT 1
U+
1
2
3
4
LED
(Status)
+UB 24V AC / 15...36V DC
Output 1 pressure [Pa]
Output 2 pressure [Pa]
–UB GND
Schematic diagram
Pin assignment
(M12)
PREMASGARD
®
722x
PREMASGARD
®
722x
1
2
3
4
5
45°
1
2
3
4
5
–UB GND
+UB 24V AC / 15...36V DC
Shield
Output 1 pressure [Pa]
Output 2 pressure [Pa]