This device can be mounted in any position. Pressure ranges (measuring ranges) are indicated on the device label. Applying measuring pressures beyond that 
range will cause mismeasurements and increased deviations or may destroy the pressure measuring transducer. 

–  Attention! When leading in cables, make sure, they do not go under the board.  

This might buckle or damage hose connections! 

–  Pressure inputs are “poled“ i.e. the above-atmospheric pressure line must be connected at input P+  

and the below-atmospheric pressure line must be connected at input P–. 

–  At an adjusting element, the output signal can be offset by ±  10 % of the final value of the measuring range.  

In this way, possible ageing or drift effects can be compensated. 

–  Adjustment may only be made at the presence of differential pressure (ca. 90 % of final value).

–  By changing the offset at the adjusting element, factory-calibration is lost! 

–  If this device is operated beyond the specified range, all warranty claims are forfeited.

Our “General Terms and Conditions for Business“ together with the “General Conditions for the Supply of Products and Services of the Electrical and Electronics 
Industry“ (ZVEI conditions) including supplementary clause “Extended Retention of Title“ apply as the exclusive terms and conditions.

In additionIn addition, the following points are to be observed:
–  These instructions must be read before installation and putting in operation and all notes provided therein are to be  regarded!
–  Devices must only be connected to safety extra-low voltage and under dead-voltage condition. To avoid damages and errors the device (e.g. by voltage 

induction) shielded cables are to be used, laying parallel with current-carrying lines is to be avoided, and EMC directives are to be observed.

–  This device shall only be used for its intended purpose. Respective safety regulations issued by the VDE, the states, their  control authorities, the TÜV and 

the local energy supply company must be observed. The purchaser has to adhere to the building and safety regulations and has to prevent perils of any kind.

–  No warranties or liabilities will be assumed for defects and damages arising from improper use of this device.
–  Consequential damages caused by a fault in this device are excluded from warranty or liability.
–  These devices must be installed and commissioned by authorised specialists.
–  The technical data and connecting conditions of the mounting and operating instructions delivered together with the device are exclusively valid. Deviations 

from the catalogue representation are not explicitly mentioned and are possible in terms of technical progress and continuous improvement of our products.

–  In case of any modifications made by the user, all warranty claims are forfeited.
–  This device must not be installed close to heat sources (e.g. radiators) or be exposed to their heat flow. Direct sun irradiation or heat  irradiation by 

similar sources (powerful lamps, halogen spotlights) must absolutely be avoided.

–  Operating this device close to other devices that do not comply with EMC directives may influence functionality.
–  This device must not be used for monitoring applications, which serve the purpose of protecting persons against hazards or injury,  

or as an EMERGENCY STOP switch for systems or machinery, or for any other similar safety-relevant purposes.

–  Dimensions of housing or housing accessories may show slight tolerances on the specifications provided in these instructions.
–  Modifications of these records are not permitted.
–  In case of a complaint, only complete devices returned in original packing will be accepted.

Notes on commissioning: 

This device was calibrated, adjusted and tested under standardised conditions. When operating under deviating conditions, we recommend performing an 
initial manual adjustment on-site during commissioning and subsequently at regular intervals. 

Commissioning is mandatory and may only be performed by qualified personnel!  
These instructions must be read before installation and commissioning and all notes provided therein are to be regarded!

G  

General notes

Conversion table for pressure values:

Unit      =

bar

mbar

Pa

kPa

mH

2

O

1 Pa  

0.00001 bar 

0.01 mbar 

1 Pa 

0.001 kPa 

0.000101971 mH

2

O

1 kPa  

0.01 bar

10 mbar

1000 Pa

1 kPa

0.101971 mH

2

O

1 bar  

1 bar

1000 mbar

100000 Pa

100 kPa

10.1971 mH

2

O

1 mbar  

0.001 bar

1 mbar

100 Pa

0.1 kPa

0.0101971 mH

2

O

1 mH

2

O  

0.0980665 bar

98.0665 mbar

9806.65 Pa

9.80665 kPa

1 mH

2

O

Содержание PREMASGARD 121 Modbus Series

Страница 1: ...paktform mit Modbus Anschluss G Operating Instructions Mounting Installation Pressure and differential pressure measuring transducers incl connection set compact form with Modbus connection F Notice d...

Страница 2: ...Y Adapter adaptateur WS 04 Wetter und Sonnenschutz optional Weather and sun protection optional Protection contre les intemp ries et le soleil en option ohne Display without display sin cran mit Disp...

Страница 3: ...nes individuell programmierbaren Anzeigewertes ber die Modbusschnittstelle kann das Display sowohl im 7 Segment Bereich als auch im Dot Matrix Bereich individuell beschrieben werden BERWACHUNGSARTEN A...

Страница 4: ...sind in dieser Konfiguration durchzuf hren Die Offseteinstellung wird mithilfe eines Werkzeuges Schraubendreher 2 5 Klingenbreite durchgef hrt Automatisches Einstellen des Offsets 1 Zum Setzen des Nu...

Страница 5: ...Stoppbits OFF inaktiv default OFF inaktiv OFF Die Baudrate bertragungsgeschwindigkeit wird ber Pos 1 und 2 des DIP Schalters B eingestellt Einstellbar sind 9600 Baud 19200 Baud oder 38400 Baud siehe...

Страница 6: ...alten Informationen ber die darzustellenden Zeichen und Segmente Der Dot Matrix Bereich ist ebenfalls in der Defaulteinstellung Register 4x0001 enth lt den Wert 0 programmierbar Im 7 Segment Bereich w...

Страница 7: ...gle Register Function 16 Write Multiple Register Register Parameter Display Data Type Value Range 4x0001 physikalischer Anzeigewert Index im Display Unsigned 8 Bit 0 10 0 10 Differenzdruck in PA und h...

Страница 8: ...s Reset Listen Only Mode Echo Telegramm 04 Aktivierung Listen Only Mode Keine Antwort 10 L sche Z hler Echo Telegramm 11 Z hler Bustelegramme Unsigned 16 Bit alle g ltigen Bustelegramme 12 Z hler Komm...

Страница 9: ...leistungen und Haftungen bernommen Folgesch den welche durch Fehler an diesem Ger t entstehen sind von der Gew hrleistung und Haftung ausgeschlossen Montage und Inbetriebnahme der Ger te darf nur durc...

Страница 10: ...individually programmable display value The Modbus interface allows the display to be individually configured in the 7 segment area and in the dot matrix area TYPES OF MONITORING A Below atmospheric p...

Страница 11: ...device s pressure range Ex factory this potentiometer is in center position and is lacquer sealed All settings and adjustments that are made before must be done in this configuration Offset adjustment...

Страница 12: ...ive ON ODD numbered OFF Inactive no parity 2 stop bits OFF Inactive default OFF Inaktive OFF The baud rate speed of transmission is set at DIP switches 1 and 2 of DIP switch block B Selectable are 960...

Страница 13: ...t the characters and segments to be displayed The dot matrix area is also programmable in the default setting register 4x0001 contains the value 0 In this case the current measured value is automatica...

Страница 14: ...e Register Register Parameter Data Type Value Range 4x0001 Physical parameter displayed Index on display Unsigned 8 Bit 0 10 0 10 Differential pressure in PA and hP 0 Default setting Freely configurab...

Страница 15: ...Modbus Reset listen only mode Echo telegram 04 Activation listen only mode No answer 10 Delete counter Echo telegram 11 Counter bus telegrams Unsigned 16 Bit All valid bus telegrams 12 Counter commun...

Страница 16: ...or defects and damages arising from improper use of this device Consequential damages caused by a fault in this device are excluded from warranty or liability These devices must be installed and commi...

Страница 17: ...ie de texte possible sur l cran avec affichage 7 segments ou aussi affichage matrice de points via l interface Modbus MODES DE SURVEILLANCE A d pression P1 n est pas raccord ouvert c t air l atmosph r...

Страница 18: ...diane et recouvert de peinture Tous les r glages et toutes les op rations d ajustage effectu s pr c demment doivent tre r alis s dans cette configuration On r alise le r glage du point z ro l aide d u...

Страница 19: ...Baud vitesse de transfert est r gl via les pos 1 et 2 de l interrupteur DIP B On peut r gler 9600 Baud 19200 Baud ou 38400 Baud voir tableau La parit est r gl e via la pos 3 de l interrupteur DIP B On...

Страница 20: ...ns sur les caract res et segments afficher La zone de matrice de points est galement programmable dans le r glage par d faut le registre 4x0001 contient la valeur 0 Dans la zone 7 segments la valeur d...

Страница 21: ...r Registre Param tre Data Type Value Range 4x0001 Valeur d affichage physique Indice l cran Unsigned 8 bits 0 10 0 10 Pression diff rentielle in PA und hP 0 R glage par d faut Affichage librement conf...

Страница 22: ...coute Seule T l gramme d cho 04 Activation Listen Only Mode mode coute seule Pas de r ponse 10 Efface compteur T l gramme d cho 11 Compteur T l grammes de bus Unsigned 16 Bit Tous les t l grammes de b...

Страница 23: ...ctant les r gles de s curit correspondantes de la VDE des L nders de leurs organes de surveillance du T V et des entreprises d approvisionnement en nergie locales L acheteur doit respecter les disposi...

Страница 24: ...Modbus 7 A P1 P2 B P1 P2 C P1 P2 P1 P2 PREMASGARD 121x Modbus Modbus ASD 06 2 PREMASGARD 121x Modbus 110 Pa 110 Pa 110 Pa 110 Pa 110 Pa 110 Pa 110 Pa 110 Pa 110 Pa A B C WG01 PREMASGARD 121x Modbus 1...

Страница 25: ...Rec Err 1 2 3 4 5 12345678 ON DIPA 123456 ON DIPB Plug for display offset auto zero min max UB GND Shielding RS485 Modbus A RS485 Modbus B UB 24V AC DC mode Plug for display contact is on the right si...

Страница 26: ...IP 1 128 DIP 1 ON DIP 2 64 DIP 2 ON DIP 3 32 DIP 3 OFF DIP 4 16 DIP 4 OFF DIP 5 8 DIP 5 OFF DIP 6 4 DIP 6 OFF DIP 7 2 DIP 7 OFF DIP 8 1 DIP 8 ON 128 64 1 193 Modbus DIP 1 DIP 2 MODBUS DIP B 9600 ON OF...

Страница 27: ...001 10 4 0002 4 0012 4x0001 0 7 4x0005 0 A 1 B 2 C 3 D 4 DP 5 6 7 8 9 10 11 12 13 14 15 A A B C D E F G B C D DP 14 1 14 2 14 4x0003 4x0004 0 A 1 B 2 C 3 D 4 E 5 F 6 G 7 G 8 H 9 I 10 J 11 K 12 L 13 M...

Страница 28: ...6 97 a 98 b 99 c 100 d 101 e 102 f 103 g 104 h 105 i 106 j 107 k 108 l 109 m 110 n 111 o 112 p 113 q ASCII 114 r 115 s 116 t 117 u 118 v 119 w 120 x 121 y 122 z 123 124 125 129 132 142 148 153 154 223...

Страница 29: ...5000 3x0003 10 16 1000 1000 5000 5000 1000 1000 5000 5000 05 Write Single Coil 0x0001 0 0 1 ON OFF 08 Diagnostics 00 Loopback 01 Modbus Reset Listen Only Mode 04 Listen Only Mode 10 11 16 12 CRC 16 1...

Страница 30: ...30 1 0 00001 0 01 1 0 001 0 000101971 1 0 01 10 1000 1 0 101971 1 1 1000 100000 100 10 1971 1 0 001 1 100 0 1 0 0101971 1 0 0980665 98 0665 9806 65 9 80665 1 P P 10 90 ZVEI VDE EMV r...

Страница 31: ...n our General Terms and Conditions Sous r serve d erreurs et de modifications techniques Toutes les informations correspondent l tat de nos connaissances au moment de la publication Elles servent uniq...

Страница 32: ...120 0 1 1 1 1 0 0 0 121 0 1 1 1 1 0 0 1 122 0 1 1 1 1 0 1 0 123 0 1 1 1 1 0 1 1 124 0 1 1 1 1 1 0 0 125 0 1 1 1 1 1 0 1 126 0 1 1 1 1 1 1 0 127 0 1 1 1 1 1 1 1 128 1 0 0 0 0 0 0 0 129 1 0 0 0 0 0 0 1...

Отзывы: