![S+S Regeltechnik AEROGARD KCO2-W Скачать руководство пользователя страница 16](http://html1.mh-extra.com/html/s-s-regeltechnik/aerogard-kco2-w/aerogard-kco2-w_operating-instructions-mounting-and-installation_3195720016.webp)
D G F r
AERASGARD
®
KCO
2
- W
Schaltbild
KCO
2
- W
Connecting diagram
KCO
2
- W
Schéma de raccordement
Схема подключения
Anschlussbild
KCO
2
- W
Schematic diagram
KCO
2
- W
Schéma de raccordement
Схема подключения
1 2 3 4
ON DIP
SET
Zero
OFFSET
13 11 12 1 2 3
Öffner
Schließer
Ausgang CO
² in ppm –UB GND
+U
B 2
4V A
C/
DC
1 2 3 4
ON DIP
SET
Zero
OFFSET
13 11 12 1 2 3
Br
eak
er
Normall
y
open c
ont
act
Output CO
² in ppm –UB GND
+U
B 2
4V A
C/
DC
1
2
3
12
11
13
UB+ 24V AC/DC
Ausgang CO
2
0-10V/4...20mA
UB– GND
Öffner
Schließer
Wechsler
24V/1A
1
2
3
12
11
13
UB+ 24V AC/DC
Output CO
2
0-10V/4...20mA
UB– GND
Breaker
changeover
24V/1A
Normally
open contact
DIP-Schalter
KCO
2
- W
CO
2
- Gehalt
DIP 1
0...2000 ppm (default)
OFF
0...5000 ppm
O N
CO
2
- Nullpunktautomatik
DIP 3
deaktiviert
OFF
aktiviert (default)
O N
Ausgang
DIP 4
Spannung 0 -10 V (default)
OFF
Strom 4...20 mA
O N
Hinweis:
DIP 2
ist nicht belegt!
DIP switch
KCO
2
- W
CO
2
content
DIP 1
0...2000 ppm (default)
OFF
0...5000 ppm
O N
CO
2
automatic zero point
DIP 3
deactivated
OFF
activated (default)
O N
Output
DIP 4
Voltage 0 -10 V (default)
OFF
Current 4...20 mA
O N
Note:
DIP 2