Maintenance-free
AERASGARD
®
CO2 sensor for schools (RCO2-A NT)
with traffic light display, incl. power supply unit, self-calibrating, in an
elegant plastic housing, for determining the CO2 content of room air (0...3000 ppm). The measuring transducer converts the measurand to a
standard signal, which is directly presented visually by five coloured LEDs (traffic light indicator). Available in device versions
RCO2-A NT
for direct
wall mounting,
RCO2-A UPNT
for recessed installation on flush-mounting socket and
RCO2-A NT ST
with metal stand for flexible positioning.
The room sensor is designed for use in class, seminar and meeting rooms, offices, hotels, homes, shops etc. and provides a simple and fast way of
assessing the room climate. This enables an energy saving and on-demand room ventilation, thus reducing the overall operating costs and enhancing
the well-being of occupants. One sensor for every 30 m² of space is recommended.
The CO2 content is measured with an optical
NDIR sensor
(non-dispersive infra-red technology).
TECHNICAL DATA
Power supply:
RCO2-A UPNT:
24 V AC ⁄ DC (± 10 %)
RCO2-A NT, RCO2-A NT ST:
230 V AC (50 -60 Hz)
Electrical connection:
power supply unit 230 V ⁄ 50 -60 Hz (included in the scope of delivery)
Sensor:
optical NDIR sensor (non-dispersive infrared technology),
with manual calibration (via zero button),
with automatic calibration
Measurement range:
0…3000 ppm
Measuring accuracy:
typically ± 30 ppm ± 3% of measured value
Temperature dependence:
± 5 ppm ⁄ °C or ± 0.5% of measured value ⁄ °C
(whichever is greater)
Pressure dependence:
± 0.13% ⁄ mm Hg
Long-term stability:
< 2% in 15 years
Gas exchange:
by diffusion
Ambient temperature:
0...+ 50 °C
Warm-up time:
approx. 1 hour
Measuring interval:
< 3 seconds
Housing:
plastic, material ABS, colour pure white (similar to RAL 9010)
Dimensions:
85 x 85 x 27 mm (Baldur 1)
Installation:
RCO2-A NT, RCO2-A UPNT:
directly on wall or on flush-mounting socket, Ø 55 mm, 4-hole base part,
for installation on vertically or horizontally installed flush-mounting socket
with cable entry from behind, with breaking points for on-wall installation
and cable entry from above or below
RCO2-A NT ST:
immediately usable free-standing device with wall power supply (plug-and-play)
Protection class:
III (according to EN 60 730)
IP rating:
IP 30
(according to EN 60 529)
Standards:
CE-conformity, electromagnetic compatibility
according to EN 61 326, EMC directive 2014 ⁄ 30 ⁄ EU,
low voltage directive 2014 ⁄ 35 ⁄ EU
Equipment:
Traffic light display
(five coloured LEDs, see table)
for indication of CO2 concentration
Plug-in power supply unit
(connection cable approx. 1.5 m) or
Flush-mount power supply unit
for installation on flush-mount socket
Stainless steel
stand
(
RCO2-A NT ST
)
AERASGARD
®
RCO2-A NT
CO2 sensor for schools with traffic light display and power supply unit
Type ⁄ WG02
Measuring ranges
CO2
Display
CO2
Equipment
Item no.
(Baldur 1)
RCO2 -A NT
RC O2-A N T
0...3000 ppm
5 LEDs
Plug-in power supply unit
1501-61A0-7331-232
RC O2-A N T S T
0...3000 ppm
5 LEDs
Plug-in power supply unit, stainless steel stand
1501-61A0-7331-231
RC O2-A UP N T
0...3000 ppm
5 LEDs
Flush-mount power supply unit
1501-61A0-7331-233
Note:
This unit must
not
be used as safety-relevant device!