S+S Regeltechnik Aerasgard KCO2 Series Скачать руководство пользователя страница 6

G  

AERASGARD

®

  KCO

2

Connecting diagram 

KCO

2

Connecting diagram 

KCO

2

 - W

Schematic diagram KCO

2

 - W 

KCO

2

1

2

3

UB- GND
UB+ supply voltage 24V AC/DC

Output 0-10V  CO

2

-content in ppm

1

2

3

5

6

7

UB- GND
UB+ supply voltage 24V AC/DC

Output 0-10V  CO

2

-content in ppm

Normally open

contact
Breaker

1

2

3

5

6

7

(KCO

2

-W)

min. max.

2000 5000 10000 aut

o

1 2 34

ON 

ATM

Sensor plug

Set CO

2

Output CO

2

 c

ont

ent

  0-10V

UB+ 24V A

C/DC

UB- GND

Br

eak

er

Normall

y open 

CO

range 

Switching 

threshold adjustment 

Measuring range

selection CO

2

Button and LED 

for manual CO

2

 

setting 

Atmospheric

pressure sensor

The self-calibrating microprocessor-controlled AERASGARD

®

 KCO

2

 is designed for 

duct  installation and is used to detect the CO

2

 content in air. This CO

2

 sensor is 

 optionally available with or without display. The measurement signals are converted 
into standard signals of 0 -10 V. Optionally, the CO

2

 measuring transducer can be 

supplied with switching output. 

The CO

2

 content in air is determined by a NDIR sensor (non-dispersive infrared 

technology). The detection range of this CO

2

 sensor is calibrated for standard appli-

cations such as  monitoring of residential rooms or conference rooms. Room venti-
lation on an as-needed basis, improvement of well-being and customer benefit, 
 increased comfort as well as a reduction of operating costs by energy conservation 
are only some of the beneficial results of employing AERASGARD

®

 KCO

2

 sensors. 

A measuring system based on NDIR (non-dispersive infrared sensor) technology for 
CO

2

  measurement consists of a light source and a receptor. A certain range of 

wavelengths of light radiated off by the source is damped respectively absorbed by 
CO

2

 molecules in the  measured section. That damping is detected by the receptor. 

TECHNICAL DATA:
Power supply: .................................. 24 V AC ⁄ DC

Sensor: ............................................. optical sensor  (NDIR)  

with automatic self-calibration,  
non-dispersive infrared technology, 
including atmospheric pressure compensation

Measuring range: ........................... multi-range switching   

(selectable via DIP switches)  
0 … 2000 ppm;    0 … 5000 ppm;    0 … 10000 ppm 

Output: ............................................. 0 -10 V or with potential-free changeover  

contact  (24 V)

Measuring accuracy CO

2

:............. ± 100 ppm plus 5 % of measured value

Pressure dependence: .................. <  ±  0,5 %  of  measured  value  ⁄  kPa   

at compensated versions (standard),  
otherwise  ±  1,6  %  of  measured  value  ⁄  kPa    
(referred to standard pressure)

Temperature dependence: ........... < 5 ppm  ⁄ K (referred to 20 °C)

Long-term stability: ....................... ± 1 % of final value per year

Service life: ...................................... > 12 years

Gas exchange: ................................. by diffusion

Ambient temperature: .................. 0 …+50 °C

Electrical connection: .................... 0.14 - 1.5 mm

2

,  

via terminals on circuit board

Enclosure: ........................................ plastic, polyamide, 30 % glass-globe-reinforced,  

with quick-locking screws,  
colour pure white (similar RAL 9010)

Dimensions: ..................................... 108  x  73.5  x 70 mm

Cable gland: ..................................... M16, including strain relief

Protective tube: ............................. metal, Ø 20 mm,  

nominal  length  NL = 190 mm

Process connection:  ..................... by mounting flange,  

plastic  (included in the scope of delivery), 
galvanised steel optional

Protection class:  ........................... III  (according to EN 60 730)

Protection type:  ............................. IP 65  (according to EN 60 529)

Standards:  ...................................... CE-conformity,  

electromagnetic compatibility  
according  to  EN  61 326 + A1 + A2,   
EMC directive 2004 ⁄ 108 ⁄ EC 

Optional: ........................................... 8 - digit  display,   

cutout  36 x14  mm  (W x H), 
for displaying actual CO

2

 content

6

Содержание Aerasgard KCO2 Series

Страница 1: ...usgang G Operating Instructions Mounting Installation Duct CO2 sensors respectively measuring transducers including mounting flange self calibrating with multi range switching and active output F Noti...

Страница 2: ...AERASGARD KCO2 D G F r Ma zeichnung KCO2 Dimensional drawing Plan cot...

Страница 3: ...ssbereich Mehrbereichsumschaltung ber DIP Schalter w hlbar 0 2000 ppm 0 5000 ppm 0 10000 ppm Ausgang 0 10V oder mit potentialfreiem Wechsler 24 V Messgenauigkeit CO2 100ppm zzgl 5 vom Messwert Druckab...

Страница 4: ...des Jumpers durch das Bet tigen des Tasters gestartet werden Nach dem Anschlie en des Ger tes ist ein Dauerbetrieb von mindestens 10 Minuten bei Frischluft CO2 Gehalt 300ppm 400 ppm sicherzustellen D...

Страница 5: ...Fortschritts und der stetigen Verbesserung unserer Produkte m glich Bei Ver nderungen der Ger te durch den Anwender entfallen alle Gew hrleistungsanspr che Dieses Ger t darf nicht in der N he von W rm...

Страница 6: ...ared sensor technology for CO2 measurement consists of a light source and a receptor A certain range of wavelengths of light radiated off by the source is damped respectively absorbed by CO2 molecules...

Страница 7: ...t of correction is here limited to 40 ppm interval Manual calibration of carbon dioxide measurement Manual calibration can be started independently from the position of jumper J3 by pushing the button...

Страница 8: ...in terms of technical progress and continuous improvement of our products In case of any modifications made by the user all warranty claims are forfeited This device must not be installed close to hea...

Страница 9: ...Un syst me de mesure du CO2 bas sur la technologie NDIR capteur infrarouge non dispersif est compos d une source lumineuse et d un r cepteur Une certaine gamme d ondes de la lumi re mise par la source...

Страница 10: ...a correction maximale est limit e 40 ppm intervalle talonnage manuel de la mesure du dioxyde de carbone L talonnage manuel peut tre lanc ind pendamment de la position du cavalier J3 en actionnant le b...

Страница 11: ...ont pas mentionn es explicitement et sont possibles suite au progr s technique et l am lioration continue de nos produits En cas de modifications des appareils par l utilisateur tous droits de garanti...

Страница 12: ...CO 2 Output CO 2 content 0 10V UB 24V AC DC UB GND Breaker Normally open CO2 range Switching threshold adjustment Measuring range selection CO2 Button and LED for manual CO2 setting Atmospheric press...