This device can be mounted in any position. The voltage output is short-circuit proof. Applying overvoltage at the voltage output will destroy this device.  

Pressure ranges are indicated on the device label. Applying measuring pressures beyond that range will cause mismeasurements and increased 

deviations or may destroy the device.
–  Attention! When leading in cables, make sure, they do not go under the board.  

This might buckle or damage hose connections!

–  Pressure inputs are “poled“ i.e. the above-atmospheric pressure line must be connected at input P+  

and the below-atmospheric pressure line must be connected at input P–.

–  At an adjusting element, the output signal can be offset by ±  10 % of the final value of the measuring range.  

In this way, possible ageing or drift effects can be compensated. 

–  If this device is operated beyond the specified range, all warranty claims are forfeited.

Our “General Terms and Conditions for Business“ together with the “General Conditions for the Supply of Products and Services of the Electrical and Elec-

tronics Industry“ (ZVEI conditions) including supplementary clause “Extended Retention of Title“ apply as the exclusive terms and conditions.

In additionIn addition, the following points are to be observed:
–  These instructions must be read before installation and putting in operation and all notes provided therein are to be  regarded!
–  A suitable weather and sun protection hood must be used when installed outdoors.
–  Devices must only be connected to safety extra-low voltage and under dead-voltage condition. To avoid damages and errors the device (e.g. by voltage 

induction) shielded cables are to be used, laying parallel with current-carrying lines is to be avoided, and EMC directives are to be observed.

–  This device shall only be used for its intended purpose. Respective safety regulations issued by the VDE, the states, their  control authorities, the TÜV and 

the local energy supply company must be observed. The purchaser has to adhere to the building and safety regulations and has to prevent perils of any kind.

–  No warranties or liabilities will be assumed for defects and damages arising from improper use of this device.
–  Consequential damages caused by a fault in this device are excluded from warranty or liability.
–  These devices must be installed and commissioned by authorised specialists.
–  The technical data and connecting conditions of the mounting and operating instructions delivered together with the device are exclusively valid. Deviations 

from the catalogue representation are not explicitly mentioned and are possible in terms of technical progress and continuous improvement of our products.

–  In case of any modifications made by the user, all warranty claims are forfeited.
–  This device must not be installed close to heat sources (e.g. radiators) or be exposed to their heat flow. Direct sun irradiation or heat  irradiation by 

similar sources (powerful lamps, halogen spotlights) must absolutely be avoided.

–  Operating this device close to other devices that do not comply with EMC directives may influence functionality.
–  This device must not be used for monitoring applications, which serve the purpose of protecting persons against hazards or injury,  

or as an EMERGENCY STOP switch for systems or machinery, or for any other similar safety-relevant purposes.

–  Dimensions of housing or housing accessories may show slight tolerances on the specifications provided in these instructions.
–  Modifications of these records are not permitted.
–  In case of a complaint, only complete devices returned in original packing will be accepted.

Notes on commissioning: 

This device was calibrated, adjusted and tested under standardised conditions. When operating under deviating conditions, we recommend performing an 

initial manual adjustment on-site during commissioning and subsequently at regular intervals. 

Commissioning is mandatory and may only be performed by qualified personnel!  

These instructions must be read before installation and commissioning and all notes provided therein are to be regarded!

G  

General notes

Connecting scheme 

Parallel operation

Connecting scheme 

Individual operation

SUPPLY  VOLTAGE :

For operating voltage reverse polarity protection, a one-way rectifier or 
reverse polarity protection diode is integrated in this device variant. 

 

This internal one-way rectifier also allows operating 0 - 10 V devices on AC 
 supply  voltage. 

The output signal is to be tapped by a measuring instrument. Output 
 voltage is measured her against zero potential (O V) of the input voltage!

When this device is operated on 

DC supply voltage

, the operating voltage 

input UB+ is to be used for 15...36 V DC supply and UB – or GND for 
ground wire!

When several devices are supplied by one 24 V

 AC voltage supply

, it is to be 

ensured that all ”positive“ operating voltage input terminals (+) of the field 
devices are connected with each other and all ”negative“ operating voltage 
input terminals (–) (= reference potential) are connected together (in-phase 
connection of field devices). All outputs of field devices must be referenced 
to the same potential!

In case of reversed polarity at one field device, a supply voltage short- 
circuit would be caused by that device. The consequential short-circuit 
current flowing through this field device may cause damage to it. 

Therefore, pay attention to correct wiring!

Circuitry

Circuitry

0...10V

0V/GND

0...10V

0V/GND

Power supply

AC 24V~ 

0V

DC 15-36V =  GND

Circuitry

0...10V

0V/GND

V

Power supply

AC 24V~ 

0V

DC 15-36V =  GND

 

# 502

00 - 2020

Содержание 2004-6191-1100-001

Страница 1: ...nd aktivem Ausgang G Operating Instructions Mounting Installation Pressure and differential pressure measuring transducers adjustable calibratable with multi range switching and active output F Notice...

Страница 2: ...8 8 17 126 8 8 17 126 8 8 17 126 8 8 17 126 113 M20x1 5 M20x1 5 143 61 126 8 8 17 126 8 8 17 Schnell Steckanschluss standardm ig Quick connect standard Raccord rapide de s rie 126 M12 M12 113 M20x1 5...

Страница 3: ...ng mit 8 umschaltbaren Messbereichen siehe Tabelle Druckart Differenzdruck Druckanschluss standardm ig mittels Schnell Steckanschluss aus rostfreiem Stahl f r PVC Gewebe Druckschlauch 6 mm 4 8 mm opti...

Страница 4: ...2004 6192 1100 011 PREMASGARD 7115 I_ VA Q 4 20 mA 2004 6191 2200 011 2004 6191 2100 011 PREMASGARD 7115 I_ VA Q LCD 4 20 mA 2004 6192 2200 011 2004 6192 2100 011 max 100 100 Pa Typ 7110 0 50 Pa 50 50...

Страница 5: ...UB GND Ausgang Druck 4 20mA in Pa Umrechnungstabelle f r Druckwerte Einheit bar mbar Pa kPa mWs 1 Pa 0 00001 bar 0 01 mbar 1 Pa 0 001 kPa 0 000101971 mWs 1 kPa 0 01 bar 10 mbar 1000 Pa 1 kPa 0 101971...

Страница 6: ...llpunktkalibrierung 1 2 3 AUTO ZERO SET min max OFFSET 1 2 3 4 5 6 ON DIP UB 15 36V DC Ausgang Druck 4 20mA Pa UB GND LCD Hintergrundbeleuchtung autom Nullpunktkalibrierung Stecker Display Offset Korr...

Страница 7: ...des Nullpunktes abgeglichen werden Der Einstellbereich betr gt ca 10 vom Druckbereich ber ein internes Ventil wird zyklisch ein Nullpunktabgleich durchgef hrt Die Zykluszeit ist zwischen 15 Minuten un...

Страница 8: ...g bei Mittelstellung des Offsetreglers 5V bei OPa Druckdifferenz Ausgangsspannung 0 10V f r Druckdifferenz P P PREMASGARD 711x MB 0 xxPa Nach erfolgreicher Nullpunktkalibrierung betr gt die Ausgangssp...

Страница 9: ...Bei Ver nderungen der Ger te durch den Anwender entfallen alle Gew hrleistungsanspr che Dieses Ger t darf nicht in der N he von W rmequellen z B Heizk rpern oder deren W rmestrom eingesetzt werden ein...

Страница 10: ...g ranges see table Type of pressure differential pressure Pressure connection equipped as standard with quick connect made from stainless steel for PVC fabric pressure hose 6 mm 4 8 mm optional option...

Страница 11: ...4 6192 1200 011 2004 6192 1100 011 PREMASGARD 7115 I_ VA Q 4 20 mA 2004 6191 2200 011 2004 6191 2100 011 PREMASGARD 7115 I_ VA Q LCD 4 20 mA 2004 6192 2200 011 2004 6192 2100 011 max 100 100 Pa Type 7...

Страница 12: ...65 kPa 1 mH2O 3 wire connection 3 wire connection 2 wire connection PREMASGARD 711x U PREMASGARD 711x I PREMASGARD 711x I 1 2 3 230V AC PLC Working resistance 24V DC UB 24V DC Output pressure Pa 4 20m...

Страница 13: ...oint calibration 1 2 3 AUTO ZERO SET min max OFFSET 1 2 3 4 5 6 ON DIP UB 15 36V DC Output pressure 4 20mA Pa UB GND LCD backlighting automatic zero point calibration Plug for display Offset correctio...

Страница 14: ...n be set between 15 minutes and 24 hours using the SET potentiometer During the automatic calibration the output value remains at its last pressure value DIP switches for pressure range setting output...

Страница 15: ...ssure difference with the offset knob in central position Output voltage 0 10 V for pressure difference P P PREMASGARD 711x Range 0 xxPa After successful zero point calibration the output current is 4...

Страница 16: ...ur products In case of any modifications made by the user all warranty claims are forfeited This device must not be installed close to heat sources e g radiators or be exposed to their heat flow Direc...

Страница 17: ...s Plages de mesure commutation multi gamme avec 8 plages de mesure commutables voir tableau Type de pression Pression diff rentielle Prise de pression de s rievia un raccord rapide enficher en acier i...

Страница 18: ...011 2004 6192 1100 011 PREMASGARD 7115 I_ VA Q 4 20 mA 2004 6191 2200 011 2004 6191 2100 011 PREMASGARD 7115 I_ VA Q LCD 4 20 mA 2004 6192 2200 011 2004 6192 2100 011 max 100 100 Pa Type 7110 0 50 Pa...

Страница 19: ...0665 kPa 1 mWs 3 fils raccordement 3 fils raccordement 2 fils raccordement PREMASGARD 711x U PREMASGARD 711x I PREMASGARD 711x I 1 2 3 230V AC PLC Working resistance 24V DC UB 24V DC Output pressure P...

Страница 20: ...TO ZERO SET min max OFFSET 1 2 3 4 5 6 ON DIP UB 15 36V DC Output pressure 4 20mA Pa UB GND LCD backlighting automatic zero point calibration Plug for display Offset correction ca 10 of final value Pu...

Страница 21: ...u point z ro La plage de r glage est d environ 10 de la plage de pression Une soupape interne permet d effectuer cycliquement un talonnage du point z ro La dur e du cycle peut tre r gl e entre 15 minu...

Страница 22: ...est de 5 V pour une diff rence de pression de 0 Pa Tension de sortie 0 10 V pour diff rence de pression P P PREMASGARD 711x plage de mesure 0 xxPa Une fois le calibrage du point z ro effectu le couran...

Страница 23: ...itement et sont possibles suite au progr s technique et l am lioration continue de nos produits En cas de modifications des appareils par l utilisateur tous droits de garantie ne seront pas reconnus C...

Страница 24: ...5 24 0 10 4 20 2 3 8 6 4 8 V2A 1 4305 6 20 50 C 7112 25 1 7110 100 2 7111 1000 5 7115 5000 25 1 2 250 0 1 C 0 3 C 250 0 7 1 4 250 100 1 c 10 c DIP 0 14 1 5 V2A 1 4305 M 20 x 1 5 6 12 M12 5 A DIN EN 61...

Страница 25: ...6192 1100 011 PREMASGARD 7115 I_ VA Q 4 20 A 2004 6191 2200 011 2004 6191 2100 011 PREMASGARD 7115 I_ VA Q LCD 4 20 A 2004 6192 2200 011 2004 6192 2100 011 100 100 7110 0 50 50 50 0 100 100 100 PREMA...

Страница 26: ...ASGARD 711x I 1 2 3 230V AC PLC Working resistance 24V DC UB 24V DC Output pressure Pa 4 20mA UB GND 1 2 3 230V AC 24V AC DC PLC PC UB 24V AC DC Output pressure Pa 0 10V UB GND 1 2 3 230V AC 24V AC DC...

Страница 27: ...o point calibration 1 2 3 AUTO ZERO SET min max OFFSET 1 2 3 4 5 6 ON DIP UB 15 36V DC Output pressure 4 20mA Pa UB GND LCD backlighting automatic zero point calibration Plug for display Offset correc...

Страница 28: ...lue Pushbutton Zero point setting Contact pin side SET Setting Cycle time autom zero point calibration 15 24 default DIP 1 DIP 2 0 25 0 50 0 100 0 1000 25 25 50 50 100 100 1000 1000 OFF OFF 0 300 0 20...

Страница 29: ...29 r PREMASGARD 711x PREMASGARD 711x 0 xx 0 0 0 10 0 PREMASGARD 711x xx xx 5 0 0 10 PREMASGARD 711x 0 xx 4 0 4 20 0 PREMASGARD 711x xx xx 12 0 4 20...

Страница 30: ...30 P P 10 ZVEI VDE EMV r 0 10 0 UB 15 36 UB GND 24 Circuitry Circuitry 0 10V 0V GND 0 10V 0V GND Power supply AC 24V 0V DC 15 36V GND Circuitry 0 10V 0V GND V Power supply AC 24V 0V DC 15 36V GND...

Страница 31: ...ol their particular suitability must be verified by each customer and or end user themselves Existing property rights must be observed We warrant the faultless quality of our products as stated in our...

Страница 32: ...D G F r PREMASGARD 711x VA PREMASGARD 711x VAQ PREMASGARD 711x VA LCD PREMASGARD 711x VAQ LCD WS 03 Wetter und Sonnenschutz optional Weather and sun protection optional Protection contre les intemp ri...

Отзывы: