AERASGARD

®

    FSFTM - CO2 - Modbus

  |   Télégrammes

TÉLÉGRAMMES 
Function 04 Read Input Register

Registre

Paramètre

Data Type

Value

Range

3x0001

CO2

Balayage  4 s  

Signed 16 Bit

350…5000

350...5000 ppm

3x0002

CO2

Filtrage  32 s

Signed 16 Bit

350…5000

350...5000 ppm

3x0003

COV

Balayage  4 s  

Signed 16 Bit

0…1000

0.0...100.0 %  COV

3x0004

COV

Filtrage  32 s

Signed 16 Bit

0…1000

0.0...100.0 %  COV

3x0005

Température

Balayage  4 s  

Signed 16 Bit

0…500

0.0...+50.0 °C

3x0006

Température

Filtrage  32 s

Signed 16 Bit

0…500

0.0...+50.0 °C

3x0007

Humidité relative

Balayage  4 s  

Signed 16 Bit

0…1000

0.0...100.0 %  h.r.

3x0008

Humidité relative

Filtrage  32 s

Signed 16 Bit

0…1000

0.0...100.0 %  h.r.

3x0009

*

non affecté

3x0010

*

non affecté

3x0011

*

Position du potentiomètre

aucun filtrage

Signed 16 Bit

0...1000

0.0...100.0 %  h.r.

uniquement pour version d'appareil avec potentiomètre de consigne

Function 05 Write Single Coil

Registre

Paramètre

Data Type

Value

Range

0x0001

Réinitialisation (Autozero)  CO2

Bit 0

0 / 1

OFF - ON

0x0003

Calibrage automatique (Automatic)  CO2

Bit 2

0 / 1

OFF - ON

Function 06 Write Single Register & Function 16 Write Multiple Register

Registre

Paramètres (écran)

Data Type

Value

Range

4x0021

*

Offset  CO2

Signed   16 Bit

–512...511

Offset

4x0022

*

non affecté

Signed   16 Bit

–512...511

Offset

4x0023

*

Offset  température

Signed   16 Bit

–512...511

Offset

4x0024

*

Offset  humidité relative

Signed   16 Bit

–512...511

Offset

uniquement pour version d'appareil avec potentiomètre de consigne

Function 08 Diagnostics   

Les

 codes sous-fonction suivants 

sont pris en charge 

Code sous-

fonction

Paramètre

Data Type

Réponse

00

Écho des données d'émission (loopback-rebouclage)

Données d'écho

01

Redémarrage Modbus (Reset Listen Only Mode –  

Réinit Mode Écoute Seule)

Télégramme d'écho

04

Activation Listen Only Mode (mode Écoute seule)

Pas de réponse

10

Efface compteur

Télégramme d'écho

11

Compteur Télégrammes de bus

Unsigned 16 Bit

Tous les télégrammes de bus valides

12

Compteur Erreur de communication 

(Parité, CRC, erreur Frame, etc.)

Unsigned 16 Bit

Télégrammes de bus erronés

13

Compteur Messages d'exception

Unsigned 16 Bit

Compteur d'erreurs

14

Compteur Télégrammes esclaves

Unsigned 16 Bit

Télégrammes esclaves

15

Compteur Télégrammes sans réponse

Unsigned 16 Bit

Message de Broadcast (adresse A)

Function 17 Report Slave ID    

Structure du télégramme de réponse 

n° de byte

Paramètre

Data Type

Réponse

00

Nombre de bytes

Unsigned 8 Bit

6

01

ID  esclave (Device Type)

Unsigned 8 Bit

14 = 

AERSGARD

®

 Modbus

02

ID  esclave (Device Class)

Unsigned 8 Bit

60 = 

AERASGARD

®

 / 

AERASREG

®

03

Statut 

Unsigned 8 Bit

255 = RUN, 0 = STOP

04

Numéro de version (release)

Unsigned 8 Bit

1…9

05

Numéro de version (version)

Unsigned 8 Bit

1…99

06

Numéro de version (index)

Unsigned 8 Bit

1

Содержание 1501-9226-6001-162

Страница 1: ...sor or measuring transducer in wall in the panel switch programme with Modbus connection F Notice d instruction Sonde d ambiance d humidit de temp rature et de CO2 resp convertisseur de mesure montage...

Страница 2: ...RD FSFTM CO2 Modbus D G F r Ma zeichnung Dimensional drawing Plan cot Ma zeichnung Dimensional drawing Plan cot 15 5 55 3 43 80 55 80 50 60 60 12 40 5 55 3 80 55 80 50 60 60 FSFTM CO2 Modbus P FSFTM C...

Страница 3: ...er keine Sollwertverstellung m glich KOHLENDIOXID CO2 Sensor CO2 optischer NDIR Sensor nicht dispersive Infrarot Technologie mit manueller Kalibrierung ber Zero Taster mit automatischer Kalibrierung a...

Страница 4: ...Vorg nge die die Umgebungsluft beeinflussen zu unterbinden Gehen Sie wie folgt vor 1x w chentlich f r 15 20 Minuten alle Fenster komplett ffnen bzw die L ftungsanlage auf Au enluft einstellen Wenn m g...

Страница 5: ...ngsgeschwindigkeit wird ber Pos 1 und 2 des DIP Schalters B eingestellt Einstellbar sind 9600 Baud 19200 Baud oder 38400 Baud siehe Tabelle Die Parity wird ber Pos 3 des DIP Schalters B eingestellt Ei...

Страница 6: ...fset CO2 Signed 16 Bit 512 511 Offset 4x0022 nicht belegt Signed 16 Bit 512 511 Offset 4x0023 Offset Temperatur Signed 16 Bit 512 511 Offset 4x0024 Offset relative Feuchte Signed 16 Bit 512 511 Offset...

Страница 7: ...etrennte Segmente aufzuteilen Die Teilnehmeradresse kann von 1 bis 247 eingestellt werden F r die Busleitung ist ein Kabel mit paarverseilter Datenleitung Spannungsversorgung und Kupferabschirmgeflech...

Страница 8: ...achten und Gef hrdungen aller Art zu vermeiden F r M ngel und Sch den die durch unsachgem e Verwendung unserer Ger te entstehen bernehmen wir keine Gew hrleistung Die Installa tion der Ger te darf nu...

Страница 9: ...an diesem Ger t entstehen sind von der Gew hrleistung und Haftung ausgeschlossen Montage und Inbetriebnahme der Ger te darf nur durch Fachpersonal erfolgen Es gelten ausschlie lich die technischen Dat...

Страница 10: ...h Jaeger CARBON DIOXIDE CO2 Sensor CO2 optical NDIR sensor non dispersive infra red technology with manual calibration via zero button with automatic calibration can be deactivated via Modbus Long ter...

Страница 11: ...r at regular intervals and to stop all CO2 producing processes that influence the ambient air Proceed as follows Open all windows fully or set the air conditioning system to use outdoor air 1x weekly...

Страница 12: ...efault OFF Inactive OFF The baud rate speed of transmission is set at DIP switches 1 and 2 of DIP switch block B Selectable are 9600 baud 19200 baud or 38400 baud see table Parity is set at DIP switch...

Страница 13: ...Signed 16 Bit 512 511 Offset 4x0022 not assigned Signed 16 Bit 512 511 Offset 4x0023 Offset temperature Signed 16 Bit 512 511 Offset 4x0024 Offset relative humidity Signed 16 Bit 512 511 Offset only...

Страница 14: ...scribers is greater the bus must be subdivided into several segments separated by repeaters The subscriber address can be set from 1 to 247 For the bus line a twisted pair cable data line power supply...

Страница 15: ...ir intended purpose Respective safety regulations issued by the VDE the states their control authorities the T V and the local energy supply company must be observed The buyer has to ensure adherence...

Страница 16: ...device Consequential damages caused by a fault in this device are excluded from warranty or liability These devices must be installed and commissioned by authorised specialists The technical data and...

Страница 17: ...ainsi que valeur de consigne du potentiom tre chez Busch Jaeger aucun r glage de la valeur de consigne possible DIOXYDE DE CARBONE CO2 Capteur CO2 capteur optique NDIR technologie infrarouge non disp...

Страница 18: ...r le syst me de ventilation sur air ext rieur tout en vitant toute op ration g n rant du CO2 qui pourrait influencer l air ambiant Proc der comme suit 1 fois par semaine ouvrir compl tement toutes les...

Страница 19: ...B On peut r gler 9600 Baud 19200 Baud ou 38400 Baud voir tableau La parit est r gl e via la pos 3 de l interrupteur DIP B On peut r gler EVEN paire ou ODD impaire voir tableau La protection par parit...

Страница 20: ...Offset 4x0023 Offset temp rature Signed 16 Bit 512 511 Offset 4x0024 Offset humidit relative Signed 16 Bit 512 511 Offset uniquement pour version d appareil avec potentiom tre de consigne Function 08...

Страница 21: ...doit tre r parti en plusieurs segments par l interm diaire de repeaters L adresse des correspondants peut tre fix e de 1 247 Pour la ligne de bus on peut utiliser un c ble avec ligne de donn es alimen...

Страница 22: ...age pr vu Les r gles de s curit correspondantes de la VDE des L nders de leurs organes de surveillance du T V et des entreprises d approvisionnement en nergie locales sont respecter L acheteur doit re...

Страница 23: ...ons toute responsabilit ou garantie pour les d fauts et dommages r sultant d une utilisation inappropri e de cet appareil Nous d clinons toute responsabilit ou garantie au titre de tout dommage cons c...

Страница 24: ...bus 2 15 CO2 0 5000 1 CO2 30 1 3 CO2 5 1 C 0 5 C 0 13 1 2 1 0 100 0 95 3 0 20 80 25 C 5 0 0 50 C 0 8 K 25 C 55 0 14 1 5 35 85 C 0 50 C 90 III EN 60730 IP20 EN 60529 EN 61326 2014 30 EC GIRA System 55...

Страница 25: ...1 30 50 1 2 3 50 CO2 ABC 350 500 1 15 20 Modbus CO2 ABC 350 500 1 1 2 ZERO CO2 5 AUTO 0 5 600 3 4 10 350 500 1 5 5 6 7 6 7 4 3 4 3 free free Shielding Modbus A Modbus B UB GND UB 24V AC DC FSFTM CO2...

Страница 26: ...28 DIP 1 ON DIP 2 64 DIP 2 ON DIP 3 32 DIP 3 OFF DIP 4 16 DIP 4 OFF DIP 5 8 DIP 5 OFF DIP 6 4 DIP 6 OFF DIP 7 2 DIP 7 OFF DIP 8 1 DIP 8 ON 128 64 1 193 Modbus DIP 1 DIP 2 MODBUS DIP B 9600 ON OFF 1 2...

Страница 27: ...100 0 3x0009 3x0010 3x0011 16 0 1000 0 0 100 0 05 Write Single Coil 0x0001 Autozero CO2 0 0 1 OFF ON 0x0003 Automatic CO2 2 0 1 OFF ON 06 Write Single Register 16 Write Multiple Register 4x0021 CO2 1...

Страница 28: ...odbus 32 1 247 100 Profibus Slave n MODBUS RTU Master RS 485 20 n 40 n Slave 1 Slave 2 LA LA A D1 D GND B D0 D MODBUS RTU Master Slave 1 Slave 2 5 B RBIAS RBIAS RAB RAB r AERASGARD FSFTM CO2 Modbus Re...

Страница 29: ...29 r VDE...

Страница 30: ...30 0 100 0 10 10 0 99 9 0 10 24 CO2 ZVEI VDE EMV VDE VDI 0 5 g r...

Страница 31: ...ust be verified by each customer and or end user themselves Existing property rights must be observed We warrant the faultless quality of our products as stated in our General Terms and Conditions Sou...

Страница 32: ...120 0 1 1 1 1 0 0 0 121 0 1 1 1 1 0 0 1 122 0 1 1 1 1 0 1 0 123 0 1 1 1 1 0 1 1 124 0 1 1 1 1 1 0 0 125 0 1 1 1 1 1 0 1 126 0 1 1 1 1 1 1 0 127 0 1 1 1 1 1 1 1 128 1 0 0 0 0 0 0 0 129 1 0 0 0 0 0 0 1...

Отзывы: