INSTRUCTION
982746.002
Installation
DALI ECG
Blu2Light
Connect ME /
+
–
+
–
L
N
DA
DA
DA
DA
DA
DA
DA
DA
L
N
DALI ECG
DALI ECG
DALI Power Supply
8,5-9,5
max. 17,5
with strain relief
8,5-9,5
without strain relief
Wiring-diagramm DALI Controller Connect ME in the Blu2Light-System
If you install the control unit in a warm environment (i.e. inside a luminaire or in a ceiling outlet
box above a luminaire), make sure that the ambient temperature does not exceed the
specified maximum value.
Connect ME draws its operating power directly from the DALI bus. For this reason, it is important
to make sure that the DALI bus is externally powered. If
is connected directly to
Connect ME
a DALI sensor or a DALI driver, these products must have an integrated DALI bus power
supply.
Use 0.5 - 1.5 mm solid or stranded conductor electrical wires. Strip the wire 8.5-9.5 mm from
2
the end.
Press the buttons on top of the dimmercase and insert the wires into the corresponding holes.
The polarity of DA1 and DA2 does not matter.
-
Make sure that the mains voltage is switched o ffwhen making any connections.
!
Note:
A connecting higher voltages than DALI voltage leads to the destruction of the device.
Operation with 24 V / 110 V / 230 V is generally not permitted!
Connect ME draws 5 mA in idle mode with 30 mA peak current from the DALI bus.
By default, the DALI bus is not SELV-protected. All wires to be mains voltage-proof.