B.  WIRING THE WALL THERMOSTAT

OEM must supply mating parts to connect these thermostats per Figure
1. The plugs must be connected to motorcoach wire harness before the
base is secured to the wall.

5

Figure 1  

6636-345* Thermostat Assembly with Plugs

2

Operation

No functions occur in this mode

ID fan low, compressor #1 and OD
blower low cycle as needed

ID fan low, compressor #1 &  #2 and
OD blower high cycle as needed

ID fan low continuous

ID fan low continuous, compressor #1
and OD blower low cycle as needed

ID fan low continuous, compressor #1
& #2 and OD blower high cycle as
needed

No functions occur in this mode

ID fan high, compressor #1 and OD
blower low cycle as needed

ID fan high, compressors #1 & #2 and
OD blower high cycle as needed

1

2

3

4

5

6

7

8

9

Mode

Switch

Cool

Cool

Cool

Cool

Cool

Cool

Cool

Cool

Cool

Fan

Switch #1

Auto

Auto

Auto

On

On

On

Auto

Auto

Auto

Fan

Switch #2

Lo

Lo

Lo

Lo

Lo

Lo

Hi

Hi

Hi

Calling

No

Stage 1

1

 Above Set

Stage 2

2

 Above Set

No

Stage 1

1

 Above Set

Stage 2

2

 Above Set

No

Stage 1

1

 Above Set

Stage 2

2

 Above Set

OPERATION CHART

The chart below shows the system functions with the 6636-345  thermostat.
After the entire air conditioning system (and furnace system) is installed,
check each position function.

6636-345  2-STAGE HEAT PUMP THERMOSTAT TRUTH TABLE

(GH) COOLING HIGH FAN

(B) 12 VDC NEGATIVE

(F) FREEZE SWITCH

(R) 12 VDC POSITIVE

(F) FREEZE SWITCH

(Y1) COMPRESSOR ONE

(Y2) COMPRESSOR TWO

(GL) COOLING LOW FAN

BLACK
BLUE
GRAY
RED
GRAY
YELLOW
ORANGE
PURPLE

(R) 12 VDC POSITIVE

(B) 12 VDC NEGATIVE

(W) FURNACE CONTROL

RED
BLUE
WHITE