background image

12

PRINTED CIRCUIT BOARD FREEZE SENSOR SECTION

 

INDOOR COIL SENSOR

1.

The Indoor Coil Sensor, T14 and T15 terminals are connected to a thermister located in the evaporator (Indoor) coil.

2.

This sensor is an active part of the circuit only in the cooling mode.

3.

This sensor is ignored if “W” (Electric Heat) is energized.

4.

This sensor opens if the TEMPERATURE of the INDOOR COIL (not ambient air temperature) reaches 28 degrees F.  The

sensor closes at 55 degrees F.

5.

If this sensor opens, the p.c. board will not output 12 volts DC to either Comp 1 (T2 and T3B) terminals or the Comp 2 (T3A

and T10) terminals on the board.

OUTDOOR COIL SENSOR

1.

The Outdoor Coil Sensor, T16 and T17 terminals are connected to a thermister located in the condenser (Outdoor) coil.

2.

This sensor is an active part of the circuit only in the heating mode.

3.

This sensor is ignored whenever “W” (Electric Heat) is NOT energized.

4.

This sensor opens if the TEMPERATURE of the OUTDOOR COIL (not ambient air temperature) reaches 18 degrees F.  The

sensor closes at 38 degrees F.

5.

If this sensor opens, the p.c. board will shut down all Heat Pump functions.

GREEN L.E.D. LIGHT OPERATION (FREEZE SENSOR)

1.

If the GREEN light is on solid, everything is OK.

2.

If the GREEN light is blinking slowly, the unit is in a 3-minute time delay mode.

3.

If the GREEN light is blinking fast, there is either no line voltage to Circuit #1 or one of the thermisters are open.

4.

If there is no GREEN light on, 12 VDC to the p.c. board has been lost.

Содержание 6535*335 Series

Страница 1: ...1 series heat pumps if the 6535 3209 Replacement P C Board Kit has been installed in the unit RV Products A Division of Airxcel Inc P O Box 4020 Wichita KS 67204 1 877 430 8084 Service Center Locator...

Страница 2: ...8 Printed Circuit Board 9 Pin Thermostat Plug Connector 9 Printed Circuit Board Indoor Blower Section 10 Printed Circuit Board Compressor Section 11 Printed Circuit Board Freeze Sensor Section 12 Pri...

Страница 3: ...display indicates room temperature and the word ROOM is shown on the LCD until the temperature selector is pressed at which time the display temporarily indicates the setpoint temperature and the word...

Страница 4: ...mp is locked out for 2 hours backup heat counter is reset if Heat Pump is running for more than 20 minutes and does not call for backup heat 71 Gas Furnace turns off Thermostat satisfied 69 Gas Furnac...

Страница 5: ...Above Set ID fan high compressor 1 and OD blower low cycle as needed 9 Cool Auto Hi Stage 2 2 Degrees Above Set ID fan high compressors 1 and 2 and OD blower high cycle as needed 10 Cool On Hi No ID...

Страница 6: ...6 II HEAT PUMP OPERATION SEQUENCE COOLING MODE...

Страница 7: ...7 III HEAT PUMP OPERATION SEQUENCE HEATING MODE...

Страница 8: ...8 IV 6535 320 PRINTED CIRCUIT BOARD FUNCTION CHART...

Страница 9: ...you were looking straight at it NOTE 1 Pin connections in this p c board socket are identical to those in the thermostat 2 Low voltage connections to the p c board socket are subject to thermostat tim...

Страница 10: ...s HOT leg power continues from terminal T6 to the High Speed motor tap 4 The motor starts and runs on High Speed until the signal is lost from the thermostat LOW SPEED INDOOR BLOWER OPERATION 1 Begins...

Страница 11: ...l 4 The Compressor Relay 1 closes 5 Compressor 1 starts and runs until the compressor signal is satisfied at the thermostat What else might shut the compressor off COMPRESSOR 2 COOLING OPERATION 1 Beg...

Страница 12: ...Outdoor Coil Sensor T16 and T17 terminals are connected to a thermister located in the condenser Outdoor coil 2 This sensor is an active part of the circuit only in the heating mode 3 This sensor is i...

Страница 13: ...e same 2 second time delay 3 The Outdoor Blower starts and runs on Low speed until compressor 1 goes off or the second stage cooling is energized HIGH SPEED OUTDOOR BLOWER OPERATION 1 Begins with a 11...

Страница 14: ...eg to the motor is not routed through the printed circuit board 6 The 115 volts HOT leg power continues from terminal T6 to the High Speed motor tap and the motor begins to run on High Speed 7 12 VDC...

Страница 15: ...15 V WIRING DIAGRAM 6536 SERIES TWO TON PACKAGED HEAT PUMP...

Страница 16: ...6536 A Model Secondary Wiring Diagram 6536 B SERIES TWO TON PACKAGED HEAT PUMP...

Отзывы: