The RG-WALL1600-M6600 is heavy. To ensure cabinet stability: install the guide rail to as low a position as possible
in the cabinet if one RG-WALL1600-M6600 is installed; install heavier devices in the lower part of the cabinet if
multiple devices are installed.
3.4 Mounting into the Cabinet
Precautions
Before mounting RG-WALL1600-M6600 into the cabinet, first verify that the front and back brackets of the cabinet are at
the right locations. If the bracket is too far forward, the front panel of the equipment may be too close to the front door, so
that the front door cannot be closed when network cables and pigtail fibers are connected. Allow at least 10 mm of
distance between the front panel of the equipment and that of the cabinet after installation. Before mounting into a cabinet,
you need to address the following conditions:
Fasten the cabinet.
Insert various modules in the frame properly.
Remove any obstacle in the frame and the surrounding environment.
Prepare the equipment and move it to the place near the cabinet where you can handle it easily.
Simple Installation Steps
1)
Levelly lift the RG-WALL1600-M6600 by two people on both sides, and slowly move it to the front of the cabinet.
2)
Levelly lift the RG-WALL1600-M6600 to a position slightly higher than the tray or the slide rail of the cabinet, put the
equipment onto the tray or the slide rail, and push it into the cabinet.
3)
Fasten the RG-WALL1600-M6600 onto the cabinet with screws. There are fastening notches on both the sides of
the front panel on the equipment frame. Use screws to fasten them to the fastening bracket of the cabinet. After
fastened, the equipment should be stable and still in the cabinet.
3.5 Connecting the AC Power Supply to the Power Module
Connect AC power cables according to the ID and position instruction on the AC power module.
Precautions
Before connecting the power supply, you must verify that the external power supply matches the power module installed
with this equipment.
Before connecting the power cable, be sure that the switch of the power module is at the OFF position.
The 16A power cable with a standard 3-pin connector should be used for connection.
After connecting the power cable, correctly lock the strip-protection button onto the power cable.
Be sure that the power cables connected are in good contact.
Simple Connection Steps
1)
Insert the plug of the power cable into the power module.
2)
Connect the other end of the power cable to the corresponding socket or connector.
When installing the unit, use 3-pin power supply cord. The cross-sectional area of each pin is 1.5mm
2
or 14AWG
minimum.
3.6 Connecting the External Port Cables
Precautions
Correctly distinguish single-mode and multi-mode fibers and ports.
Avoid bends of small radius at the connector.
Simple Connection Steps
1)
Connect one end of the RJ45 connector for configuring Ethernet cables to the Ethernet port of the device board and
the other end to the NMS or a control terminal; or connect one end of the standard RJ45 serial port cable to the serial
port of the device board and the other end to the NMS or a control terminal.
2)
Insert the single-mode or multi-mode fiber into the appropriate port according to the identification on the panel of the
linecard. Distinguish the Rx/Tx end of the fiber.