Ruijie RG-NBS3100 Series Switches Hardware Installation and Reference Guide 

 

Appendix C Lightning Protection 

 

39 

 

During the switch usage, the Ethernet port arrester shall be connected to the switch to prevent the switch damage by 

lightning before the outdoor network cable connects to the switch.   

Tools: Cross or straight screwdriver, Multimeter, Diagonal pliers 

Installation Steps: 

 

Tear one side of the protection paper for the double-sided adhesive tape and paste the tape to the framework of the 

Ethernet port arrester. Tear the other side of the protection paper for the double-sided adhesive tape and paste the 

Ethernet port arrester to the switch framework. The paste location for the Ethernet port arrester shall be as close to 

the grounding terminal of the switch.   

 

Based on the distance of the switch grounding terminal, cut the grounding line for the Ethernet port arrester and 

firmly tighten the grounding line to the grounding terminal of the switch. 

 

Use the multimeter to check whether the grounding line for the arrester is in good contact with the switch grounding 

terminal and the framework.   

 

According to the description on the Ethernet Port Arrester Hardware Installation Guide, connect the arrester using 

the adapter cable(note that the external network cable is connected to the end of IN, while the adapter cable 

connected to the switch is connected to the end of OUT) and observe whether the LED on the borad is normal or not. 

 

Use the nylon button to bundle the power cables.   

Figure C-2 Schematic Diagram for the Ethernet port Arrester Installation 

 

 

The Ethernet port arrester is only for the 10M/100M copper Ethernet ports with the RJ-45 connector; 

 

The Ethernet port arrester is not provided, the user can purchase them to address their own pratical requirements. 

For the detailed information during the arrester installation, please refer to Ethenet Port Arrester Hardware 

Installation Guide, which contains the technical specification and the maintenance and installation of the arrester. 

You may pay attention to the following conditions during the actual installation to avoid influencing the performance of the 

Ethernet port arrester:   

Содержание RG-NBS3100 Series

Страница 1: ...Ruijie RG NBS3100 Series Switches Hardware Installation and Reference Guide...

Страница 2: ...or by any means without the prior written consent of Ruijie Networks is prohibited Exemption Statement This document is provided as is The contents of this document are subject to change without any n...

Страница 3: ...ite https www ruijienetworks com Technical Support Website https ruijienetworks com support Case Portal https caseportal ruijienetworks com Community https community ruijienetworks com Technical Suppo...

Страница 4: ...wnward compatible with 100Base FX 1000Base T is downward compatible with 100Base TX and 10Base T 1 1 RG NBS3100 24GT4SFP Technical Specifications Model RG NBS3100 24GT4SFP CPU Built in CPU single core...

Страница 5: ...61000 3 3 EN 55035 ETSI EN 300 386 Security Standards GB4943 2011 EN 62368 1 Dimensions W x D x H 440 mm x 165 mm x 44 mm Weight 2 4 kg The RG NBS3100 24GT4SFP switch is a class A product In a domest...

Страница 6: ...the separate protective earthing terminal The device installation shall be permanently connected to building earth by a skilled person The device shall be intended to be used in a location having equ...

Страница 7: ...cal Specifications Model RG NBS3100 24GT4SFP P CPU Built in CPU single core processor 500MHz Flash Memory 16 MB SDRAM DDRIII 256MB Optical Module See Appendix B The copper cable is not supported The s...

Страница 8: ...RG NBS3100 24GT4SFP P switch is a class A product In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures The high tempera...

Страница 9: ...he LED is solid green it indicates that the PoE supported ports are supplying power when the LED blinks green the power of the ports is overloaded Back Panel Figure 1 6 Back Panel of RG NBS3100 24GT4S...

Страница 10: ...f The port is not connected Solid green The port is connected at 10 100 1000 Mbps Blinking green The port is receiving or transmitting traffic at 10 100 1000 Mbps RJ45 port PoE status LED 1 24 Off PoE...

Страница 11: ...d Power Consumption 8W Temperature Operating temperature 0 C to 50 C Storage temperature 40 C to 70 C Humidity Operating humidity 10 to 90 RH Storage humidity 5 to 95 RH Fan Not supported Temperature...

Страница 12: ...00 8GT2SFP Front Panel Figure 1 9 Front Panel of RG NBS3100 8GT2SFP Note 1 System status LED 2 Reset button 3 10 100 1000 Base T Ethernet port 4 Copper port status LED 5 1000 Base X SFP port 6 SFP por...

Страница 13: ...air circulation It is recommended to clean the device once every 3 months to avoid dust from blocking vents LED LED Panel Identification State Meaning System status LED Status Off The switch is not re...

Страница 14: ...PoE Supports PoE and PoE Ports 1 8 are PoE capable with the maximum power output of 30W per port Port 9 does not support PoE The overall maximum output power of PoE PoE is 125W PoE Mode Mode A data pa...

Страница 15: ...d be installed in the restricted area when the ambient temperature exceeds 50 deg C Product Appearance On the front panel the RG NBS3100 8GT2SFP P Ethernet switch provides 8 10 100 1000Base T Ethernet...

Страница 16: ...a skilled person The device shall be intended to be used in a location having equipotential bonding such as a telecommunication centre a dedicated computer room or a restricted access area Heat Dissi...

Страница 17: ...lation Keep the chassis clean and free from dust Do not place the equipment in a passage Do not wear loose clothes or any other things that may be caught by the chassis during installation and mainten...

Страница 18: ...eakage protector divided by two is greater than the sum of maximum leakage currents of all the power supplies The rated leakage non action current of a leakage protector shall be 50 of the leakage act...

Страница 19: ...the equipment may be damaged In an environment with high relative humidity the insulating material may have bad insulation or even leak electricity Sometimes the materials may suffer from mechanical...

Страница 20: ...caused by capacity coupling inductance coupling electromagnetic wave radiation common impedance including grounding system coupling and conducting wires including power cords signal and output wires T...

Страница 21: ...tection system of a facility is an independent system that consists of the lightning rod download conductor and the connector to the grounding system which usually shares the power reference ground an...

Страница 22: ...er Radiated interference may affect any signal path in the equipment and is difficult to shield For the AC power supply system TN single phase three core power socket with protective earthing conducto...

Страница 23: ...re installation please confirm the following points Whether ventilation requirements are met for the switch Whether the requirements of temperature and humidity are met for the switch Whether power ca...

Страница 24: ...pted For example use interface cables to shield cables 100 meter network cables should be laid inside the equipment room and outdoor cabling of such cables is prohibited If outdoor cabling is necessar...

Страница 25: ...Port Switch Figure 3 5 Attaching the Brackets to the Rack 24 Port Switch Figure 3 6 Attaching the Brackets to the Rack 24 Port Switch 3 3 2 Mounting the Switch on a Table Attach the four rubber pads...

Страница 26: ...aximum current Cables of good conductor should be used Do not use bare wire The grounding electric resistance should be less than 1 To guarantee the security of the body and the device the switch must...

Страница 27: ...fibers at the connectors have natural bends or bends of large radius Do not bundle fibers and twisted pairs too tightly as this may press hard the fibers and affect their service time and transmission...

Страница 28: ...Ruijie RG NBS3100 Series Switches Hardware Installation and Reference Guide Product Installation 28 Check that sufficient airflow is available around the device over 10 cm...

Страница 29: ...d RJ 45 port of the network cable to any Ethernet port of the switch Configuring the Device Step 1 Start the PC and configure the IP address of the PC as 10 44 77 XXX 10 44 77 XXX indicates the IP add...

Страница 30: ...the parameters are already configured Checking after Power on Recommended After power on you are recommended to perform the following checks to ensure the normal operation of follow up configurations...

Страница 31: ...port is not in connectivity or it is erroneous in receiving transmitting frames The connected twisted pair cable is faulty The length of the cable exceeds 100 m The port has special configuration tha...

Страница 32: ...Ruijie RG NBS3100 Series Switches Hardware Installation and Reference Guide Troubleshooting 32 that rated of the optical module appropriate length...

Страница 33: ...BASE T port uses four pairs of wires for transmission all of which must be connected Figure A 1 shows the connections of the twisted pairs used by the 1000BASE T port Figure A 1 Schematic Diagram for...

Страница 34: ...and Connection Media 34 Optical Fiber Connection For the optical fiber ports select single mode or multiple mode optical fibers for connection according to the fiber module connected The connection s...

Страница 35: ...ransmitted Light dBm Intensity of Received Light dBm Min Max Min Max MINI GBIC SX MM8 50 850 MMF No 9 5 3 17 0 MINI GBIC LX SM13 10 1310 SMF No 9 5 3 20 3 GE eSFP SX MM85 0 850 MMF Yes 9 5 3 17 0 GE e...

Страница 36: ...MF 50 125 500m GE SFP SX SM1550 BIDI LC MMF 50 125 500m GE SFP LX20 SM1310 BIDI LC SMF 9 125 20km GE SFP LX20 SM1550 BIDI LC SMF 9 125 20km GE SFP LH40 SM1310 BIDI LC SMF 9 125 40km GE SFP LH40 SM1550...

Страница 37: ...Module 37 Rate Distance Module Pairs 1000M 500m GE SFP SX SM1310 BIDI GE SFP SX SM1550 BIDI 1000M 20km GE SFP LX20 SM1310 BIDI GE SFP LX20 SM1550 BIDI 1000M 40km GE SFP LH40 SM1310 BIDI GE SFP LH40 SM...

Страница 38: ...cal requirement Precautions for installation Make sure that the PE terminal of the power arrester has been well grounded After connecting the switch AC power plug to the socket of the power arrester l...

Страница 39: ...to check whether the grounding line for the arrester is in good contact with the switch grounding terminal and the framework According to the description on the Ethernet Port Arrester Hardware Instal...

Страница 40: ...to the OUT end Poor arrester grounding The length of the grounding line should be as short as possible to ensure that it is in good contact with the switch grounding terminal Use the multimeter to con...

Страница 41: ...erall diameter The minimum bend radius of a coaxial cable should be 7 times the overall diameter of the cable If the cable is constantly bent plugged or unplugged the bend radius should be 10 times th...

Страница 42: ...proper cable ties to bind cables together Do not tie two or more cable ties to bind cables Cut off excess cable tie cleanly with no sharp edges after bundling cables as shown in Figure D 2 Figure D 2...

Страница 43: ...ed and prevented from loosening as shown in Figure D 4 Figure D 4 Fastening Cable Lugs Note Flat washer Nut Spring washer Flat washer When using a stiff cable fix it near the cable lug to avoid stress...

Страница 44: ...conditions such as windstorm and heavy rain as well as away from dust If the dust is unavoidable keep the door and window away from the pollution source The machine room should be away from the resid...

Страница 45: ...Ruijie RG NBS3100 Series Switches Hardware Installation and Reference Guide 45...

Отзывы: