Hardware Installation and Reference GuideProduct Installation
During installation, note the following points:
Connect the power cables of different colors to the corresponding grounding posts.
Ensure that the interface of the power supply cable is well connected to the power interface of the device. The power
cables must be protected using
power cable retention clips
after they are connected to the device.
Do not place any articles on the XS-S1960-24GT4SFP-Hseries switch.
Reserve a spacing of at least 10 cm around the chassis for good ventilation. Do not stack the devices.
The switch should be located at places free from the large power radio launch pad, radar launch pad, and
high-frequency large-current devices. If necessary, electromagnetic shielding should be adopted. For example, use
interface cables to shield cables.
100-meter network cables should be laid inside the equipment room and outdoor cabling of such cables is prohibited.
If outdoor cabling is necessary, take relevant measures for lightning protection.
3.3.1 Mounting the Switch inthe Rack
The XS-S1960-24GT4SFP-Hseries switches are designed with the EIA standard dimensions and can be installed in
19-inch rack.
Step 1: Take out supplied screws and brackets, and then mount the brackets onto left and right sides of the switch.
Figure 3-2Attaching the Mounting Brackets to the Switch
Step 2: Place the switch into the rack. Fix the other ends of both brakcets onto the suqre hole strips of the rack by using
M6 screws and cage nuts, as shown in Figure 3-3 and Figure 3-4.
Figure 3-3Fixing the Brackets to the Rack