Appendix E Site Selection 

 

The  machine  room  should  be  at  least  5km  away  from  the  heavy  pollution  source  such  as  the 

smelter, coal mine and thermal power plant, 3.7km away from the medium pollution source such as 

the  chemical  industry,  rubber  industry  and  electroplating  industry,  and  2km  away  from  the  light 

pollution  source  such  as  the  food  manufacturer  and  leather  plant.  If  the  pollution  source  is 

unavoidable,  the  machine  room  should  be  located  on  the  windward  side  of  the  pollution  source 

perennially with advanced protection. 

 

The machine room should be at least 3.7km away from the sea or salt lake. Otherwise, the machine 

room  must  be  sealed,  with  air  conditioner  installed  for  temperature  control.  Saline  soil  cannot  be 

used  for  construction.  Otherwise,  you  should  select  devices  with  advanced  protection  against 

severe environment. 

 

Do  not  build  the  machine  room  in  the  proximity  of  livestock  farms.  Otherwise,  the  machine  room 

should be located on the windward side of the pollution source perennially. The previous livestock 

house or fertilizer warehouse cannot be used as the machine room.   

 

The  machine  room  should  be  firm  enough  to  withstand  severe  weather  conditions  such  as 

windstorm and heavy rain as well as away from dust. If the dust is unavoidable, keep the door and 

window away from the pollution source. 

 

The machine room should be away from the residential area. Otherwise, the machine room should 

meet the construction standard in terms of noise. 

 

Make sure the air vent of the machine room is away from the sewage pipe, septic tank, and sewage 

treatment  tank.  Keep  the  machine  room  under  positive  pressure  to  prevent  corrosive  gas  from 

entering  the  machine  room  to  corrode  components  and  circuit  boards.  Keep  the  machine  room 

away from industrial boiler and heating boiler. 

 

The machine room had better be on the second floor or above. Otherwise, the machine room floor 

should be 600mm higher than the highest flood level ever recorded. 

 

Make sure there are no cracks or holes in the wall and floor. If there are cable entries in the wall or 

window,  take  proper  sealing measures.  Ensure  that  the  wall  is  flat,  wear-resistant,  and dust-free, 

which  should  be  up  to  the  standard  for  flame  retarding,  soundproofing,  heat  absorption,  dust 

reduction, and electromagnetic shielding. 

 

Keep the door and the window closed to make the machine room sealed. 

 

The steel door is recommended for soundproofing. 

 

Sulfur-containing materials are forbidden. 

 

Pay  attention  to  the  location  of  the  air  conditioner.  Keep  the  air  conditioner  from  blowing  wind 

straight toward the device or blowing water drops from the window or air vent toward the device. 

Содержание RG-AM5528 Series

Страница 1: ...RG AM5528 Series Access point Hardware Installation and Reference Guide V1 00...

Страница 2: ...or by any means without the prior written consent of Ruijie Networks is prohibited Exemption statement This document is provided as is The contents of this document are subject to change without any n...

Страница 3: ...www ruijienetworks com service aspx Technical Support Hotline 86 4008 111 000 Related Documents Documents Description Configuration Guide Describes network protocols and related mechanisms that suppo...

Страница 4: ...l and supports up to 24 rooms with optimal dual stream coverage under dual band 2 4GHz 5GHz Each room enjoys 600M bandwidth and the whole access point features a throughput of 14 4G meeting the demand...

Страница 5: ...D x H 440 mm x 260 mm x 44 mm Weight 5 8 kg with package The RG AM5528access point is a class A product In a domestic environment this product may cause radio interference in which case the user may b...

Страница 6: ...GE copper port LED 4 Fiber port LED 5 Mode button 6 Console port 7 10 100 1000Base T auto sensing Ethernet port 8 1000Base T copper port 9 SFP port Long press Mode for above 2 seconds to switch the di...

Страница 7: ...10 cm distance space should be reserved at both sides and the back panel of the deviceto allow air circulation It is recommended to clean the device once every 3 months to prevent dust from blocking v...

Страница 8: ...green The port is connected at 1000 Mbps Blinking green The port is receiving or transmitting traffic at 1000 Mbps Solid yellow The port is connected at 10 100 Mbps Blinking yellow The port is receivi...

Страница 9: ...Blinking green The port is receiving or transmitting traffic at 1000 Mbps...

Страница 10: ...bserve local regulations and specifications when performing electric operations Relevant operators must be qualified Before installing the device carefully check any potential danger in the surroundin...

Страница 11: ...installation site must meet the following requirements Ventilation For the RG AM5528 a sufficient space at least 10 cm distances from both sides and the back plane of the cabinet should be reserved a...

Страница 12: ...rostatic adherence may occur more easily when the relative humidity is low not only affecting the useful life of the equipment but also causing communication faults Table 2 2 shows the requirements fo...

Страница 13: ...ounding wire to connect the grounding end of the A C socket to the building s protection location The power supply socket must be installed in a place that is near to the device and where users can op...

Страница 14: ...inside the equipment or application system affects the system in the conductive ways such as capacitive coupling inductive coupling and electromagnetic radiation There are two types of electromagneti...

Страница 15: ...of the access point must be deployed far away from the grounding device of the electrical equipment and anti lightning grounding device Keep the equipment away from high power radio transmitter radar...

Страница 16: ...stallation Flowchart Confirmations before Installation Before installation please confirm the following points Whether ventilation requirements are met for the access point Whether the requirements of...

Страница 17: ...t stack the devices The access point should be located at places free from the large power radio launch pad radar launch pad and high frequency large current devices If necessary electromagnetic shiel...

Страница 18: ...tach the mounting brackets to the rack as shown in Figure 2 3 Figure 2 3 Mounting the Access Point on the Wall The RG AM5528access point can be mounted on the wall as shown in the following figure Att...

Страница 19: ...l as shown in Figure 2 5 Figure 2 4 Attaching the Access Point on the Wall Mounting the Access Point on a Table Attach the four rubber feet to the recessed areas on the bottom of the access point as s...

Страница 20: ...r supply so as to avoid any personal injury or damage to the component due to connection errors Check that the ground line is connected Check that the cables and power input cables are correctly conne...

Страница 21: ...he serial port of the PC Step 2 Connect the end of the console cable with RJ45 to the console port of the access point Setting Hyper Terminal Parameters Step 1 Start the PC and run the terminal simula...

Страница 22: ...layed Choose the serial port used currently in the column use when connecting Figure 4 3 After choosing the serial port click OK to display the serial port parameter setting interface set the baud rat...

Страница 23: ...sole port of the access point The HyperTerminal is started and the parameter settings are correct Checking after Program Startup Recommended After power on you are recommended to perform the following...

Страница 24: ...Check whether the service interface forwards data normally...

Страница 25: ...he power socket at the equipment room is normal and whether the power cable of the access point is in good contact The status indicator is red Fan alarm Temperature alarm Power alarm Check whether the...

Страница 26: ...r cable is faulty The length of the cable exceeds 100 m The port has special configuration that has no common working mode with the connected access point Replace the twisted pair cable Check that the...

Страница 27: ...n all of which must be connected Figure A 1 shows the connections of the twisted pairs used by the 1000BASE T port Figure A 1 Four Twisted Pairs of the 1000BASE T In addition to the above cables the 1...

Страница 28: ...For the optical fiber ports select single mode or multiple mode optical fibers for connection according to the fiber module connected The connection schematic diagram is shown in Figure A 4 Figure A 4...

Страница 29: ...E SFP LX MM1310 1310 MMF 62 5 125 2km Yes 22 14 30 14 FE SFP LH15 SM1310 1310 SMF 9 125 15km Yes 15 8 28 8 Table B 2 Models and Technical Specifications of the 1000M Mini GBIC Module Model Wave Length...

Страница 30: ...SFP Type 1000Base T Mini GBIC GT The existing 1000Base T module 1000baseT Copper Type Cabling Distance DDM Yes No Mini GBIC GT Category 5 or above UTP STP 100m No Table B 5 Models and Technical Specif...

Страница 31: ...XG SFP CU1M Passive SFP 1 28 10 3125 No XG SFP CU3M Passive SFP 3 28 10 3125 No XG SFP CU5M Passive SFP 5 26 10 3125 No For the optical module with transmission distance exceeding 40 km and more one o...

Страница 32: ...lation Make sure that the PE terminal of the power arrester has been well grounded After connecting the access point AC power plug to the socket of the power arrester lightning protection cable row li...

Страница 33: ...rounding terminal of the access point Use the multimeter to check whether the grounding line for the arrester is in good contact with the access point grounding terminal and the framework According to...

Страница 34: ...t Ethernet port to the OUT end Poor arrester grounding The length of the grounding line should be as short as possible to ensure that it is in good contact with the access point grounding terminal Use...

Страница 35: ...greater than seven times their respective diameters The bend radius of a common coaxial cable should be greater than seven times its diameter The bend radius of this type of cables that often bend or...

Страница 36: ...traversed by cables should have a smooth and fully rounding surface or an insulated lining Proper buckles should be selected to bundle up cables It is forbidden to connect two or more buckles to bund...

Страница 37: ...e guide rails of moving parts The power cables connecting moving parts such as door grounding wires should be reserved with some access after assembled When the moving part reaches the installation po...

Страница 38: ...bunches with cables in cable bunches clean and straight Binding by using buckles should be performed according to Table D 1 Cable Bunch Diameter mm Binding Space mm 10 80 150 10 30 150 200 30 200 300...

Страница 39: ...as away from dust If the dust is unavoidable keep the door and window away from the pollution source The machine room should be away from the residential area Otherwise the machine room should meet t...

Отзывы: