Technical Specifications
RuggedCom
®
- Rev.122
46
RuggedRouter
®
RX1000 Family
5.6 IEEE 1613 Type Tests
IEEE
Test
IEEE
1613
Clause
Description
Test Levels
C37.90.3
9
ESD
Enclosure Contact
+/- 8kV
Enclosure Air
+/- 15kV
C37.90.2
8
Radiated RFI
Enclosure ports
35 V/m
C37.90.1
7
Fast Transient
Signal ports
+/- 4kV @ 2.5kHz
D.C. Power ports
+/- 4kV
A.C. Power ports
+/- 4kV
Earth ground ports
+/- 4kV
C37.90.1
7
Oscillatory
Signal ports
2.5kV common mode @ 1MHz
D.C. Power ports
2.5kV common & differential mode @
1MHz
A.C. Power ports
2.5kV common & differential mode @
1MHz
C37.90
6
H.V. Impulse
Signal ports
5 kV (Failsafe Relay)
D.C. Power ports
5 kV
A.C. Power ports
5 kV
C37.90
6
Dielectric
Strength
Signal ports
2kV AC(Failsafe Relay)
D.C. Power ports
1.5kV DC
A.C. Power ports
2kV AC
Table 26: IEEE 1613 Type Tests
NOTES:
If the unit contains copper ports the IEEE 1613 conformance is Class 1
(During disturbance errors may occur but recovery is automatic).
If the unit contains all fiber ports the IEEE 1613 conformance is Class 2
(During disturbance no errors will occur).