CLASSIC-LINE
ECO-LINE
Installation Guide
58
Non-inflammable environment (non-inf)
Floor
The appliance adjustable feet must
stand directly on a load-bearing sur-
face.
A layer of thermal insulation, 3 cm thick,
should be placed between the appli-
ance and the concrete slab.
Side and rear walls
No protective wall.
The protection consists of a
layer of
thermal insulation
, at least
6 cm
thick.
It seamlessly covers the whole of the
building wall, inside the fireplace casing
cavity.
Ceiling
The room ceiling must be at least
12 cm thick.
If the fireplace casing cavity above the
appliance extends to the ceiling, then
the ceiling must be fitted with a layer of
thermal insulation
at least
6 cm
thick,
that is laid directly on the ceiling.
The thermal insulation is laid on a min.
2 cm
non-inflammable cover, with a
permanent, unchanging thermal re-
sistance.
Guidelines for the use of substitute thermal insulation are given on pages 30 and
31.
*
Version with fresh air unit
> See page 20
3
cm
≥2
c
m
≥
12
c
m
≥
6
cm
≥ 6 cm
*
≥ 10 cm