CLASSIC-LINE
ECO-LINE
Installation Guide
52
Combustion chamber lining in Thermobrikk
®
The elements of the lining in Thermobrikk
®
consist of several loose items. The
illustrations below are applicable on all Rüegg fireplaces equipped with a lining in
Thermobrikk
®
.
Please proceed as follows when inserting the lining:
Insert wall parts in the combustion chamber; start
in the corner between back- and sidewall.
Insert wall parts in the combustion chamber. Next
to the fireplace opening, slide the element behind
the steel strip.
Custom cut parts must always be placed in front,
next to the fireplace opening!
Fill the side- and back walls with the wall elements
and slide them together without any space be-
tween them.
Fix the L-Profile with screws to the wall of the
combustion chamber, as a fixation for the back-
and side wall elements.
Place all floor elements correctly on the steel floor,
and divide the space between the different ele-
ments evenly between the floor parts.