background image

FIGURE 3  RJ-45 cable and cable gland assembly

2. Use a wide flat-blade screwdriver to remove the required

(PoE IN) blanking cap from the AP.

3. Connect the cable to the Ethernet port on the AP.
4. Tighten the cable gland base into the AP chassis to 7 N.m

or 62 in-lbs.

5. Wrap the clamping ring assembly around the rubber O-

ring. Make sure that the clamping ring assembly fully

encloses the rubber O-ring.

6. Seat the clamping ring assembly and rubber O-ring in the

cable gland base.

7. Hand-tighten the sealing nut.

Attaching the Mounting Bracket To A Flat

Surface

1. The AP mounting bracket attaches to the AP using a

captive screw. Use a medium flat-blade or No. 2 Phillips

screwdriver to loosen the captive screw (A in the Figure

below) and pull up on the end of the bracket to remove

the bracket from the AP (B in the Figure below).

FIGURE 4  Removing the mounting bracket

2. Using either of the two options shown in Figure 5, hold

the mounting bracket at the location on the mounting

surface where you want to mount the AP. Use the holes

on the mounting bracket as a template to mark the

locations of the mounting holes.

NOTE: The mounting bracket can be mounted to a

vertical or horizontal surface to support the AP in the

required orientation.

FIGURE 5  Mounting bracket on a flat surface

3. Remove the mounting bracket from the mounting surface.
4. Drill holes required for the customer-supplied mounting

hardware.

5. Attach the mounting bracket to the flat surface using the

mounting hardware.

6. Using the mounting hardware instructions, tighten the

hardware to secure the mounting bracket.

7. Continue with Mounting the AP.

Attaching the Mounting Bracket to a Pole

1. The AP mounting bracket attaches to the AP using a

captive screw. Loosen the screw (A in Figure 4) and pull

up on the end of the bracket to remove the bracket from

the AP (B in the Figure above).

2. Insert the open end of one steel clamp (D in the Figure

above) into two of the slots on the mounting bracket.

NOTE: The mounting bracket can be mounted to a

vertical or horizontal pole to support the AP in the

required orientation.

3. Using either of the two options shown, use the clamp(s) to

attach the mounting bracket to the pole. Tighten the

clamps to 3 N.m or 27 in-lbs, or per manufacturer’s

specifications if the factory-supplied clamps are not used.

4. If necessary, daisy-chain the other steel clamps to

accommodate larger poles.

FIGURE 6  Mounting bracket on a pole

5. Continue with Mounting the AP.

Mounting the AP

1. Snap the AP back onto the mounting bracket (A in the

Figure below), and use a medium flat-blade or No. 2

Phillips screwdriver to tighten the captive screw to 1.1

N.m or 10 in-lbs to secure the bracket to the AP (B).

FIGURE 7  Attaching the mounting bracket to the AP

2. Optional Step: If you also need to lock the mounting

bracket to the AP, then use a matching security

screwdriver to screw the customer-supplied locking

stainless steel 6mm M3 panhead security screw through

the mounting bracket and into the AP chassis.

CAUTION! 

Make sure that the customer-supplied

locking stainless steel M3 panhead security screw is no

longer than 6mm. If the security screw is longer than

6mm, it can damage the AP chassis.

Copyright 

®

 2017 Ruckus Wireless, Inc.

Page 2 of 3

Published September 2017, Part Number 800-71622-001 Rev A

Отзывы: