22
Compliance with CE Mark
This section describes how to install and operate RTP equipment for use in the European Union
(EU) to comply with the requirements of the CE Mark and its referenced standards. The
procedures in this section apply also to other environments where provisions of the EU’s EMC
and Low Voltage Directives are either required or desirable.
RTP Corporation has successfully tested and reviewed its products to the stringent requirements
of the European Union’s EMC Directives (2004/108/EC) and Low Voltage Directive (2006/95/EC).
In order for the equipment to meet the requirements of these directives, the equipment
must be installed and operated in accordance with these instructions
.
These tests and reviews are in accordance to EN 61131-2:2007 as listed in the next section.
Information on the tests performed and the standards involved is available from RTP Corporation.
To comply with the requirements of the CE Mark and its referenced standards, the system
integrator, installer, and end user must store, integrate, install, and operate this equipment in
accordance with the following guidelines.
1. Compliance with all product specific instructions (including but not limited to storage
instructions, installation instructions, operating instructions, maintenance instructions,
disposal instructions, and specifications) is required.
2. RTP equipment is rated for use in Installation Category (Overvoltage Category) II and
Pollution Degree 2 environments in accordance with standard IEC 664.
3. To assure that an
Operator
is not exposed to electrical hazards, all equipment capable of
electrical hazards must be housed in a grounded enclosure (equipment cabinet/rack) that
limits access to the equipment only to
Service Personnel
. Limited access may include
enclosure doors and side panels, which are locked or require a tool to open. To assure
compliance with the EMC requirements, the equipment must be housed in an enclosure
(equipment cabinet/rack) that provides EMC shielding. Compliance testing was
performed in a shielded equipment rack provided by Hoffman Concept® Wall Mounted
Enclosure model number CSD242420. To assure compliance, the equipment must be
installed in this style cabinet, or one with similar or greater RF attenuation characteristics.
The cabinet should be outfitted with continuous copper finger gasketing and copper foil
along all seams and joints.
4. The
Service Personnel
must be trained to operate the equipment and must be aware of
the potential of electrical hazards of the equipment and of the field I/O signals connected
to the equipment.
5. Hazardous voltage warning labels must be applied to the enclosure doors adjacent to the
locking mechanisms to warn the
Service Personnel
that hazardous voltages are
contained within the enclosure, if modules carrying 120 V and above are used.
6. Hazardous voltage warning labels also must be applied to the termination modules
(which carry 120 V and above), adjacent to the external connectors, to warn the
Service
Personnel
that hazardous voltages are present at the module's terminal blocks.
7. To assure compliance with the EMC requirements, the equipment must have all
communications, power, and field signal cabling exiting the enclosure enclosed in metal
conduits or shielded wireways. These conduits must provide EMI/RFI shielding and must
be terminated at the enclosure shell. There must be no uncovered openings in the
cabinet. Connections between the cabinet and conduit must be made with conduit
connectors making good (low impedance) electrical contact to the enclosure. Input
mains power to the enclosure and mains power fed to switching digital output I/O cards
and modules must be filtered by AC mains filters with attenuation characteristics of