Environmental Conditions 

 

The modules are rated for the following environmental conditions: 

Specification Type 

Recommended Range 

Test Specification 

Operating Temperature 

-20 ºC to 60 ºC 

IEC 60068-2-30, Db 
RTP Type Testing 

Operating Temperature Change 

10 ºC/minute 

IEC 60068-2-14 Test Nb 

Operating Humidity 

10% to 95% non-condensing 

IEC 60068-2-30, Db 

Storage Temperature 

-40 ºC to 85 ºC 

IEC 60068-2-1 Tests Ab, Ad 
IEC 60068-2-2 Tests Bb, Bd 
RTP Type Testing 

Storage Temperature Change 

10 ºC/minute 

IEC 60068-2-14 Test Na 

Storage Humidity 

0% to 100% condensing 

IEC 60068-2-30, Db 

Vibration 

9 Hz to 150 Hz at 1 g 

IEC 60068-2-6, Fc 

Mechanical Shock 

15 g for 11 milliseconds 

IEC 60068-2-27, Ea 

Electrostatic Discharge Immunity  ±6 kV contact 

IEC 61000-4-2 

Radiated E-Field Immunity 

80 MHz to 1 GHz at 20 V/m 
1 GHz to 2.1 GHz at 10 V/m 
2.1 GHz to 2.5 GHz at 5 V/m 
2.5 GHz to 2.7 GHz at 1 V/m 

IEC 61000-4-3 

Ethernet Line Burst Immunity 

±2 kV 

IEC 61000-4-4 

Ethernet Line Surge Immunity 

±2 kV 

IEC 61000-4-5 

Ethernet Line Conducted RF 
Immunity 

150 kHz to 80 MHz at 10 V 

IEC 61000-4-6 

Pulsed Magnetic Field 

300 A/m 

IEC 61000-4-9 

 

Modules can be ordered with optional HumiSeal© conformal coating.  In this case, the modules can be 
installed in G3 harsh environmental conditions as defined in standard ISA

–S71.04–1985. 

This equipment is intended for use in altitudes up to 2000 meters.  Contact RTP regarding use in altitudes 
higher than 2000 meters. 

This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant 
to Part 15 of FCC Rules.  These limits are designed to provide reasonable protection against harmful 
interference when the equipment is operated in a commercial environment.  This equipment generates, 
uses, and can radiate radio frequency energy and, if not installed and used in accordance with the 
instruction manual, may cause harmful interference to radio communications.  Operation of this 
equipment in a residential area is likely to cause interference in which case the user will be required to 
correct the interference at his own expense. 

This Class A digital apparatus complies with Canadian ICES-003. 

Cet appareil numérique de la Classe A est conforme à la norme NMB-003 du Canada. 

 

Содержание 3000 TAS

Страница 1: ...Technical Manual RTP 3000 TAS Chassis Manual...

Страница 2: ...ectual property of RTP Corp unless otherwise indicated and are to be considered RTP Corp confidential This intellectual property is made available solely for the direct use of potential or licensed RT...

Страница 3: ...AND MAINTENANCE 10 General 10 Power Connections 10 Fuse Replacement 13 Fans 15 I O Cards 15 Ethernet Switches 16 3000 R2 AND 3100 R2 SYSTEMS 16 Ethernet Cabling 16 Software Configuration 17 3200 R3 SY...

Страница 4: ...ons include a fan assembly TAS Nodes A TAS Node can contain up to four 3000 06 Node Processors and one or two 3000 01 Chassis Processors Based on your processor configuration you can have up to 17 I O...

Страница 5: ...Model numbers may also begin with 3100 instead of 3000 XYZ is factory assigned number that determines the number of I O slots number of Chassis Processors number and type of power supplies within the...

Страница 6: ...lock The power supplies are compatible with standard mains power and are compliant with the European Union s EMC and Low Voltage Directives The main input connection is an eight pin detachable termina...

Страница 7: ...t the top of the chassis and exits at the bottom of the chassis Chassis Dimensions Height 11 3 inches 28 7 cm Width 15 19 Slot 19 0 inches 48 3 cm 11 slot 11 4 inches 28 9 cm 6 Slot 7 6 inches 19 3 cm...

Страница 8: ...Slot Chassis Mounting Dimensions Figure 2 6 Slot Chassis Mounting Dimensions 0 7 inches 1 8 cm 0 3 inches 0 8 cm 8 0 inches 20 3 cm 7 5 inches 19 1 cm 18 5 inches 47 0 cm 5 1 inches 12 9 cm 0 3 inches...

Страница 9: ...9 Figure 3 11 Slot Chassis Mounting Dimensions 8 9 inches 22 6 cm 1 3 inches 3 2 cm 0 3 inches 0 8 cm...

Страница 10: ...circuit for example power strips Power Connections The main connector block on the front panel of the power supply see Figure 4 connects to an 8 pin UL approved detachable terminal block The terminal...

Страница 11: ...n 6 No Connection 7 Safety Ground 8 Figure 4 Input Connection Block Pin Signals and Retaining Screw Locations Note For model 3000DCPWR and TASDCPWR the DC Return and the BPEXTV Return are tied togethe...

Страница 12: ...in Table 1 must not exceed 10 Amperes The same rules apply to the 24 VDC Power Supply module except that the BPEXTV on Main Terminal Block must be always wired Table 1 Example Chassis Current Consumpt...

Страница 13: ...upply module to the chassis and then tighten the retaining screws 6 Reconnect the chassis fan cables 7 Reconnect the main power input cables Refer to Figure 5 and Figure 6 for the AC Power Supply fuse...

Страница 14: ...rated 10 A 250 V Littelfuse type 216010 Littelfuse type 216010 BPEXTV 24 VDC Fuse F2 F4 5 x 20 mm rated 10 A 250 V 5 x 20 mm rated 10 A 250 V Littelfuse type 216010 Littelfuse type 216010 Chassis Fan...

Страница 15: ...ly Figure 9 Chassis Fan Power Cable I O Cards When you insert an I O card make sure that you properly align the card in the supporting card guides and then gently slide the card forward into the matin...

Страница 16: ...shielded Ethernet cables with four twisted pair wires and RJ 45 tips These cables are limited to a maximum length of 328 feet 100 meters 3000 R2 and 3100 R2 Systems Ethernet Cabling Table 2 Ethernet...

Страница 17: ...2 1 Single 16 3000D 00 2D 1 2 1 Dual 12 3000D 00 3 2 1 1 Single 17 3000D 00 3D 2 1 1 Dual 13 3000D 00 7 1 2 2 Single 15 3000D 00 7D 1 2 2 Dual 11 3000D 00 8 2 1 2 Single 16 3000D 00 8D 2 1 2 Dual 12 3...

Страница 18: ...0 Single 18 SIL 3000 Remote Chassis Number of Chassis Number of Node Processors in Each Chassis Number of Chassis Processors in Each Chassis Chassis Power Supply Type Number of Available Slots for I...

Страница 19: ...8 2 1 2 Single 16 3100D 00 8D 2 1 2 Dual 12 3100 Micro Series CPU Nodes Number of Chassis Number of Micro Processors in Each Chassis Number of Chassis Processors in Each Chassis Chassis Power Supply...

Страница 20: ...O Switch B 3200T Processor Domain Node Rack 0 J1 X J2 X Domain Node Rack 0R J1 X J2 X Domain Node Rack 1 J1 X J2 X Domain Node Rack 1R J1 X J2 X Domain Node Rack 2 J1 X J2 X Domain Node Rack 2R J1 X...

Страница 21: ...X J2 X J3 X J4 X Domain Node Rack 0R J1 X J2 X J3 X J4 X Domain Node Rack 1 J1 X J2 X J3 X J4 X Domain Node Rack 1R J1 X J2 X J3 X J4 X Domain Node Rack 2 J1 X J2 X J3 X J4 X Domain Node Rack 2R J1 X...

Страница 22: ...D5 D 1 2 Dual 13 3200T 00 D6 D 1 2 Single 17 3200T 00 D7 D 2 1 Single 18 3200T 00 D8 D 2 2 Dual 13 3200T 00 D9 D 2 2 Single 17 3200T 00 D18 D 2 1 Single 10 3200T 00 D19 D 2 1 Dual 14 3200T 00 D20 D 2...

Страница 23: ...00 C27 D 5 2 1 Single 5 Triple Redundant 3200T 00 C7 T 18 3 1 Single 18 3200T 00 C8 T 14 3 1 Dual 14 3200T 00 C9 T 17 3 2 Single 17 3200T 00 C10 T 13 3 2 Dual 13 3200T 00 C21 T 10 3 1 Single 10 Quad...

Страница 24: ...24 Diagnostic Information The Chassis Info object reports diagnostic information for the Chassis Processor configured in its Property Manager display Properties...

Страница 25: ...n the left Primary power supply Chassis Power Supply2 Errors Boolean variable can be used to determine any failure on the right Secondary power supply If the value of this variable is True then it ind...

Страница 26: ...ode to chassis communications The chassis processor redundancy increases system availability I O Path RA Status Bool Variable can be used to determine any failure on the communications link between th...

Страница 27: ...or require a tool to open To assure compliance with the EMC requirements the equipment must be housed in an enclosure equipment cabinet rack that provides EMC shielding Compliance testing was perform...

Страница 28: ...limited to lead in solder and lithium in batteries 11 Prior to storage or shipping the equipment must be packaged in accordance with the following guidelines Inventory all items and inspect all compo...

Страница 29: ...ucted RF Immunity 150 kHz to 80 MHz at 10 V IEC 61000 4 6 Pulsed Magnetic Field 300 A m IEC 61000 4 9 Modules can be ordered with optional HumiSeal conformal coating In this case the modules can be in...

Страница 30: ...sumed reasonably careful in dealing with obvious hazards CE Conformit Europ enne EMC Electro Magnetic Compatibility EMI Electro Magnetic Interference EC European Community EN European Norm ESD Electro...

Отзывы: