16
Ethernet Switches
The 3000/06 Atom Node Processors and 3200/3201 Node/Chassis Processor require industrial-quality 1-
GB TX Ethernet Switches. The 3000/01 Chassis Processors, the 3000/02-004 Modbus TCP Cards, and
Distributed I/O Cards require industrial-quality 100-Base TX Ethernet Switches. Ethernet switches must
not re-compute the packet CRCs. While the Host Ethernet switches can be managed, I/O Ethernet
switches connected to the RTP3000 TAS shall be unmanaged. RTP recommends STP Category 5 (EIA
568B, Cat 5), shielded Ethernet cables with four twisted-pair wires and RJ-45 tips. These cables are
limited to a maximum length of 328 feet (100 meters).
3000/R2 and 3100/R2 Systems
Ethernet Cabling
Table 2: Ethernet Cabling Matrix
Description
Redundant ID
Ethernet
Port
Host
Switch
A
I/O
Switch
B
I/O
Switch
C
I/O
Switch
D
Node Processor
Single (Non-redundant)
J1
X
J2
X
J3
X
J4
X
A
J1
X
J2
X
J3
X
J4
X
B
J1
X
J2
X
J3
X
J4
X
C
J1
X
J2
X
J3
X
J4
X
D
J1
X
J2
X
J3
X
J4
X
Chassis Processor
Main (00-15)
J1
X
J2
X
Redundant (00R - 15R)
J1
X
J2
X
MODBUS TCP/IP
Main (32-47)
J3
X
J4
X
Redundant (32-47)
J3
X
J4
X
2-Channel Servo
Main (32-63)
J1
X
J2
X
Redundant (32-63)
J1
X
J2
X
8-Channel Counter
Main (32-63)
J1
X
J2
X
Redundant (32-63)
J1
X
J2
X