Wiring diagram 

See Appendix  

 

3

 

Commissioning 

Commissioning is only possible if the installation is correct as in cap.2.1 wiring diagram described. 

If delivered with an actuator and valve, the controller is factory commissioned. A new initialisation is not necessary. 

The controller is ready to operate. 

 

By retro-fitting in an actuator or changing the controller or the potentiometer, a new initialisation will be necessary. 

 

To initialise the controller, the LED                must be flashing. To make it flash, delete initialisation data (Reset) (see cap. 3.1). 

 

1.4.1

 

Delete initialisation data (Reset) 

Before a new initialisation can be performed, the existing data must be deleted. 

Deleting the existing data: 

 

 

 

 

 

 

 

 

 

 

Press all 3 keys together longer than 10 sec. (All LEDs illuminate). 

 

 

 

After all LEDs illuminate for  2 sec. the service LED is flashes 

 

. The controller waits for password input, to start the automatic 

initialisation. 

 

2.4.1

 

Initialisation 

The following things must be done exactly for correct initialisation. 

 

1.

 

Potentiometer should be adjusted as described (Section 2) 

2.

 

Switch manual mode on (see cap. 4.1 manual mode) 

3.

 

Enter password 

4.

 

Drive valve to middle position (+/- 20%). 

5.

 

Switch manual mode off, initialisation starts automatically. 

6.

 

Power off after initalisation, power on RE3446 in hand mode 

7.

 

Switch into automatic mode 

 

 

 

3.4.1

 

non-monitored manual operation 

After entering the correct password, the valve can be operated via the keys "OPEN" and "CLOSE". Drive the valve to the middle 

po/- 20%. It is not possible to start the initialisation near the end positions. 

 

 

 

 

 

 

Содержание RE3446

Страница 1: ...onen 2 2 Montage und Anschluß 2 3 Inbetriebnahme 3 4 Betriebsarten Stellungsregler 5 5 Funktionsbeschreibung 5 1 General Information 10 2 Installation and connection 10 3 Commissioning 11 4 Operation modes 13 5 Description of function 13 1 Общая информация 18 2 Установка и подключение 18 3 Ввод в эксплуатацию 19 4 Режимы работы 21 5 Описание функций 21 1 Elektrischer Anschluß Electric Connection Э...

Страница 2: ...bei nachträglichem Einbau Motor Potentiometer Eingangs und Rückmeldesignal wie im Anhang Elektrischer Anschluß beschrieben an Das Potentiometer muß so justiert werden daß bei geschlossenem Ventil 0 Hub ca 10 des ohmschen Wertes zwischen Klemme 62 und 63 gemessen werden können Bei geöffnetem Ventil sollten ca 90 des ohmschen Wertes erreicht werden Bei gedrehtem Wirksinn müssen diese Werte an Klemme...

Страница 3: ...löscht werden Löschen der aktuellen Daten Halten sie alle 3 Tasten gleichzeitig länger als 10s gedrückt bis alle LEDs leuchten Nachdem alle LEDs für ca 2 sek an waren blinkt die LED Der Regler erwartet eine Passworteingabe um mit der Initialisierung starten zu können 3 2 Initialisierung Zur Initialisierung sind folgende Schritte notwendig und genau zu beachten 1 Potentiometer wie oben beschrieben ...

Страница 4: ...startet Initialisierung automatische Initialisierung läuft Passwort eingeben siehe unten Passwort ok ja aus nein nein Manuelle Hubbegrenzung optional drücken Hub 100 bestimmen Alle LEDs 3 sek an 4 20mA Alle LEDs 3 Sek an 4 20mA drücken Hub 0 bestimmen Antriebsvermessung Passwort Eingabezeit max 10s Alle LEDs 3 sek an 4 20mA drücken an an unüberwachter Handbetrieb aktiv Alle 3 Taster gleichzeitg dr...

Страница 5: ...s System muß dazu einmalig initialisiert werden Die Ventilstellung wird als 4 20mA Signal ausgegeben Die Endlagen Hub 0 und Hub 100 werden durch Endschalter automatisch erkannt Der Antrieb kann durch Umschalten von Automatik auf Handbetrieb mit Hilfsenergie manuell gefahren werden 5 1 Galvanisch getrennte Rückmeldung Das Rückmeldesignal 4 20mA wird auf den Hub automatisch bei der Initialisierung a...

Страница 6: ...rt wird verkleinert Antrieb fährt in Richtung Hub 0 Stellen sie den Wert so ein daß die 0 Position des Ventils übereinstimmt mit dem 0 4mA Eingangssignal Der Antrieb muss die 0 Position erreichen wenn 0 4 mA am Eingang anliegen Abgleich Eingang Verstärkung Bereich oder Legen Sie ein 20mA Signal am Stromeingang an und warten bis der Antrieb stehen bleibt Sollte die 100 Endlage nicht erreicht werden...

Страница 7: ...rückt halten Taste Auf drücken Rückmeldewert wird größer Taste Zu drücken Rückmeldewert wird kleiner Stellen Sie genau 4 mA ein Abgleich Span Verstärkung Bereich oder Legen Sie 20 mA am Stromeingang an und warten bis der Antrieb die 100 Endlage erreicht hat Taste Auf drücken Rückmeldewert wird größer Taste Zu drücken Rückmeldewert wird kleiner Stellen Sie genau 20 mA ein Kontrollieren Sie den 0 En...

Страница 8: ...gespeichert Der Regler arbeitet nun von 0 bis 100 Hub mit 4 12mA Eingangssignal Das Rückmeldesignal bleibt auf 4 20mA eingestellt 5 4 2 Splitrange von 12 20mA einstellen Taste Öffnen drücken Nach Betätigung der Öffnen Taste leuchten die LEDs 4 20mA Öffnen und Endlage für ca 2 Sekunden Splitrange Betrieb von 12 20mA ist jetzt eingestellt Trennen sie die Verbindung Brücke Die LED Init erlischt nach ...

Страница 9: ...A 11 8mA Fährt man wieder zurück fängt der Motor ab Sollwertvorgabe 11 6 mA wieder an zu laufen Manuelle Änderung der Totzone 1 mA Geber aus oder abgeklemmt ermöglicht das manuelle Ändern der Totzone 2 AUF oder ZU Taste betätigen Service LED leuchtet 3 LED erlischt nach ca 5 sek Nachdem der letzte Tastendruck erfolgt ist Totzone ist nun fest im EEProm abgespeichert Mit Taste AUF vergrößert man die...

Страница 10: ... mounting the controller into the actuator do the following Connect the motor potentiometer input signal and output signal as described in Cap The potentiometer must be adjusted so that if the valve is closed the value of the potentiometer is approximately 10 of the whole potentiometer value If the valve is completely open the value should be approximately 90 of the whole potentiometer value The p...

Страница 11: ...tion can be performed the existing data must be deleted Deleting the existing data Press all 3 keys together longer than 10 sec All LEDs illuminate After all LEDs illuminate for 2 sec the service LED is flashes The controller waits for password input to start the automatic initialisation 2 4 1 Initialisation The following things must be done exactly for correct initialisation 1 Potentiometer shoul...

Страница 12: ...econds flashes RE 3446 in operation Initialisation ok yes Drive valve to middle position 20 with and keys Handmode off starts initialisation auto initialisation is performed Enter password see below password ok yes off no no Manual stroke limitation optional push stroke 100 set All LEDs 3 sec on 4 20mA All LEDs 3 Sec on 4 20mA push stroke 0 set Measurement Password All LEDs 3 sec on 4 20mA push on...

Страница 13: ...s a microcontroller system Its job is to position the actuator by the commands of the master controller An initialisation for the first time is required to get the RE 3446 in operation The stroke limits 0 and 100 are recognised by limit switches The RE 3446 generates a retransmission signal 4 20mA for the stroke Manual operation is possible during power supply on 1 4 1 Galvanic isolated feedback T...

Страница 14: ...ep pressed step with key Open to make the input signal higher step with key Close to make the input signal lower adjust the signal exactly to the right valve position Adjust span Input signal or Connect 20mA signal to the input and wait until the controller position has stabilised Control the valve position If the position is not correct make a digital correction step with key Open to make the inp...

Страница 15: ...alve position If the feedback signal is not correct make a digital correction key hand auto keep pressed step with key Open to make the output signal higher step with key Close to make the output signal lower adjust the signal exactly to the desired output value Adjust span Output signal or connect 20mA signal to the input and wait as long as the controller stopped Control the valve position If th...

Страница 16: ...4 12mA is now set Disconnect the bridge The LED Init extinguishes after 2 seconds The changes are saved The controller now operates from 0 to 100 Stroke with 4 12mA input signal The feedback signal operates as before with 4 20mA 5 4 2 Set split range operation 12 20mA Press key Open Then the LEDs Open 4 20mA and Limit illuminate for 2 seconds Split range operation from 12 20mA is now set Disconnec...

Страница 17: ...eder zurück fängt der Motor ab Sollwertvorgabe 11 6 mA wieder an zu laufen Manuelle Änderung der Totzone 1 mA Geber aus oder abgeklemmt ermöglicht das manuelle Ändern der Totzone 2 AUF oder ZU Taste betätigen Service LED leuchtet 3 LED erlischt nach ca 5 sek Nachdem der letzte Tastendruck erfolgt ist Totzone ist nun fest im EEProm abgespeichert Mit Taste AUF vergrößert man die Totzone pro Tastendr...

Страница 18: ...плуатацию После установки контроллера на силовой привод необходимо выполнить следующие процедуры Подключите двигатель потенциометр входной и выходной сигналы как описано в приложении Электрическое подключение Потенциометр должен быть отрегулирован таким образом чтобы закрытому положению регулировочного вентиля соответствовал сигнал потенциометра величиной 10 от полного диапазона Когда же регулиров...

Страница 19: ...новременно все 3 клавиши и удерживайте их более 10 секунд При этом загораются все светодиодные индикаторы Через 2 секунды после включения всех индикаторов начнет мигать сервисный индикатор Контроллер находится в ожидании ввода пароля чтобы начать автоматическую инициализацию 3 2 Инициализация Для правильной инициализации контроллера необходимо в обязательном порядке произвести следующие процедуры ...

Страница 20: ...3446 8010 Einbau und Betriebsanleitung Installation and operating instructions Инструкции по установке и эксплуатации 07 2008 3 4 Блок схема инициализации ...

Страница 21: ...ючение напряжения 230 В переменного тока опция 24 В постоянного тока на контакты Z1 и Z2 Контакты Z1 и Z3 не соединены друг с другом силовой привод никак не реагирует на прерывание сигнала только при входных сигналах 4 20 мА и 2 10 В ПРИМЕЧАНИЕ Если величина входного сигнала падает ниже 2 мА или 1 В контроллер переходит в безопасное положение 5 Описание функций Контроллер RE 3446 относится к микро...

Страница 22: ...ней панели Настройка нуля Входной сигнал и или Подайте на вход сигнал например 4 мА и подождите не менее 5 секунд пока контроллер не стабилизируется Произведите пробное управление регулировочным вентилем Если положения вентиля недостаточно точные выполните цифровую корректировку нажмите и удерживайте клавишу Ручное Автомат с помощью клавиши Открытие произведите пошаговое увеличение величины входно...

Страница 23: ...ое Автомат с помощью клавиши Открытие произведите пошаговое увеличение величины выходного сигнала с помощью клавиши Закрытие произведите пошаговое уменьшение величины выходного сигнала Произведите точную настройку величины сигнала для правильного управления регулировочным вентилем Настройка длины хода Выходной сигнал или Подайте на вход сигнал 20 мА и подождите пока контроллер не стабилизируется П...

Страница 24: ...изация должен погаснуть сигнализируя о сохранении всех новых настроек Теперь контроллер работает на длине хода штока вентиля от 0 до 100 с величиной входного сигнала 4 12 мА При этом диапазон сигнала обратной связи остается без изменений 4 20 мА 5 4 2 Настройка управления с разделенным диапазоном 12 20 мА Нажмите клавишу Открытие При этом на 2 секунды загораются светодиодные индикаторы 4 20 мА Отк...

Страница 25: ...3446 8010 Einbau und Betriebsanleitung Installation and operating instructions Инструкции по установке и эксплуатации 07 2008 ...

Страница 26: ...т работать Ручное изменение мертвой зоны 1 Отключите или отсоедините миллиамперный датчик чтобы можно было произвести ручное изменение мертвой зоны 2 С помощью клавиши ОТКРЫТИЕ или ЗАКРЫТИЕ включите светодиодный индикатор Сервис 3 Примерно через 5 с после последнего нажатия клавиши светодиодный индикатор погаснет Теперь мертвая зона будет постоянно храниться в памяти контроллера С помощью клавиши ...

Страница 27: ... Ventil bleibt bei Signalbruch stehen Z1 connect to N Z2 connect to L1 means safety position 100 or Z3 connect to L1 means safety position 0 Z1 Z2 Z3 not connect Valve doesn t move PE N 65 L 66 68 69 Z2 Z1 Z3 POT 1 Обрыв провода Положение 0 4 20 мА 4 20 мА 0 10 В Выход 2 10 В N L 100 L 0 ЗАЗЕМЛЕНИЕ Вход K6 K4 K5 61 62 63 RE 3446 M A3 A1 A2 POT потенциометр Подключение Z1 к N Подключение Z2 к L1 оз...

Страница 28: ...free keys Potentiometer 200Ω to 5KΩ Feedback signal 4 20mA max 500Ω galvanic isolated 24V DC supply necessary Display LED s Switch step Relay contacts max 250V 50 60 Hz 2A Supply 24V 110V 230V 50 60 Hz 24V DC chosseable 1 5 VA Power loading 1 5 VA Terminal connect Snap terminals for 1 5mm2 solid wire or stranded wire with wire case Ambient temperature 10 C 50 C Технические данные Сигнал управления...

Отзывы: