0x1E
Embedded server error
An embedded service resulted in an error: This can mean
the Controller Slot, IP Address or Tag Name does not
match. The Tag is not defined in the Controller Scope
within the PLC, or the Tag does not have Read/Write
privileges.
0x1F
Vendor specific error
A vendor specific error has been encountered. The
Additional Code Field of the Error Response defines the
particular error encountered. Use of this General Error
Code should only be performed when none of the Error
Codes presented in this table or within an Object Class
definition accurately reflect the error
0x20
Invalid parameter
A parameter associated with the request was invalid.
This code is used when a parameter does not meet the
requirements of this specification and/or the
requirements defined in an Application Object
Specification
0x21
Write once value or medium already
written
An attempt was made to write to a write-once medium
that has already been written, or to modify a value that
cannot be changed once established
0x22
Invalid reply received
An invalid reply is received. This status code can serve for
other causes of invalid replies
0x23
Buffer Overflow
The message received is larger than the receiving buffer
can handle. The entire message was discarded.
0x24
Message format error
The format of the received message is not supported by
the server
0x25
Key failure in path
The key segment that was included as the first segment
in the path does not match the destination module. The
object specific status shall indicate which part of the key
check failed
0x26
Path size invalid
The size of the path which was sent with the Service
Request is either not large enough for all the Requests to
be routed to an object or too much routing data was
included
0x27
Unexpected attribute
An attempt was made to set an attribute that is not able
to be set at this time
0x28
Invalid member ID
The Member ID specified in the request does not exist in
the specified Class/Instance/Attribute
Real Time Automation, Inc.
32