Real Time Automation, Inc.
77
1-800-249-1612
Diagnostics
– BACnet MS/TP Slave
Select the
BACnet MS/TP Slave
in the dropdown menu on the Diagnostics Page. Additional diagnostic
information can be found by clicking the
Help
button.
NOTE
: This page will auto-refresh every five seconds with the latest data.
Clear All Values
- This will only affect displayed values.
1)
This will reset all displayed values back to zero and clear the Status Strings.
2)
If viewing BACnet MS/TP Slave, this will only clear the values for the BACnet MS/TP Slave section of
the gateway.
Device Status:
1)
Connected
–
The gateway is connected to a BACnet MS/TP master.
2)
Not Connected
–
The gateway is not connected to a BACnet MS/TP master.
3)
Error: Timeout
–
If the Inactivity Timeout is set to non-zero, the gateway has not received a
read/write request in the amount of time specified by the inactivity timeout.
LED Status:
1)
Good Communication (Solid Green) - Connected to a BACnet MS/TP master.
2)
Never Connected (Blink Green)
–
Gateway has never been connected to a BACnet MS/TP master.
3)
Connection Timeout (Blink Red)
–
If the Inactivity Timeout is set to non-zero, the gateway has lost a
connection to the BACnet MS/TP master due to no Read/Write Requests received.
4)
Port Not Configured (Solid Red)
–
Port Configured in the BACnet MS/TP Slave configuration page is
not enabled in the Port Configuration page.